background image

Product/Technical Bulletin

A419

Issue Date

February 10, 2003

© 2003 Johnson Controls, Inc.

1

Code No. LIT-125188

www.johnsoncontrols.com

® 

A419 Series Electronic Temperature Controls with Display

and NEMA 1 or NEMA 4X Watertight Enclosures

The A419 series controls are single-stage, electronic
temperature controls with a Single-Pole, Double-Throw
(SPDT) output relay. They feature a lockable
front-panel touchpad for setup and adjustment, and a
Liquid Crystal Display (LCD) for viewing the
temperature and status of other functions. A
Light-Emitting Diode (LED) indicates the controls’
output relay On/Off status. The A419 controls are
available in 24 VAC or 120/240 VAC powered models.

The A419 controls have heating and cooling modes,
adjustable setpoint and differential, an adjustable
anti-short cycle delay, and a temperature offset
function. The setpoint range is -30 to 212°F
(-34 to 100°C). The controls feature remote sensing
capability and interchangeable sensors. The
A419 controls are available in either NEMA 1,
high-impact plastic enclosure suitable for surface or
DIN rail mounting or NEMA 4X watertight,
corrosion-resistant surface-mount enclosures.

Figure 1: A419 Temperature Control with NEMA 1

Enclosure and A99 Temperature Sensor

Features and Benefits

Easy-to-Read Front-Panel
Liquid Crystal Display

Displays the sensed temperature and control-function
status clearly; custom icons on the display indicate the
control and system status at a glance

Wide Temperature Differential Adjustment
Range (1 to 30F° or C°)

Allows the user to set a precise (1F° or C°) temperature
differential from 1 to 30F° or C°; providing a much
tighter differential than electromechanical controls

Adjustable Anti-Short Cycle Delay
(0 to 12 Minutes in 1-Minute Increments)

Ensures that the output relay remains off for a user-set
time delay, which helps avoid hard starts, nuisance
overload outages, and unnecessary equipment wear

Switch-Activated Temperature Offset
Function

Allows the user to shift the cut-in and cutout setpoints
by an adjustable offset based on the status of a
user-installed, external switch, such as a time clock

High-Impact, Thermoplastic NEMA 1 or
NEMA 4X Watertight, Corrosion-Resistant
Enclosures

Increase application options, allowing surface and
snap-fit DIN rail mount, or Watertight surface mount

Lockable Front Panel Touchpad

Allows easy set up and adjustment of the A419 control
setpoint, differential, and other functions; a concealed
jumper locks the touchpad, and deters unauthorized
adjustment of the control settings

Low- and Line-Voltage Models

Provide options for most refrigeration and HVAC
control-voltage applications

Содержание A419 Series

Страница 1: ...Temperature Sensor Features and Benefits Easy to Read Front Panel Liquid Crystal Display Displays the sensed temperature and control function status clearly custom icons on the display indicate the control and system status at a glance Wide Temperature Differential Adjustment Range 1 to 30F or C Allows the user to set a precise 1F or C temperature differential from 1 to 30F or C providing a much t...

Страница 2: ...e harmful interference and 2 this device must accept any interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment gen...

Страница 3: ...n to adjust the control setting Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the SPDT output relay is energized and the Normally Open N O contacts are closed See Figure 5 A419 Control Definitions Cut in is the temperature at which the N O contacts on the SPDT output relay close Cutout is the temperature at which the N O contacts on the SPDT output rel...

Страница 4: ...ue set in Temperature Offset The BIN and COM terminals may be connected to a user supplied external switching device such as a time clock that has a set of Single Pole Single Throw SPST contacts Closing a circuit between the BIN and COM terminals activates the Temperature Offset See Wiring This function enables the control to alternate between two temperature setpoints based on the position of the...

Страница 5: ...n A419 control has either a standard high impact plastic NEMA 1 or a NEMA 4X corrosion resistant watertight enclosure The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment Note When mounting the control to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure The mounting hole pattern of the NEMA 1 enclosure is ...

Страница 6: ...igure 10 and Figure 11 Keep the leads between the control and sensor as short as possible practical in your application The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature Refer to Table 1 when extending sensor leads Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15...

Страница 7: ...pers to set Cooling Heating Setpoint and Touchpad Lock functions 4 Replace the cover and fasten in place with the four screws 5 Restore power to the control IMPORTANT Verify that the Cooling Heating jumper is positioned properly before powering the A419 control to ensure that the relay operates as intended See Figure 13 and Table 2 Jumper Pins Removed Jumper Positioned on One Pin Installed Jumper ...

Страница 8: ...everts to the previously saved setpoint value Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Table 3 Function Ranges and Settings Function Range Factory Setting SP Setpoint 30 to 212 F 34 to 100 C 30 dIF Differential 1 to 30 F or C 5 ASd Anti short Cycle Delay 0 to 12 minutes 1 OFS Temperature Offset 0 to 50 F or C 0 SF Sensor F...

Страница 9: ...sly saved value for that function Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Checkout Before applying power make sure installation and wiring connections are according to job specifications After necessary adjustments and electrical connections have been made put the system in operation and observe the control for at least t...

Страница 10: ...s 1 and 2 before performing this step b Disconnect the load from the output relay terminals c Ensure that the Touchpad Lock jumper is installed so that the touchpad is unlocked d Reconnect the sensor leads and supply power to the control e Replace the cover f Check the control settings for proper values g Press and hold the MENU button until Setpoint appears occurs in about 2 seconds h Use the Up ...

Страница 11: ...he control Ordering Information Refer to Table 6 to order controls and accessories Table 6 Ordering Information Product Code Number Item Description A419ABC 1C Line Voltage NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included A419AEC 1C Line Voltage NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included Supply Voltage 1...

Страница 12: ...hp Full Load Amperes N O N C 16 5 8 A 9 2 4 0 A 8 0 4 9 A Locked Rotor Amperes N O N C 96 34 8 A 55 2 24 A 48 29 4 A Non inductive Amperes N O N C 15 10 A 10 10 A 10 10 A Pilot Duty 125 VA N O contacts 24 to 240 VAC 125 VA N C contacts 120 to 240 VAC 50 VA N C contacts 24 VAC Sensor Type A99BB Type PTC Sensor See Table 6 Control Ambient Temperature Operating 26 to 140 F 32 to 60 C Shipping 40 to 1...