background image

the sampling tube is mounted so that the arrow points into the air flow 
(see Figure 4). Figure 5 shows the various combinations of tube mounting 
configurations with respect to air flow. Mounting the detector housing in a 
vertical orientation is acceptable, provided that a metal sampling tube is 
used and the air flows directly into the sampling tube holes as indicated 
in Figure 4.

[4.1] Installation For Ducts Greater Than 1

1⁄ 2

 Feet But Less Than 

8 Feet Wide

1. 

If the tube is longer than the width of the air duct,

 drill a

 

3

⁄ 4

 hole in the 

duct opposite the hole already cut for the sampling tube. Make sure the 
hole is 1

 to 2

 below the inlet hole on the opposite side of the duct to 

allow moisture drainage away from the detector. 

If the tube is shorter 

than the width of the air duct,

 install the end cap into the sampling tube 

as shown in Figure 4. Sampling tubes over 3 ft. long must be supported 
at the end opposite the duct smoke detector.

2.  Slide the tube into the housing bushing that meets the air flow first. 

Position the tube so that the arrow points into the air flow, as shown 
in Figure 4. 

3.  Secure the tube flange to the housing bushing with two #6 self-tapping 

screws.

4.  For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct. If there are more than 2 holes in 
the  section  of  the  tube  extending  out  of  the  duct,  select  a  different 
length using Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1

 to 2

 of the tube extend outside the duct. 

Plug this end with the end cap and tape closed any holes in the pro-
truding section of the tube. Be sure to seal the duct where the tube 
protrudes.

NOTE:

 The sampling tube end cap is critical to the proper operation of 

the duct smoke detectors. The end cap is needed to create the 
proper air flow to the sensor of the duct smoke detector.

Table 1. Sampling tubes recommended for different 
duct widths:

Outside Duct Width 

Sampling Tube Recommended*

 

1 to 2 ft. (0.3 to 0.6 m) 

ST-1.5

 

2 to 4 ft. (0.6 to 1.2 m) 

ST-3

 

4 to 8 ft. (1.2 to 2.4 m) 

ST-5

 

8 to 12 ft. (2.4 to 3.7 m) 

ST-10

*Must extend a minimum of 

2

3

 the duct width

J500-42-00 

I56-2198-003R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over  
sampling tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE:  Only metal sampling tubes can be installed in 

orientations C and D. 

H0107-00

H0108-02

H0109-01

[4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

  To install sampling tubes in ducts more than 8 feet wide, work 

must be performed inside the air duct. Sampling of air in ducts 
wider than 8 feet is accomplished by using the ST-10 sampling 
tube. If the tube is shorter than the width of the air duct, install 
the end cap into the sampling tube as shown in Figure 4 and 
support the end opposite the duct smoke detector.

Install the sampling tube as follows:

1.  Drill a 

3

⁄4

-inch hole in the duct directly opposite the hole already drilled 

for the sampling tube. Make sure the hole is 1

 to 2

 below the inlet 

hole on the opposite side of the duct to allow for moisture drainage.

2.  Slide the sampling tube with the flange into the housing bushing that 

meets the air flow first. Position the tube so that the arrow points into 
the air flow. Secure the tube flange to the housing bushing with two 
#6 self-tapping screws.

3.  From inside the duct, couple the other sections of the sampling tube 

to the section already installed using the 

1

⁄ 2

-inch conduit fittings sup-

plied. Make sure that the holes on both of the sampling tubes are lined 
up and facing into the air flow.

4.  Trim the end of the tube protruding through the duct so that 1

 to 2

 of 

the tube extend outside the duct. Plug this end with the end cap and 
tape closed any holes in the protruding section of the tube. Be sure to 
seal the duct where the tube protrudes.

Содержание DH300PL

Страница 1: ...also a remote alarm output for use with auxiliary devices The DH300PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT The DH300PL Duct Smoke Detector consists of the following items See Figure 1 DH300PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Figu...

Страница 2: ...emplate supplied Affix the template to the duct at the desired mounting location Make sure the tem plate lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 2 1 Sampling Tube Installation for Ducts Less Than 11 2 Feet Wide see Figure 2 1 Remove the front cover 2 Slide the plastic sampling tube into the housing bushing and extend it the full widt...

Страница 3: ...12 ft 2 4 to 3 7 m ST 10 Must extend a minimum of 2 3 the duct width J500 42 00 3 I56 2198 003R SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK Figure 3 Installation of foam gaskets over sampling tube bushings Figure 5 Tube mounting configurations with varying air flow direction SAMPLING TUBE END CAP AIR HOLES ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Figure 4 Air duct detector sampli...

Страница 4: ...ate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in the housing Solid conduit con nections may be used if desired Smoke detectors and alarm system control panels have specifications for Signaling Line Circuit SLC wiring Consult the control panel man...

Страница 5: ...sing Aerosol Smoke This test is intended for low flow systems 100 500 FPM If the air speed is greater than 500 FPM use a conventional manometer to measure differ ential pressure between the sampling tubes as described in 9 1 1 Drill a 1 4 hole 3 feet upstream from the duct smoke detector With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray ae...

Страница 6: ...nce exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests 9 2 1 Standby And Trouble Standby If programmed by the system control panel look for the presence of the flashing LEDs through the transparent housing cover The LED will flash with each communication Trouble If programmed by the system control pan...

Страница 7: ...tion facilitates test of the alarm capability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The detector is self restoring when the accessory test stimulus is removed Verify that the system control panel has reset 9 2 3 Sensitivity Tests Notify the proper authorities that the smoke detector system is undergoing maintenance and that...

Страница 8: ... Any smoke detector fire alarm equipment or any component of that system which fails shall be repaired or replaced as soon as possible Please refer to insert for the Limitations of Fire Alarm Systems 10 Board Replacement 10 1 Sensor Board Replacement 1 Remove the two sensor board mounting screws 2 Pull gently on the board to remove it 3 To replace the board align the board mounting features holes ...

Отзывы: