background image

Technical specifications

Table 1: CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature Transmitters technical specifications

Specification

Description

CO

measuring range

0 to 2,000 ppm CO

2

CO

accuracy across temperature range

68 to 86°F (20 to 30°C): ±(30 ppm +3% of reading)

50 to 68°F (10 to 20°C), 86 to 104°F (30 to 40°C): ±(35 ppm +3.7% of

reading)

32 to 50 °F (0 to 10°C), 104 to 122°F (40 to 50°C): ±(40 ppm +4.8% of

reading)

Long-term stability

±(15 ppm +2% of reading) over 5 years

Response time, 0 to 63%

1 minute

Platinum temperature sensor

Temperature Sensor: 1,000 ohm, Class F0.15 IEC60751 (Class A), thin-

film platinum

Temperature coefficient: approximately 2 ohms per F° (3.9 ohms per

C°)

Reference resistance: 1,000 ohms at 32°F (0°C)

Accuracy: ±0.34F° at 70°F (±0.18C° at 21°C)

Operating temperature range

32 to 122°F (0 to 50°C)

Storage temperature range

-40 to 158°F (-40 to 70°C)

Operating humidity range

0 to 95% RH, noncondensing, 86°F (30°C) maximum dew point

Transmitter CO

2

 output signal

4 to 20 mA and 0 to 10 VDC

Maximum output current: 21 mA; maximum output voltage: 11 V

Resolution of analog outputs

0.3 ppm CO

2

External load

Minimum 1,000 ohms load resistance for 0 to 10 V
Maximum 600 ohm load resistance for 4 to 20 mA

Power supply range

24 VAC ±20%, 50/60 Hz (18 to 30 VDC), Class 2

Power consumption

<1.0W Average, excluding current output consumption

Current consumption

100 mA peak on AC power; 45 mA peak on DC power

Warm-up time

<1 minute

<10 minutes for full specification

Dimensions, H x W x D

5 x 3-3/16 x 1-1/32 in. (127 x 81 x 26 mm)

Shipping weight

0.25 lb (114 g)

Compliance

United States

UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment, FCC Compliant to CFR 47, Part 15, Subpart B, Class A

Europe

CE Mark - Johnson Controls, Inc. declares that this product is in

compliance with the essential requirements and other relevant

provisions of the EMC directive.

Canada

UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205-12,

Energy Management Equipment, Industry Canada Compliant,

ICES-003

Australia and

New Zealand

RCM Mark, Australia/NZ Emissions Compliant.

CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature Transmitters Installation Guide

5

Содержание CD-W00-0-2 Series

Страница 1: ...uire de brouillage et 2 L utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Installation Important The CD W00 x0 2 Series Wall Mount CO2 and Temperature Transmitters are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could...

Страница 2: ... a cable ferrule to the cable end If the distance between the sensor and the controller is over 3 meters 9 8 feet use shielded cable Connect the shield at the controller end of the cable Location selection When mounting wall model transmitters Select a location that represents the area of interest Do not install the transmitter on the ceiling Avoid placing the transmitter near heat and moisture so...

Страница 3: ...ts on the top or bottom side of the printed circuit board Failure to follow proper wiring procedures may cause the transmitter to fail 2 Connect the wires to the mounting base screw terminals as shown in Figure 4 Figure 4 Screw terminals Note The transmitter generates both voltage and current output Each output has its own individual positive screw terminal Power supply requirements The transmitte...

Страница 4: ...eset the 2 000 ppm value using the controller s compensation factor CF shown in Figure 7 or Figure 8 Calculate the corrected value Corrected Value CF x 2 000 For example if the sensor is situated at an altitude of 3 000 ft 914 4 m above sea level the CF is 1 10 See Figure 7 or Figure 8 The corrected value is Corrected Value 1 10 x 2 000 ppm 2 200 ppm Note For altitude compensation only adjust the ...

Страница 5: ... mA and 0 to 10 VDC Maximum output current 21 mA maximum output voltage 11 V Resolution of analog outputs 0 3 ppm CO2 External load Minimum 1 000 ohms load resistance for 0 to 10 V Maximum 600 ohm load resistance for 4 to 20 mA Power supply range 24 VAC 20 50 60 Hz 18 to 30 VDC Class 2 Power consumption 1 0W Average excluding current output consumption Current consumption 100 mA peak on AC power 4...

Страница 6: ...ht Dieser Sensor Transmitter kann nur wandmontiert eingesetzt werden Der elektrische Anschluß ist nach den örtlichen Vorschriften durch autorisiertes Personal durchzuführen Versorgungsspannung und Niederspannung sind getrennt zuzuführen Bei Verwendung von flexiblen Leitungen sind Kabelschuhe zu verwenden Überprüfen Sie alle Kabelverbindungen bevor Sie den Antrieb einschalten Der Kontakt mit Kompon...

Страница 7: ...nslutningen ska utföras av behörig personal i enlighet med de lokala föreskrifterna Försörjningsspänning och lågspänning ska tillföras åtskilt Vid användning av flexibla ledningar ska kabelskor användas Kontrollera alla kabelförbindelser innan du tillkopplar ställdonet Kontakt med komponenter med farlig spänning kan ge elektriska stötar som kan orsaka allvarliga eller livshotande personskador Kort...

Страница 8: ...ь причиной несчастного случая или повреждения оборудования если кабель между Датчик и контроллером составляет более 3 метров то должен быть экранирован Экран следует заземлять в одной точке на стороне контроллера Сохраните этот документ Portuguese Certifique se que a fonte de alimentação é compatível com a fonte de alimentação especificada na secção de Especificação Técnica Este sensor transmissor...

Страница 9: ...s com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnsoncontrols com contact us Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PR...

Страница 10: ... 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice ...

Отзывы: