Johnson Controls 13 SEER - THGD Скачать руководство пользователя страница 6

359513-UIM-A-0408

6

Johnson Controls Unitary Products

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures  7-8. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

 FIGURE 6:  

Typical Field Wiring (Air Handler / Electrical Heat) - (Single Phase)

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

POWER WIRING

208/230-1-60

CONTACTOR
TERMINALS

COIL

GND.

LUG

C

Y

R

G

W

Y

R

G

W

POWER WIRING
CONTROL WIRING

FACTORY WIRING

24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)

FURNACE OR AIR HANDLER TERMINAL BLOCK

ROOM THERMOSTAT

CONDENSING UNIT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.

*

*

Содержание 13 SEER - THGD

Страница 1: ...As soon as a unit is received it should be inspected for possible dam age during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate req...

Страница 2: ...o the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT The following steps should be performed in order to insure proper sys tem operation and performance 1 Change out o...

Страница 3: ...al vapor lines at least 1 every 20 feet toward the outdoor unit to facilitate proper oil return PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be take...

Страница 4: ...rts except when necessary for servicing the system 12 Release the refrigerant charge into the system Open both the liq uid and vapor valves by removing the plunger cap and with an allen wrench back ou...

Страница 5: ...r and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring opening pro vided and into the unit control box as shown in Figure 5...

Страница 6: ...if the relative humidity in the space is higher than the desired set point of the dehumidification control the variable speed blower motor will operate at lower speed until the dehumidification con t...

Страница 7: ...A DN22U00124 THERMOSTAT Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND...

Страница 8: ...Heat XFMR R 24 Volt Hot Cool XFMR Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compres...

Страница 9: ...weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided on the units rating plate for cooling mode only There is no accurate method for chargin...

Страница 10: ...6 93 206 103 236 113 88 52 118 68 148 82 178 94 208 104 238 114 90 54 120 69 150 83 180 94 210 105 240 114 92 55 122 70 152 84 182 95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 1...

Страница 11: ...e defrost cycle it will terminate the defrost cycle and de energize the compres sor The control will also stop the defrost cycle length timer but not reset it When the control receives another call fo...

Страница 12: ...e state of the liquid line temperature and outdoor ambient tem perature inputs The coil does not have to be cold and the outdoor tem perature does not have to be within a certain range for the heat pu...

Страница 13: ...s reset the control will stop displaying the fault code and will respond to thermostat inputs normally INDICATIONS OF PROPER OPERATION Cooling Cooling operation is the same as any conventional air con...

Страница 14: ...ted in U S A 359513 UIM A 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 SECTION X WIRING DIAGRAM...

Отзывы: