P5417050-rev.1
15
6. Tighten the nuts on the suspension brackets after adjustments are completed. Add thread lock
compound to the suspension bolts and nuts in order to prevent them from loosening. Adjust the indoor
unit into correct position, using the scale of the pattern board (template).
NOTE:
While adjusting the clearance spacing between the indoor unit and the ceiling surface, keep the indoor
unit level. Otherwise, it may cause a malfunction of the float switch. Verify the vertical alignment of the
unit with a level.
Verify the vertical alignment at each
corner (
•
) of the unit with a level or
by pouring water into the clear vinyl
tubing as shown here.
1. Verify the clearance dimension between the indoor unit and the false ceiling. The tolerance for that
distance is within 1-7/8
+ 3/16
0
inches (47
+ 5
0
mm).
If not correct, adjust the distance by using the scale of the pattern board (template) while maintaining
the vertical alignment of the indoor unit.
2. See that the securing screws for the panel are tightened. Tighten the securing screws for the panel
until they touch the stopper to the suspension bracket.
NOTE:
Pay attention to the distance between the indoor unit and the false ceiling. If there is more than
2-1/16 inches (52mm) gap from the mounting position, condensation may form due to escaping air
from the packing seal.
3. Secure all connections for the optional decorative panel to the unit.
For Decorative Panel
5.4 Installation of Decorative Panel
● Install the decorative panel in accordance with the installation manual for the decorative panel.
● Confirm that all connections between the unit and the decorative panel and are secure.
Indoor Unit
1-7/8
+3/16
0
(47 )
+5
0
Ceiling Surface
Mounting Position
Unit: inch (mm)
NOTICE
Vinyl Tube
Condensate Pipe
Level
Bracket for
Decorative Panel