background image

 

A25 Series Warm Air Control with Manual Reset Product/Technical Bulletin     

5

 

O

peration 

Models A25AN and A25CN 

Setpoint Adjustment: 

 Adjust the A25 setpoint by 

rotating the setpoint knob (Figure 7).  The setpoint 

is displayed in the setpoint window. 

Test Procedure: 

To test (trip) the A25:

  Raise the temperature 

at the sensor above the setpoint or lower the 

setpoint below the ambient temperature. 

The 

control should lockout (trip). 

To reset after test: 

 Lower the temperature at 

the sensor to 20F° (11C°) below the setpoint or 

raise the setpoint to 20F° (11C°) above the 

ambient temperature.  Press the reset lever.  

The A25 should reset (closing the circuit). 

Reset Procedure:

 Verify that the temperature has 

dropped to 20F° (11C°) below setpoint.  Press the 

reset lever to reset the A25 (closing the circuit). 

 

 

Figure 7:  Models A25AN and A25CN   

Содержание A25 Series

Страница 1: ...ntrol in the supply air duct or plenum where a lockout type control is desired or required by local code Figure 1 The A25 Series Warm Air Control with Manual Reset Features and Benefits Trip free Rese...

Страница 2: ...ng location refer to Figure 2 3 Using the flange as a template on the duct mark the location for two 1 2 in 13 mm No 10 sheet metal screws 4 Punch or drill both sheet metal screw holes in the duct at...

Страница 3: ...ncrease The red to blue circuit opens on temperature increase Refer to Figures 3 and 4 for terminal identification and typical wiring connections When the reset lever is pressed during normal operatio...

Страница 4: ...nd the alarm or signal if applicable should activate Note The setpoint at shutdown should equal the approximate duct air temperature 3 Turn the setpoint knob clockwise to the desired setpoint Nothing...

Страница 5: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Страница 6: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Страница 7: ...n The A25 is not sensing properly The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct or plenum Insert the sensing element as f...

Страница 8: ...8 A25 Series Warm Air Control with Manual Reset Product Technical Bulletin Notes...

Страница 9: ...e reset when the temperature drops 20F 11C below the dial setting Sensing Element Bi metal rod and tube construction Shipping Weight Individual pack 1 8 lb 0 8 kg Overpack of 12 units 23 lb 10 4 kg Wi...

Отзывы: