background image

NOTE:

  An alternate method to using the ST-10 is to use two ST-5 sampling tubes. Remove the flange from one of the tubes and install as described 

above. After the installation, use electrical tape to close off some of the sampling holes so that there are a total of 10 to 12 holes spaced as 
evenly as possible across the width of the duct.

NOTE:

  Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch 

floor flange (available at most plumbing supply stores) may be used to fasten the sampling tube to the other side of the duct. When using 
the flange/connector mounting technique, drill a 1-inch to 1

1

⁄ 4

-inch hole where the flange will be used. 

[5] Install The Filters 

To install the sampling tube filters, simply push the filters into the sampling and exhaust tube holes, as shown in Figure 6. If a metal sampling tube 
is used, install the filters into the tube end.

[6] Field Wiring Installation Guidelines

All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction. Proper wire gauges should be used. 
The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper 
connections can prevent a system from responding properly in the event of a fire.

CAUTION

Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated. Visually inspect the filters at least quarterly; 
inspect them more often if the dust accumulation warrants it. See Section [9.1.2] for more information. Replacement filters can be ordered (filter P/N 
F36-09-11).

For signal wiring, (the wiring between detectors or from detectors to auxiliary devices), it is usually recommended that single conductor wire be no 
smaller than 18 gauge. The duct smoke detector terminals accommodate wire sizes up to 12 gauge. The last foot of conduit should be flexible conduit 
(available in electrical supply houses), which facilitates easier installation and puts less strain on the conduit holes in the housing. Solid conduit con-
nections may be used if desired.

Smoke detectors and alarm system control panels have specifications for 
Signaling-Line Circuit (SLC) wiring. Consult the control panel manufactur-
er’s specifications for wiring requirements for the particular model control 
panel being used before wiring the detector loop. 

The DH300PL detector is designed for ease of wiring. The housing pro-
vides a terminal strip with clamping plates.  Wiring connections are made 
by stripping about 3/8-inch of insulation from the end of the wire, sliding 
the bare end under the plate, and tightening the clamping plate screw. 

Two LEDs on each duct smoke detector may light, if programmed by the 
system control panel, to provide a local, visible indication.  Remote LED 
annunciator capability is available as an option. Each duct smoke detec-
tor can only be wired to one remote accessory.

Johnson Controls fire panels offer different feature sets across different panel models.  As a result, certain features of the DH300PL may be available 
on some control panels, but not on others.  The possible features available in the DH300PL, if supported by the control panel are:  
1.  Panel  controls  the  LED  operation  on  the  duct  smoke  detector.    Operational  modes  are  RED  blink,  RED  continuous, 

GREEN blink, GREEN continuous, and off.  

2.  The remote output may be synchronized to the LED operation or controlled independent of the LEDs. 

Please refer to the operation manual for the UL listed control panel for specific operation of the DH300PL

WIRING INSTRUCTIONS

Disconnect power from the communication line before installing the DH300PL duct smoke detectors.  

Wire the DH300PL duct smoke detector per the Control Panel 
Installation Manual and Figures 9, 10 or 11. Set the desired 
address on the sensor board code wheel address switches

.

J500-42-00 

I56-2198-003R

Figure 6. Sampling tube filter installation:

H0138-00

Содержание DH300PL

Страница 1: ...also a remote alarm output for use with auxiliary devices The DH300PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT The DH300PL Duct Smoke Detector consists of the following items See Figure 1 DH300PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Figu...

Страница 2: ...emplate supplied Affix the template to the duct at the desired mounting location Make sure the tem plate lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 2 1 Sampling Tube Installation for Ducts Less Than 11 2 Feet Wide see Figure 2 1 Remove the front cover 2 Slide the plastic sampling tube into the housing bushing and extend it the full widt...

Страница 3: ...12 ft 2 4 to 3 7 m ST 10 Must extend a minimum of 2 3 the duct width J500 42 00 3 I56 2198 003R SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK Figure 3 Installation of foam gaskets over sampling tube bushings Figure 5 Tube mounting configurations with varying air flow direction SAMPLING TUBE END CAP AIR HOLES ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Figure 4 Air duct detector sampli...

Страница 4: ...ate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in the housing Solid conduit con nections may be used if desired Smoke detectors and alarm system control panels have specifications for Signaling Line Circuit SLC wiring Consult the control panel man...

Страница 5: ...sing Aerosol Smoke This test is intended for low flow systems 100 500 FPM If the air speed is greater than 500 FPM use a conventional manometer to measure differ ential pressure between the sampling tubes as described in 9 1 1 Drill a 1 4 hole 3 feet upstream from the duct smoke detector With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray ae...

Страница 6: ...nce exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests 9 2 1 Standby And Trouble Standby If programmed by the system control panel look for the presence of the flashing LEDs through the transparent housing cover The LED will flash with each communication Trouble If programmed by the system control pan...

Страница 7: ...tion facilitates test of the alarm capability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The detector is self restoring when the accessory test stimulus is removed Verify that the system control panel has reset 9 2 3 Sensitivity Tests Notify the proper authorities that the smoke detector system is undergoing maintenance and that...

Страница 8: ... Any smoke detector fire alarm equipment or any component of that system which fails shall be repaired or replaced as soon as possible Please refer to insert for the Limitations of Fire Alarm Systems 10 Board Replacement 10 1 Sensor Board Replacement 1 Remove the two sensor board mounting screws 2 Pull gently on the board to remove it 3 To replace the board align the board mounting features holes ...

Отзывы: