Johnson Controls 13 SEER - THGD Скачать руководство пользователя страница 11

359513-UIM-A-0408

Johnson Controls Unitary Products

11

LOW VOLTAGE DETECTION

The control monitors the transformer secondary (24 VAC) voltage and
provides low voltage protection for the heat pump and its components.
In particular, the control prevents contactor chatter during low voltage
conditions. If the voltage drops below approximately 19 VAC, the con-
trol will continue to energize any relays that are already energized but
will not energize any additional relays until the voltage level increases.
If the voltage drops below approximately 16 VAC, the control will imme-
diately de-energize the relay outputs and will not energize any relays
until the voltage level increases.

TEST INPUT

The control includes a TEST input connector that can be used for vari-
ous testing functions during installation and service. The TEST input
connector is shown in Figure  11 "Demand Defrost Control Module".
The following table summarizes the behavior of the control when the
two TEST pins are connected. More detailed descriptions of the various
functions are included in other sections of this document.

FAULT CODE DISPLAY

X/L Output

The X/L terminal of the heat pump control is typically connected to the
X/L input of the room thermostat. The thermostat uses this signal to
notify the homeowner of a problem with the heat pump using an LED or
LCD display. When the control energizes the X/L terminal, the thermo-
stat displays the flash code so the homeowner can see it.

When the control locks out the compressor because of a pressure
switch lockout, it will energize the X/L output as shown in Table 3 "X/L
Output Categories". The control has a three second delay between fault
code flashes.

DEFROST OPERATION

General

The control maintains proper airflow through the outdoor coil during
heating operation by melting frost and ice that may form on the coil.
Frost may accumulate unevenly in different sections of the coil because
of the arrangement of the refrigeration circuit within the coil. The control
may initiate a defrost cycle even when the coil is not completely cov-
ered with frost. This is normal operation.

The control regulates the defrost operation of the heat pump based on
accumulated compressor run time, outdoor coil temperature, and out-
door ambient temperature. The control will cause the unit to operate in
the normal heating mode until it determines that a defrost cycle is
needed.

All defrost timings are based on accumulated compressor run time.

Operation

The defrost mode is equivalent to the cooling mode except that the out-
door fan motor is de-energized. The control shall do the following to ini-
tiate a defrost cycle.

De-energize the outdoor fan

Energize the reversing valve

Energize the auxiliary heat output through the W1/66 terminal.

Begin the maximum defrost cycle length timer

If the call for heating (Y) is removed from the control during the defrost
cycle, it will terminate the defrost cycle and de-energize the compres-
sor. The control will also stop the defrost cycle length timer but not reset
it. When the control receives another call for heating, it will restart the
defrost cycle and the timer at the point at which the call for heating was
removed. This will happen only if the liquid line temperature conditions
allow defrost to occur.

Defrost Curves

The control uses a set of defrost curve parameters that are selected
using the defrost curve selection jumper. The location of the defrost
curve selection jumper is shown in Figure  11 "Demand Defrost Control
Module". Table 4 "Defrost Initiate Curves" shows the jumper position
that is appropriate for each heat pump model. Jumper position 4 is not
used and the control will not allow the compressor to operate when the
jumper is in this position.

Defrost Curve Selection

The factory activates the correct defrost curve during production. They
will place the defrost curve selection jumper in the P position or in a
numbered position appropriate for the specific heat pump model. You
should not have to change the defrost curve selection jumper during ini-
tial installation. 

If the jumper is inadvertently moved, it should be placed in the appropri-
ate numbered location based on the model number and Table 4
"Defrost Initiate Curves". If the factory has activated the curve using the
P position, the jumper may also be returned to that position. If, however,
the factory has not activated the curve in the P position and the jumper
is placed in the P position, the control will not energize the compressor.
The control will also not energize the compressor if the defrost curve
selection jumper is in a numbered position that is not described in
Table 4 "Defrost Initiate Curves" or if the defrost curve selection jumper
is missing. The control will display the proper fault code when a defrost
curve jumper error is present. If the jumper is missing, the control will
behave as if the jumper was in the P position. If the jumper is placed in
a numbered position, the defrost curve selected by the jumper will over-
ride the defrost curve activated at the factory until the jumper is returned
to the P position. The control will display the active defrost curve using
the X/L terminal when the heat pump is operating in a defrost cycle that
has been forced using the TEST inputs.

TABLE 2: 

TEST Input Functionality

Duration of 

connection (seconds)

Control behavior

Less than 2

No response

2-6

Bypass ASCD. If Y is present and pressure switch is closed, contactors will be energized.

Clear lockout

More than 6

Initiate defrost cycle ignoring the liquid line and outdoor ambient temp. Energize X/L with active defrost curve flash code

Connection removed

Terminate defrost as normal.

Connection 

not removed

Continue defrost cycle and X/L flash code until TEST connection removed.

TABLE 3: 

X/L Output Categories

Condition

X/L

Pressure Switch lockout - last mode of operation was heating 2 flashes

Pressure Switch lockout - last mode of operation was defrost 3 flashes

Содержание 13 SEER - THGD

Страница 1: ...As soon as a unit is received it should be inspected for possible dam age during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate req...

Страница 2: ...o the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT The following steps should be performed in order to insure proper sys tem operation and performance 1 Change out o...

Страница 3: ...al vapor lines at least 1 every 20 feet toward the outdoor unit to facilitate proper oil return PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be take...

Страница 4: ...rts except when necessary for servicing the system 12 Release the refrigerant charge into the system Open both the liq uid and vapor valves by removing the plunger cap and with an allen wrench back ou...

Страница 5: ...r and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring opening pro vided and into the unit control box as shown in Figure 5...

Страница 6: ...if the relative humidity in the space is higher than the desired set point of the dehumidification control the variable speed blower motor will operate at lower speed until the dehumidification con t...

Страница 7: ...A DN22U00124 THERMOSTAT Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND...

Страница 8: ...Heat XFMR R 24 Volt Hot Cool XFMR Part Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compres...

Страница 9: ...weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided on the units rating plate for cooling mode only There is no accurate method for chargin...

Страница 10: ...6 93 206 103 236 113 88 52 118 68 148 82 178 94 208 104 238 114 90 54 120 69 150 83 180 94 210 105 240 114 92 55 122 70 152 84 182 95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 1...

Страница 11: ...e defrost cycle it will terminate the defrost cycle and de energize the compres sor The control will also stop the defrost cycle length timer but not reset it When the control receives another call fo...

Страница 12: ...e state of the liquid line temperature and outdoor ambient tem perature inputs The coil does not have to be cold and the outdoor tem perature does not have to be within a certain range for the heat pu...

Страница 13: ...s reset the control will stop displaying the fault code and will respond to thermostat inputs normally INDICATIONS OF PROPER OPERATION Cooling Cooling operation is the same as any conventional air con...

Страница 14: ...ted in U S A 359513 UIM A 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 SECTION X WIRING DIAGRAM...

Отзывы: