background image

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

Product/Technical Bulletin    

9

Setting Other Functions

To set the Differential (dIF), Anti-short Cycle Delay
(ASd), Temperature Offset (OFS), or Sensor Failure
(SF) operation, use the method illustrated and outlined
below.

Figure 14 illustrates the order of functions shown using
the Up or Down button. The Up button accesses
functions in the clockwise direction; the Down button
accesses functions in the counterclockwise direction.
Refer to Table 3 for function ranges and factory
settings.

O F S

A S d

  d I F

S F

S P

Up

Button

Down
Button

Figure 14: Order of the Functions

1.  Press and hold the 

MENU

 button

until the display changes to
flashing 

SP

. This will take about 2

seconds.

2. Press 

the 

Up

 or 

Down

 button

repeatedly until the desired
function is displayed.
See Table 3.

3. Press 

the 

MENU

 button to display

the function’s current value.

4. Press 

the 

Up

 or 

Down

 button

until the desired value is
displayed.

5. Press 

the 

MENU

 button to save

the new value. The display then
returns to the sensor temperature.

Notes: 

If no entries are made for 30 seconds while

programming is in progress, the control reverts to the
normal temperature display.

If the 

MENU

 button is not pressed after setting a new

value, the new value is not saved and the A419 control
reverts to the previously saved value for that function.

Any 

saved

 A419 control setting values are

non-volatile

 and remain in the control’s memory

during power interruptions.

Checkout

Before applying power, make sure installation and
wiring connections are according to job specifications.
After necessary adjustments and electrical
connections have been made, put the system in
operation and observe the control for at least three
complete operating cycles before leaving the
installation.

Troubleshooting

If the control system does not function properly, verify
that the unit is wired, configured, and set properly. If
the problem persists, use the following procedures to
determine the cause of the problem:

1.  Check for proper supply voltage to the A419

control.

a.  Remove the cover by loosening the four

captive cover screws.

!

 

WARNING: Risk of Electrical Shock.

High voltages may be present at electrical terminals
and other exposed internal metal surfaces. Avoid
contact with all metal surfaces on control when cover
is removed.

b.  Use a reliable AC voltmeter to check the

voltage between the 

COM

 and 

120V

 or 

240V

terminals on line voltage models and the two
24V terminals on low-voltage models. Refer to
Figure 9, Figure 10, and Figure 11.

c.  The voltage must be between: 20 and 30 VAC

for 24 volt applications, 102 and 132 VAC for
120 volt applications, 177 and 264 VAC for
208/240 volt applications

Notes: 

If the voltage reading is within the

required range, proceed to Step 2.

If the voltage reading is 

not

 within the required

range, check the power source and input
power wires for problems.

Содержание A419 Series

Страница 1: ...Temperature Sensor Features and Benefits Easy to Read Front Panel Liquid Crystal Display Displays the sensed temperature and control function status clearly custom icons on the display indicate the control and system status at a glance Wide Temperature Differential Adjustment Range 1 to 30F or C Allows the user to set a precise 1F or C temperature differential from 1 to 30F or C providing a much t...

Страница 2: ...e harmful interference and 2 this device must accept any interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment gen...

Страница 3: ...n to adjust the control setting Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the SPDT output relay is energized and the Normally Open N O contacts are closed See Figure 5 A419 Control Definitions Cut in is the temperature at which the N O contacts on the SPDT output relay close Cutout is the temperature at which the N O contacts on the SPDT output rel...

Страница 4: ...ue set in Temperature Offset The BIN and COM terminals may be connected to a user supplied external switching device such as a time clock that has a set of Single Pole Single Throw SPST contacts Closing a circuit between the BIN and COM terminals activates the Temperature Offset See Wiring This function enables the control to alternate between two temperature setpoints based on the position of the...

Страница 5: ...n A419 control has either a standard high impact plastic NEMA 1 or a NEMA 4X corrosion resistant watertight enclosure The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment Note When mounting the control to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure The mounting hole pattern of the NEMA 1 enclosure is ...

Страница 6: ...igure 10 and Figure 11 Keep the leads between the control and sensor as short as possible practical in your application The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature Refer to Table 1 when extending sensor leads Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15...

Страница 7: ...pers to set Cooling Heating Setpoint and Touchpad Lock functions 4 Replace the cover and fasten in place with the four screws 5 Restore power to the control IMPORTANT Verify that the Cooling Heating jumper is positioned properly before powering the A419 control to ensure that the relay operates as intended See Figure 13 and Table 2 Jumper Pins Removed Jumper Positioned on One Pin Installed Jumper ...

Страница 8: ...everts to the previously saved setpoint value Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Table 3 Function Ranges and Settings Function Range Factory Setting SP Setpoint 30 to 212 F 34 to 100 C 30 dIF Differential 1 to 30 F or C 5 ASd Anti short Cycle Delay 0 to 12 minutes 1 OFS Temperature Offset 0 to 50 F or C 0 SF Sensor F...

Страница 9: ...sly saved value for that function Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Checkout Before applying power make sure installation and wiring connections are according to job specifications After necessary adjustments and electrical connections have been made put the system in operation and observe the control for at least t...

Страница 10: ...s 1 and 2 before performing this step b Disconnect the load from the output relay terminals c Ensure that the Touchpad Lock jumper is installed so that the touchpad is unlocked d Reconnect the sensor leads and supply power to the control e Replace the cover f Check the control settings for proper values g Press and hold the MENU button until Setpoint appears occurs in about 2 seconds h Use the Up ...

Страница 11: ...he control Ordering Information Refer to Table 6 to order controls and accessories Table 6 Ordering Information Product Code Number Item Description A419ABC 1C Line Voltage NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included A419AEC 1C Line Voltage NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included Supply Voltage 1...

Страница 12: ...hp Full Load Amperes N O N C 16 5 8 A 9 2 4 0 A 8 0 4 9 A Locked Rotor Amperes N O N C 96 34 8 A 55 2 24 A 48 29 4 A Non inductive Amperes N O N C 15 10 A 10 10 A 10 10 A Pilot Duty 125 VA N O contacts 24 to 240 VAC 125 VA N C contacts 120 to 240 VAC 50 VA N C contacts 24 VAC Sensor Type A99BB Type PTC Sensor See Table 6 Control Ambient Temperature Operating 26 to 140 F 32 to 60 C Shipping 40 to 1...

Отзывы: