Connecting Serial Controllers to the P2000 Comark Server Running Software Version 3.11 

Preliminary – This information may change. 

Table 4: Tools Required to Install Wires in MTA Connectors 

Johnson Controls 

Part Number 

AMP Part 

Number 

Tool Description 

96-0014 

58074-1 

Pistol-grip Handle Assembly 

96-0015 

58246-1 

MTA-100 Modular Head (used in pistol-grip tool) 

96-0010-01 

59803-1 

MTA-100 Maintenance Hand Tool (inserts one wire at a time) 

Cabling between PC232-S4-X Converter Board and Connector Box 

Create the cables to connect the connector box and the PC232-S4-X converter board using 

#22, 4- and 5-conductor shielded cabling. We recommend Belden® 9940 and 9941, 

respectively. The cable length must not exceed 25 feet (7.6 m). 
For systems with one PC232-S4-X converter board, use 4-conductor cable to connect ports 2, 

3, and 4 of the FPI connector box to the PC232-S4-X PCB connectors J3, J4, and J5, 

respectively. Use the 25-pin connectors supplied with the kit on ports 2, 3, and 4 of the 

connector box. Use the red 4-pin connectors supplied with the kit on the PC232-S4-X PCB 

end. A 5-conductor cable connects port 1 of the connector box to connector J2 on the PC232-

S4-X PCB. Use the remaining 25-pin connector for port 1 of the connector box and the only 

red 5-pin connector for J2 of the PC232-S4-X PCB. (See Figure 4 for the wiring diagram.) 
For systems with two PC232-S4-X converter boards, use 4-conductor cable to connect ports 

2 through 8 of the FPI connector box to both PC232-S4-X PCB connectors J3, J4, and J5, 

respectively. Use the 25-pin connectors supplied with the kit on ports 2 through 8 of the 

connector box. Use the red 4-pin connectors supplied with the kit on both PC232-S4-X PCB 

ends. Use a red 5-pin connector for connector J2 on the second PC232-S4-X PCB. Only four 

wires connect to the 5-pin connector attaching to J2 of the second PC232-S4-X PCB. A  

5-conductor cable connects port 1 of the connector box to connector J2 on the first PC232-

S4-X PCB. Use the remaining 25-pin connector for port 1 of the connector box and 

remaining red 5-pin connector for J2 of the first PC232-S4-X PCB. (See Figure 4 for the 

wiring diagram.) 

Cabling between PC232-S4-X and the Serial Controllers 

Construct the cables to connect the PC232-S4-X and the serial controllers using #22, two 

twisted pair cabling (Belden 8723 recommended). See Figure 4 for the wiring diagram. The 

diagram shows the pin-to-pin connections for the serial controllers. The maximum cable 

length is 4,000 feet (1,219 m) total loop distance. 
Install a Lightning Transient Suppressor at each end of every cable between the PC232-S4-X 

and the serial controller that is exposed to an area where lightning may strike directly or 

nearby. This includes any above-ground cable runs between buildings. We recommend the 

Johnson Controls Model TS10/TS11 Transient Suppressor for this purpose. 

Содержание D600-AP

Страница 1: ...u may need the following equipment Digi AccelePort serial adapter board installed at the P2000 server PC232 converter S321 DIN and P900 controllers excluded B B Electronics RS 232 to RS 485 converter model 485OT9L S321 DIN controllers using serial communications only Note The S321 DIN can use serial communications with the RS 232 to RS 485 converter or it can communicate via IP using the Digi One ...

Страница 2: ...0 and P900 including how to connect the controllers to the system and establish communications These components are not supplied and must be purchased separately Note This section does not include instructions for installing S321 DIN controllers For information on connecting these controllers see Connecting S321 DIN Controllers on page 13 Note The sections on the current loop converter do not appl...

Страница 3: ...ons on installing the board Note When configuring the AccelePort name your devices as COM1 COM2 and so on The AccelePort does not support other names AccelePort to PC232 Installation The AccelePort module provides additional RS 232 serial ports The module is connected to the AccelePort PCI board in the server by a DB44 RS 232 cable Connect one end of the DB44 cable to the AccelePort COM port and t...

Страница 4: ...ld Panel Interface board are the same as for the computers The specifications of the current loop converter are listed in Table 1 Table 1 Current Loop Converter Specifications Item Specification Number of Channels per PCBA 4 Input Output RS 232 to current loop and current loop to RS 232 Number of Serial Controllers per Channel 16 Ambient Temperature 32 to 122 F 0 to 50 C Relative Humidity 0 to 95 ...

