31
SECTION 1 – INSTALLATION
FORM 145.32-IOM5
ISSUE DATE: 04/08/2019
1
TABLE
16 -
DSH096C – CONDENSER F
AN PERFORMANCE
OUTDOOR
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive +3 HP
Optional Hi-Static Drive +3 HP
6100
516
1.53
572
1.79
623
2.06
672
2.33
718
2.60
762
2.88
805
3.16
TABLE
17 -
DSH120C – SUPPL
Y AIR BLOWER PERFORMANCE
SUPPL
Y
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive + 3 HP
Optional Hi-Static Drive + 2.0 HP
Field Supplied Drive
3
3200
486
0.60
548
0.73
604
0.87
657
1.01
706
1.15
753
1.30
800
1.48
847
1.68
885
1.89
923
2.07
3600
524
0.79
580
0.94
633
1.09
683
1.24
730
1.40
775
1.56
817
1.73
867
2.13
905
2.29
941
2.45
4000
568
1.05
619
1.21
668
1.37
715
1.54
759
1.71
802
1.88
843
2.06
882
2.24
920
2.43
962
2.76
4400
616
1.37
664
1.54
709
1.72
753
1.90
795
2.08
835
2.27
874
2.46
911
2.66
948
2.86
983
3.06
4800
660
1.72
704
1.91
747
2.10
788
2.29
827
2.49
865
2.69
902
2.90
938
3.1
1
-
-
-
-
NOTES:
1.
Blower performance includes evaporator coil and 2-inch filters.
2.
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur
. Decrease airflow downward as necessary
.
3.
For external static requirements outside of factory supplied drives consult factory for appropriate drive information.
TABLE
18 -
DSH120C– CONDENSER F
AN PERFORMANCE
OUTDOOR
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive +3 HP
Optional Hi-Static Drive +5 HP
6400
691
1.98
747
2.24
800
2.52
850
2.80
898
3.08
945
3.36
990
3.66
1033
3.96
1075
4.26