COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
GCGD60S41S3
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1600
1800
2000
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
55.5
61.1
59.4
62.4
64.9
57.7
62.9
60.1
63.8
66.9
59.9
64.7
60.8
65.3
68.8
S.C.
54.5
49.8
40.0
39.7
28.6
56.4
52.4
42.4
41.2
30.8
58.3
54.9
44.9
42.7
32.9
KW
3.68
3.73
3.74
3.76
3.80
3.77
3.81
3.81
3.85
3.88
3.86
3.90
3.89
3.94
3.95
75
T.C.
54.5
58.5
56.4
60.1
63.1
56.6
60.3
57.4
61.6
65.0
58.8
62.2
58.4
63.1
66.8
S.C.
52.1
48.7
39.2
38.7
28.5
53.9
51.3
41.6
40.4
30.4
55.8
53.9
44.1
42.1
32.4
KW
4.14
4.17
4.17
4.21
4.26
4.23
4.25
4.25
4.29
4.34
4.31
4.34
4.33
4.38
4.42
85
T.C.
53.4
55.9
53.3
57.7
61.4
55.5
57.8
54.7
59.3
63.1
57.7
59.7
56.0
60.8
64.8
S.C.
49.7
47.6
38.3
37.7
28.4
51.5
50.2
40.8
39.6
30.1
53.2
52.8
43.2
41.5
31.8
KW
4.59
4.61
4.60
4.66
4.71
4.68
4.69
4.69
4.74
4.80
4.77
4.77
4.77
4.82
4.89
95
T.C.
52.4
53.4
50.3
55.4
59.6
54.4
55.3
51.9
57.0
61.2
56.5
57.2
53.6
58.6
62.7
S.C.
47.3
46.5
37.5
36.7
28.4
49.0
49.1
40.0
38.8
29.8
50.6
51.8
42.4
40.9
31.2
KW
5.05
5.05
5.03
5.10
5.17
5.13
5.13
5.12
5.18
5.26
5.22
5.21
5.21
5.26
5.35
105
T.C.
49.4
50.0
46.7
51.7
55.4
51.7
52.0
48.3
53.3
57.2
54.0
53.9
50.0
54.9
58.9
S.C.
44.6
44.4
36.2
35.2
26.9
46.3
46.6
38.6
37.4
28.4
48.0
48.9
41.0
39.5
29.8
KW
5.64
5.63
5.61
5.70
5.78
5.73
5.72
5.70
5.78
5.87
5.83
5.81
5.80
5.86
5.97
115
T.C.
46.6
46.7
43.3
48.1
51.4
49.1
48.7
44.8
49.7
53.3
51.5
50.8
46.4
51.3
55.2
S.C.
42.0
42.3
34.9
33.8
25.4
43.7
44.2
37.3
36.1
27.0
45.5
46.1
39.7
38.3
28.5
KW
6.21
6.20
6.17
6.29
6.37
6.32
6.30
6.27
6.37
6.47
6.42
6.40
6.36
6.45
6.57
125
T.C.
43.7
43.5
39.8
44.5
47.3
46.4
45.5
41.3
46.1
49.4
49.1
47.6
42.9
47.7
51.5
S.C.
39.3
40.3
33.7
32.5
24.0
41.1
41.8
36.0
34.7
25.6
43.0
43.2
38.3
37.0
27.2
KW
6.79
6.77
6.73
6.87
6.96
6.90
6.88
6.83
6.95
7.06
7.01
6.98
6.93
7.03
7.16
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC62
1.00
1.00
1.00
–
FC64
1.00
1.01
0.98
–
UC60
1.00
1.00
1.00
AHE60
–
1.03
1.03
0.98
AHP60
–
1.00
1.00
1.00
AHR60
–
1.00
1.00
1.00
AHX60
–
1.03
1.04
0.98
AV*60
–
1.02
1.01
1.02
MV20D
FC/MC60D
1.00
1.00
1.00
MV20D
FC/MC62D
1.00
1.00
1.00
MV20D
FC64D
1.00
1.01
0.96
MX20D
FC/MC60D
1.01
1.01
0.96
MX20D
FC/MC62D
1.02
1.01
0.95
MX20D
FC64D
1.03
1.03
0.94
F5FP060
–
1.00
1.00
1.00
F6FP060
–
1.01
1.01
0.96
F4FV060 –
1.00
1.00
1.00
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C16
FC/PC60C
0.99
0.98
0.99
T*(8,L)X*C20
FC/MC/PC60D
1.00
0.98
1.00
T*9X*C16
FC/PC60C
0.99
0.98
0.99
T*9X*C20
FC/PC60C
0.99
0.98
0.99
T*9X*D20
FC/MC/PC60D
1.00
0.98
1.00
T*9X*C20
FC/MC/PC60D
0.98
0.97
0.98
T*(8,L)X*C20
FC/MC62D
0.99
1.00
0.99
T*(8,L)X*C16
UC60C
0.98
0.97
0.98
T*(8,L)X*C20
UC60D
0.98
0.97
0.98
T*9X*D20
UC60D
0.98
0.97
0.98
T*(8,L)X*C20
UC60D
0.99
1.00
0.99
T*9X*C20
UC60D
0.98
0.97
0.98
(T*9C/T*9V)*D20
FC/MC/PC60D
0.97
0.96
0.97
(T*(8,L)C/T*8V)*C20 FC/MC62D
0.99
0.97
0.99
(T*9C/T*9V)*C20
FC/MC62D
0.98
0.97
0.98
(T*9C/T*9V)*D20
FC/MC62D
0.98
0.97
0.98
(T*(8,L)C/T*8V)*C20 FC/PC60C
0.97
0.96
0.97
(T*9C/T*9V)*C20
FC/PC60C
0.96
0.96
0.96
(T*(8,L)C/T*8V)*C20 UC60C
0.95
0.91
0.95
(T*9C/T*9V)*C20
UC60C
0.94
0.91
0.96
(T*9C/T*9V)*D20
UC60D
0.94
0.91
0.95