SECTION VIII: SYSTEM OPERATION

ANTI-SHORT CYCLE DELAY

The control includes a five-minute anti-short cycle delay (ASCD) timer
to prevent the compressor from short cycling after a power or thermo-
stat signal interruption. The ASCD timer is applied when the control is
first powered from the indoor unit thermostat and immediately following
the completion of a compressor run cycle. The compressor and the out-
door fan will not operate during the five minutes that the timer is active. 

The ASCD timer can be bypassed by connecting the TEST terminals
for three seconds while the thermostat is calling for compressor opera-
tion (Y input signal energized).

TABLE 1: 

R-22 Saturated Properties

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

80

48

110

64

140

78

170

91

200

101

230

111

82

49

112

65

142

79

172

91

202

102

232

112

84

50

114

66

144

80

174

92

204

103

234

112

86

51

116

67

146

81

176

93

206

103

236

113

88

52

118

68

148

82

178

94

208

104

238

114

90

54

120

69

150

83

180

94

210

105

240

114

92

55

122

70

152

84

182

95

212

105

242

115

94

56

124

71

154

84

184

96

214

106

244

115

96

57

126

72

156

85

186

97

216

107

246

116

98

58

128

73

158

86

188

97

218

107

248

117

100

59

130

74

160

87

190

98

220

108

250

117

102

60

132

75

162

88

192

99

222

109

252

118

104

61

134

76

164

88

194

99

224

109

254

118

106

62

136

77

166

89

196

100

226

110

256

119

108

63

138

78

168

90

198

101

228

111

258

119

 FIGURE 10:  

Heat Pump Flow Diagram

CHARGE COMPENSATOR

(Empty in cooling / full in heating)

(Not included in all Units)

FIELD CONNECTED LINE

INDOOR COIL

OUTDOOR
COIL

4-WAY
REVERSING
VALVE

FILTER DRYER
(Solid core)

SUCTION
ACCUMULATOR

LIQUID
SENSOR

COMPRESSOR

FIELD CONNECTED LINE

SHOWN IN COOLING POSITION.

COOLING CYCLE FLOW

HEATING CYCLE FLOW

BI-FLOW
TXV/CHECK
VALVE (Cooling) **

** NOTE: The indoor coil is shipped with an orifice. The orifice must be replaced with a TXV Kit.

BI-FLOW
TXV/CHECK
VALVE OR ORIFICE (Heating)

 FIGURE 11:  

Demand Defrost Control Module

TEST

AMBIENT

AMBG

COIL

G

COIL

1

2

3

4

COND

FA
N

HIGH

VOL

T

AGE

PRESSURE

M

SWITCH

REV

VALVE

X/L

R

C

Y

O

W

W1/66

X/L

R

C

Y

O

W

W1/66

DEMAND
DEFROST CURVE
SELECTION JUMPER

P

Содержание 13 SEER - THGD

Страница 1: ...As soon as a unit is received it should be inspected for possible dam age during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate req...

Страница 2: ...o the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT The following steps should be performed in order to insure proper sys tem operation and performance 1 Change out o...

Страница 3: ...al vapor lines at least 1 every 20 feet toward the outdoor unit to facilitate proper oil return PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be take...

Страница 4: ...rts except when necessary for servicing the system 12 Release the refrigerant charge into the system Open both the liq uid and vapor valves by removing the plunger cap and with an allen wrench back ou...

Страница 5: ...r and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring opening pro vided and into the unit control box as shown in Figure 5...

Страница 6: ...if the relative humidity in the space is higher than the desired set point of the dehumidification control the variable speed blower motor will operate at lower speed until the dehumidification con t...

Страница 7: ...A DN22U00124 THERMOSTAT Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND...

Страница 8: ...Heat XFMR R 24 Volt Hot Cool XFMR Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compres...

Страница 9: ...weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided on the units rating plate for cooling mode only There is no accurate method for chargin...

Страница 10: ...6 93 206 103 236 113 88 52 118 68 148 82 178 94 208 104 238 114 90 54 120 69 150 83 180 94 210 105 240 114 92 55 122 70 152 84 182 95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 1...

Страница 11: ...e defrost cycle it will terminate the defrost cycle and de energize the compres sor The control will also stop the defrost cycle length timer but not reset it When the control receives another call fo...

Страница 12: ...e state of the liquid line temperature and outdoor ambient tem perature inputs The coil does not have to be cold and the outdoor tem perature does not have to be within a certain range for the heat pu...

Страница 13: ...s reset the control will stop displaying the fault code and will respond to thermostat inputs normally INDICATIONS OF PROPER OPERATION Cooling Cooling operation is the same as any conventional air con...

Страница 14: ...ted in U S A 359513 UIM A 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 SECTION X WIRING DIAGRAM...

Отзывы: