29
SECTION 1 – INSTALLATION
FORM 145.32-IOM5
ISSUE DATE: 04/08/2019
1
TABLE
10 -
DSH024C – CONDENSER F
AN PERFORMANCE
OUTDOOR
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
0.0
0.2
0.4
0.6
0.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive
Hi-Static Drive
2100
542
0.31
631
0.40
717
0.49
799
0.58
875
0.68
TABLE
1
1 -
DSH048C – SUPPL
Y AIR BLOWER PERFORMANCE
SUPPL
Y
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
1
0.0
0.1
0.2
0.3
0.4
0.6
0.8
1.0
1.2
1.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Low Static Drive
3
Factory Drive +0.75 HP
Hi-Static Drive + 1.0 HP
1200
381
0.1
1
451
0.14
511
0.16
569
0.20
620
0.24
717
0.30
803
0.36
882
0.44
954
0.51
1023
0.60
1400
447
0.18
506
0.21
561
0.24
612
0.28
660
0.31
750
0.39
831
0.46
906
0.55
977
0.64
-
-
1600
511
0.25
562
0.30
612
0.34
658
0.38
703
0.43
786
0.50
863
0.59
935
0.68
1002
0.78
-
-
1800
575
0.36
621
0.41
666
0.45
708
0.50
749
0.55
826
0.64
898
0.74
967
0.84
-
-
-
-
2000
637
0.50
680
0.55
720
0.60
760
0.65
797
0.70
869
0.80
937
0.91
1001
1.00
-
-
-
-
NOTES:
1.
Blower performance includes evaporator coil and 2-inch filters.
2.
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur
. Decrease airflow downward as necessary
.
3.
Field supplied low static drive.
TABLE
12 -
DSH048C – CONDENSER F
AN PERFORMANCE
OUTDOOR
CFM
AV
AILABLE EXTERNAL
ST
ATIC PRESSURE – IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Factory Drive
Hi-Static Drive
2400
503
0.40
577
0.50
645
0.60
708
0.71
767
0.82
822
0.93
875
1.05