30
FORM 145.32-IOM5
ISSUE DATE: 04/08/2019
SECTION 1 – INSTALLATION
TABLE
13 -
DSH060C – SUPPL
Y AIR BLOWER PERFORMANCE
SUPPL
Y
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
1
0.0
0.1
0.2
0.3
0.4
0.6
0.8
1.0
1.2
1.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Low Static Drive
3
Factory Drive +1.0 HP
Hi-Static Drive + 1.5 HP
1600
511
0.25
562
0.30
612
0.34
658
0.38
703
0.43
786
0.50
863
0.59
935
0.68
1002
0.78
1066
0.86
1800
575
0.36
620
0.41
666
0.45
708
0.50
749
0.55
826
0.64
898
0.74
967
0.84
1031
0.94
1092
1.04
2000
637
0.50
680
0.55
720
0.60
759
0.65
797
0.70
869
0.80
937
0.91
1001
1.01
1063
1.13
1121
1.24
2200
699
0.66
739
0.71
776
0.78
813
0.83
847
0.89
914
1.00
978
1.1
1
1039
1.23
1098
1.34
-
-
2400
765
0.86
800
0.93
835
0.99
868
1.04
901
1.10
964
1.23
1024
1.35
1082
1.48
-
-
-
-
NOTES:
1.
Blower performance includes evaporator coil and 2-inch filters.
2.
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur
. Decrease airflow downward as necessary
.
3.
Field supplied low static drive.
TABLE
14 -
DSH060C – CONDENSER F
AN PERFORMANCE
OUTDOOR
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive
Hi-Static Drive
2800
567
0.60
632
0.71
694
0.83
751
0.95
806
1.08
858
1.21
907
1.33
TABLE
15 -
DSH096C – SUPPL
Y AIR BLOWER PERFORMANCE
SUPPL
Y
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Low Static Drive
3
Standard Factory Drive + 1.5HP
Optional Hi-Static Drive + 2.0 HP
2400
458
0.31
543
0.42
619
0.53
690
0.64
752
0.75
812
0.87
878
1.04
935
1.21
985
1.40
1038
1.51
2800
503
0.44
580
0.57
650
0.69
715
0.83
776
0.97
831
1.1
1
885
1.27
942
1.45
998
1.65
1045
1.77
3200
542
0.60
613
0.74
678
0.88
739
1.02
796
1.18
847
1.33
903
1.49
960
1.66
1017
1.83
1072
2.01
3600
607
0.85
670
1.00
730
1.16
786
1.32
839
1.48
890
1.66
939
1.83
980
1.99
-
-
-
-
4000
660
1.12
718
1.29
773
1.46
826
1.64
876
1.82
924
2.00
-
-
-
-
-
-
-
-
NOTES:
1.
Blower performance includes evaporator coil and 2-inch filters.
2.
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur
. Decrease airflow downward as necessary
.
3.
Field supplied low static drive.