![Johnson Controls ANSUL 10 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/johnson-controls/ansul-10/ansul-10_operation-inspection-service-and-maintenance-and-recharge-manual_2023954033.webp)
ANSUL Cartridge Dry Chemical Fire Extinguishers
Models 10, 20, 30, Operation, Inspection, Service and
Maintenance, and Recharge Manual (Form No. F-7674)
2018-OCT-15 REV. 10 PAGE 27
CARTRIDGE RECEIVER PUNCTURE PIN REPLACEMENT
CARTRIDGE RECEIVER PUNCTURE PIN REPLACEMENT
PROCEDURE
1. Ensure cartridge is removed from extinguisher.
2. Remove retaining roll pin from lever as shown.
3. Remove old puncture pin by pushing downward.
4. Install new puncture pin and roll pin in reverse procedure.
5. Ensure the puncture pin travels freely by operating the
lever.
1
003244
2
003245
3
003246
4
003247
5
000910