ANSUL Cartridge Dry Chemical Fire Extinguishers
Models 10, 20, 30, Operation, Inspection, Service and
Maintenance, and Recharge Manual (Form No. F-7674)
2018-OCT-15 REV. 10 PAGE 5
INSPECTION
INSPECTION
Where an inspection reveals that tampering has occurred
or that the extinguisher is damaged, impaired, leaking
or has obvious corrosion, complete maintenance as
described on pages 9 through 16 should be followed.
To provide reasonable assurance extinguisher is charged
and operable:
1. Make certain the extinguisher is in its designated place,
is clearly visible and is accessible for immediate use.
Any obstructions that obscure it, or that would otherwise
impair its being readily accessible, should be removed.
2. Check the visual seal on the cartridge receiver and,
if provided, the tamper-proof seal on the fill cap. The
absence of a seal or a broken seal may indicate either
unreported use or tampering. In either case, a complete
maintenance check is required.
3. Ansul indicator fill cap models, in addition to a visual seal,
feature a red stem indicator which pops up in the center
of the fill cap and remains up after the pressure has been
relieved. Check the red indicator stem. If up, a complete
maintenance check is in order.
4. Remove the extinguisher from its mounting bracket and
heft (lift up and down slightly) to determine if it is filled.
5. Examine the extinguisher shell, cartridge guard, cartridge
receiver and all other external parts for evidence of physi-
cal damage, corrosion or other impairments.
6. Check the nameplate for readability – especially the oper-
ating instructions. If they are not legible, an instructed (but
not necessarily trained) person may not understand the
method of operation in the excitement created by a fire.
1
003189
2
003190
3
003191
4
003192
5
003193
6
003194
Содержание ANSUL 10
Страница 2: ......