Страница 5: ...move the PC232 S4 X board from the enclosure by disconnecting the power cable from J6 and the tamper switch cable from J1 Then remove the four screws securing the PC232 S4 X board to the enclosure 2 Set aside the screws in a safe place so you can use them to replace the board into the enclosure 3 Hold the enclosure in the desired location on the mounting surface and use as a template to mark the l...

Страница 6: ...tors and plug them into the mating connectors For Canadian installations refer to the Canadian Electric Code C22 1 Take into account the following requirements for cable routing Route power lines separately from data lines These lines can be a standard 3 wire stranded 16 AWG UL listed CSA approved line cord used with UL listed CSA approved strain relief All low level input cables system data alarm...

Страница 7: ...r board to enclosure wall Screw 6 32x1 2 inch 6 Used to ground wire shields to enclosure wall Two PC232 S4 X Units This kit is used for the installation of two PC232 S4 X boards The cable connections of the kit complete the interface of the serial controllers to the server Table 3 Connector Kit supplied with two PC232 S4 X units Type Quantity Mating Connector Function Conn 25 pin MTA 100 8 Ports 1...

Страница 8: ...wiring diagram For systems with two PC232 S4 X converter boards use 4 conductor cable to connect ports 2 through 8 of the FPI connector box to both PC232 S4 X PCB connectors J3 J4 and J5 respectively Use the 25 pin connectors supplied with the kit on ports 2 through 8 of the connector box Use the red 4 pin connectors supplied with the kit on both PC232 S4 X PCB ends Use a red 5 pin connector for c...

Страница 9: ...ty of the grounding circuit periodically Testing Communications This test assumes that all hardware and software is installed Refer to the P2000 Server Workstation Software Installation Manual Part No 24 10618 120 for instructions Monitor the status of loops controllers and terminals by using the P2000 System Status window located in the System menu Refer to the P2000 Software User Manual Part No ...

Страница 10: ...Connecting Serial Controllers to the P2000 Comark Server Running Software Version 3 11 Preliminary This information may change 10 Figure 4 Interconnect I O Converter to Current Loop Converter ...

Страница 11: ...assis connected to a verified electrical ground earth In all cases the pertinent national wiring codes apply National Electrical Code NFPA 70 must be followed for installations in the USA Canadian Electrical Code C22 1 must be followed for installations in Canada BSI Standard BS7671 latest edition must be followed for installations in Great Britain Additional information is given in the Johnson Co...

Страница 12: ... a lug to the end of the wire and screw securely to the wall of the enclosure or the nearest stud 4 All internal ground earth bonding straps must be left intact after installation 5 Check that grounding points are clean and free from paint or corrosion D Type Connectors All D type connectors must use an Electromagnetic Interference EMI shielded shroud Verify good contact occurs when connecting D t...

Страница 13: ...orithm Two door access control input output interface One general purpose input and output per terminal The S321 DIN can communicate with the P2000 server in one of the following configurations Serial communications using a B B Electronics RS 232 to RS 485 converter model 485OT9L IP network communications using the Digi One SP serial to Ethernet converter The following subsections provide instruct...

Страница 14: ...d Switch 1 Switch 2 Switch 3 Switch 4 R21 Time out ms 1200 OFF OFF OFF OFF 820k Ω 9 0 2400 OFF OFF OFF OFF 410k Ω 4 5 4800 ON OFF OFF OFF Not Used 2 2 9600 1 OFF ON OFF OFF Not Used 1 1 19 200 OFF OFF ON OFF Not Used 0 6 38 400 OFF OFF OFF ON Not Used 0 3 1 Default setting 2 Set the remaining switch positions for RS 485 Half Duplex operation and termination according to Table 6 Table 6 Remaining S...

Страница 15: ...er to connect to an IP network via the controller s serial port See Figure 8 Figure 8 S321 DIN Controller in an IP Network Configuration To install the converter 1 Change the DIP switch settings on the bottom of the Digi One SP converter according to Figure 9 and Table 7 Figure 9 Digi One SP Converter DIP Switch Settings Table 7 Digi One SP Converter DIP Switch Positions DIP Switch Position 1 Down...

Страница 16: ...onnect the DB 9F connector to the Digi One SP s DB 9M connector 4 Run an Ethernet cable from the Digi One SP to your network connection 5 Connect the power cable to the Digi One SP and run to an appropriate 110 240 VAC power source To install the driver for the Digi One SP and configure the device download the driver and configure the software according to the screen captures located at ftp cardke...

Страница 17: ...nning Software Version 3 11 17 Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2012 Johnson Controls Inc ...

Отзывы: