8.12 Setback Operation
(1) Press and hold “Menu” and “Back/Help”on the wired controller simultaneously for at least three
seconds during the normal mode (unit stoppage).
The Test Run menu is displayed.
(2) Select “Input/Output” from the Test Run menu and press “OK”.
(3) Select either "Input 1" or "Input 2" and change the setting to "09".
(4) Build a circuit such as shown below.
(5) Temperature compensation for the setback function can be selected on the wired controller.
Refer to “Function Selection by Wired Controller” section for details.