30 seconds as the controller attempts to establish
connection with the sensor.
For more details about the workflow, refer to FAN-410,
which can be downloaded from https://my.jci.com/
sites/BE/NASysOpsOn/Pages/home/welcome/
Commissioning field controllers
You commission controllers with the Controller
Configuration Tool (CCT) software. You can connect the
controller using NxE Passthru (with network engines
(NxEs) at release 9.0.2 or above), MAP4.2+/BACnet
Router (Mobile Access Portal (MAP) Gateway at version
4.2 or above, or through Bluetooth (using BTCVT).
Refer to
Controller Tool Help (LIT-12011147)
for detailed
information about commissioning field controllers.
Note:
• You can use the Bluetooth connection to
Transfer to Computer (Upload) and commission
the controller, but you cannot use the
Bluetooth connection to Transfer to Device
(Download).
• The MAP Gateway serves as a replacement
for the BTCVT, which is no longer available for
purchase, but continues to be supported.
Firmware package file for CCT
The MS-FCP-0 equipment controller firmware package
files are required for CCT to configure and commission
the controllers. The firmware package files also allow
you to upgrade an existing controller to the latest
firmware release available for that controller.
Beginning at CCT Release 13, the firmware package
files are orderable separately; they are not included
with CCT. They are obtained from the
Metasys
software
licensing portal, and are loaded and licensed on the
computer/server that is running CCT.
For additional information about the firmware
package files, refer to the
CCT Installation Instructions
(LIT-12011259)
.
ATC1510 Advanced Terminal Unit Controller Installation Guide
14