Installation Sheets Manual  121 

 

Temperature Controls Section 

 

Technical Bulletin  A11 

  

Issue 

Date 

0790 

©  1990 Johnson Controls, Inc. 

1

 

  Code No.  LIT-121010 
  Part No. 997-358 

 

A11 Series 

Low Temperature Cutout Control 

 
 

Application 

A11 Series low temperature 
cutout controls are available with 
SPDT or SPST contact action.  
Typical applications include the 
sensing of low temperature 
conditions to avoid overcooling 
or icing of hydronic coils, cooling 
coils and liquid handling pipes.  
The controls are compact and 
sturdy, and have an adjustable 
temperature set point range with 
a fixed differential.  The range 
adjustment screw is accessible 
at the bottom of the control, and 
at the top of the control when the 
cover is removed. 

All Series A11 temperature 
controls are designed for use 

only

 as operating controls.  

Where an operating control 
failure would result in personal  
injury and/or loss of property, it is 
the responsibility of the installer 
to add devices (safety, limit 
controls) or systems (alarm, 
supervisory systems) that protect 
against, or warn of, control 
failure. 

Operation 

The A11D and A11E models 
have SPDT contact action; 
models A11A and A11B have 
SPST contacts.  When  
16 inches (406 mm) or more of 
an A11’s sensing bulb senses a 
temperature equal to or lower 
than the set point, the contacts 
will open on SPST controls, or 

the circuit between the Red and 
Yellow terminals will open on 
SPDT controls.  The A11A and 
A11D models lock out when the 
temperature decreases below 
the control’s temperature set 
point and must be manually 
reset by depressing the trip free 
reset lever (which must be 
pressed and released before 
power will be restored) when the 
temperature increases 12F

°

 

(6.7C

°

) or more above the set 

point.  The A11B and A11E will 
automatically recycle on an 
increase in temperature. 

Installation 

Mounting 

The bulb is usually located on 
the downstream side of the coil 
with the bulb exposed to all 
areas where low temperatures 
are likely to be encountered.  
The sensing element is 20 feet 
(6.1 m) long and should be 
horizontally serpentined across 
the face of the coil to sense 
temperatures in all areas.  (See 
Fig. 2.)  Do not install A11 Series 
controls where the ambient 
temperature at the control 
exceeds 140

°

F (60

°

C), or falls 

below 0

°

F (-18

°

C).  The 

maximum temperature at the 
sensing bulb should not exceed 
250

°

F (121

°

C). 

 

Wiring 

!

 CAUTION: Disconnect the 

power supply before wiring 
connections are made to 
avoid possible electrical 
shock or damage to the 
equipment. 

Make all wiring connections using 
copper conductors only, and in 
accordance with the National 
Electrical Code and local 
regulations.  For maximum 
electrical rating of the control, see 
the cover label on the inside of the 
control cover.  Loads exceeding 
the rating of the control can be 
handled with a relay or motor 
starter.  On the SPDT models the 
Red terminal is the common 
terminal.  See Fig. 3 for terminal 
identifications. 

Note

:  Use terminal screws 

furnished (8-32 

×

 1/4 in. binder 

head).  Substitution of other 
screws may cause problems in 
making proper connections. 

 

 

Fig. 1 -- Interior view of a Low 

Temperature Cutout Control with 

manual reset.

 