430648-JIM-D-1010
2
Johnson Controls Unitary Products
Nomenclature
General
These condensing units are designed for outdoor installation on
a roof or at ground level. Every unit is completely piped and
wired at the factory and is shipped ready for immediate
installation. Only the liquid and suction lines to the evaporator
coil, the filter drier, the thermostat wiring and the main power
wiring are required to complete the installation. Each unit is
dehydrated, evacuated, leak tested and pressure tested at 450
psig before being pressurized with a holding charge of
refrigerant R-410A for shipment and/or storage.
All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wiring
(power and control) can be made through the front of the unit.
Product Category
Product Identifier
C = Standard Efficiency, 2-Pipe, R-410A
D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
J07 = 7.5 Ton
J10 = 10 Ton
J12 = 12.5 Ton
J15 = 15 Ton
J20 = 20 Ton
J25 = 25 Ton
C00 = Cooling Only
Product Options
AA = None
Installation Options
A = None
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Configured Split Condenser Model Number Nomenclature
A = Standard Motor
Airflow
Product Generation
1 = First Generation
Voltage
Heat Type & Nominal Heat Capacity
J20 Y
C00 A T A AA 2 A
Product Style
A = Style A
Y = Split System, Condenser, AC, R-410A
AC = Coil Guard
AB = Phase Monitor
2 = Non Pwr’d Conv Outlet
1 = Disconnect
T = Options 1 & 5
S = Options 5
D = Options 1 & 2
C = Option 2
B = Option 1
Options
5 = Pwr’d Conv Outlet
TB = Technicoat Condenser Coil + Phase
TC = Technicoat Condenser Coil + Coil Guard
TA = Technicoat Condenser Coil
LH = Low A Technicoat Cond. Coil
LG = Low A Technicoat Cond. Coil
LF = Low A Technicoat Cond. Coil
LE = Low A Technicoat Cond. Coil
LD = Low A Phase Monitor
LC = Low A Coil Guard
LB = Low A Phase Monitor
LA = Low Ambient
AE = Phase M Coil Guard
TE = Technicoat Condenser Coil + Coil Guard
+ Coil Guard
+ Phase Monitor
+ Coil Guard
+ Phase M Coil Guard
+ Phase Monitor
Monitor
C
This Split-System (Air Condensing / Heat Pump / Air
Handling) unit is one component of an entire system. As
such it requires specific application considerations with
regard to the rest of the system (air handling unit, duct
design, condensing unit, refrigerant piping and control
scheme).
Failure to properly apply this equipment with the rest of
the system may result in premature failure and/or
reduced performance / increased costs. Warranty
coverage specifically excludes failures due to improper
application and Unitary Products specifically disclaims
any liability resulting from improper application.
Please refer to the equipment Technical Guide,
Installation Manual and the piping applications bulletin
247077 or call the applications department for Unitary
Products @ 1-877-UPG-SERV for guidance.