556452-UTG-C-0611
Johnson Controls Unitary Products
15
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per
degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
GCGD24S41S3
INDOOR COIL MODEL NO.
FC/MC/PC36
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
20.5
25.5
25.4
27.0
28.2
22.6
26.7
26.5
28.3
29.5
24.7
28.0
27.7
29.6
30.8
S.C.
20.5
19.1
16.6
16.3
13.3
22.6
22.0
18.8
18.0
14.2
24.7
24.9
21.0
19.7
15.1
KW
1.66
1.67
1.67
1.67
1.67
1.73
1.74
1.74
1.74
1.74
1.81
1.81
1.82
1.82
1.82
75
T.C.
19.1
23.5
23.4
25.5
27.2
21.4
25.0
24.7
26.9
28.6
23.7
26.4
26.0
28.2
29.9
S.C.
19.1
18.5
15.7
15.8
12.8
21.4
21.1
18.0
17.6
13.8
23.7
23.8
20.4
19.4
14.9
KW
1.79
1.80
1.80
1.81
1.82
1.87
1.87
1.88
1.89
1.90
1.95
1.95
1.95
1.97
1.98
85
T.C.
17.7
21.6
21.3
24.0
26.3
20.2
23.2
22.8
25.4
27.6
22.7
24.8
24.3
26.9
28.9
S.C.
17.7
17.9
14.9
15.3
12.3
20.2
20.3
17.3
17.2
13.5
22.7
22.7
19.7
19.1
14.6
KW
1.92
1.92
1.92
1.95
1.98
2.01
2.01
2.01
2.04
2.06
2.09
2.10
2.09
2.12
2.14
95
T.C.
16.3
19.6
19.3
22.5
25.3
19.0
21.5
21.0
24.0
26.7
21.7
23.3
22.6
25.5
28.0
S.C.
16.3
17.3
14.1
14.7
11.9
19.0
19.5
16.5
16.8
13.1
21.6
21.6
19.0
18.9
14.4
KW
2.05
2.05
2.05
2.09
2.14
2.14
2.15
2.14
2.18
2.22
2.24
2.24
2.23
2.27
2.30
105
T.C.
15.0
17.7
17.1
20.1
23.1
17.4
19.5
18.8
21.6
24.4
19.8
21.3
20.4
23.1
25.8
S.C.
15.0
15.9
13.1
13.8
11.1
17.4
17.8
15.3
15.9
12.5
19.8
19.8
17.4
18.0
13.9
KW
2.17
2.17
2.16
2.22
2.28
2.28
2.28
2.26
2.31
2.37
2.38
2.39
2.36
2.41
2.45
115
T.C.
13.8
15.8
15.0
17.9
20.9
15.9
17.6
16.6
19.3
22.2
18.0
19.4
18.3
20.7
23.6
S.C.
13.8
14.6
12.1
12.9
10.4
15.9
16.3
14.0
15.0
11.8
17.9
17.9
15.8
17.1
13.3
KW
2.29
2.29
2.27
2.34
2.41
2.41
2.41
2.38
2.44
2.51
2.53
2.53
2.49
2.54
2.60
125
T.C.
12.5
13.9
12.8
15.7
18.7
14.4
15.7
14.5
17.0
20.1
16.2
17.5
16.2
18.4
21.4
S.C.
12.5
13.4
11.2
12.0
9.6
14.4
14.7
12.7
14.1
11.2
16.1
16.4
14.3
16.2
12.8
KW
2.41
2.41
2.38
2.46
2.55
2.54
2.54
2.50
2.56
2.65
2.67
2.67
2.61
2.67
2.75
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC32
1.00
1.00
1.00
–
FC/MC/PC35
1.00
1.00
1.00
–
FC/MC/PC37
1.00
1.00
1.00
–
FC/MC/PC43
1.00
1.00
1.00
–
UC36
1.00
1.00
1.00
AHE24
–
1.02
1.04
0.93
AHE30
–
1.02
1.04
0.93
AHE36
–
1.05
1.11
0.92
AHP30
–
1.00
1.01
1.00
AHR24
–
0.99
0.99
0.99
AHX30
–
1.00
1.01
0.92
AHX36
–
1.00
1.01
0.92
AV*36
–
1.00
1.04
0.92
MV12B
FC/MC36B
1.00
1.04
0.92
MV12B
FC/MC35B
1.00
1.04
0.92
MV12B
FC/MC43B
1.00
1.04
0.92
MX12B
FC/MC35B
1.03
1.04
0.91
MX12B
FC/MC36B
1.01
1.01
0.91
MX12B
FC/MC43B
1.03
1.02
0.90
F4FP36
–
1.00
1.00
1.00
F6FP030
–
1.00
1.01
0.93
F6FP036
–
1.00
1.02
0.92
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*A12
FC/MC/PC32A
1.00
1.01
0.96
T*(8,L)X*B12
FC/MC/PC35B
1.00
1.02
0.92
T*9X*C16
FC/MC/PC35C
0.99
0.98
0.91
T*9X*C20
FC/MC/PC35C
1.00
1.02
0.92
T*(8,L)X*A12
FC/MC/PC36A
1.00
1.01
0.92
T*(8,L)X*B12
FC/MC/PC36B
1.00
1.01
0.92
T*9X*B12
FC/MC/PC36B
1.00
1.01
0.92
T*9X*C16
FC/MC/PC36C
1.00
1.01
0.92
T*9X*C20
FC/MC/PC36C
1.00
1.01
0.92
T*(8,L)X*A12
FC/MC/PC37A
1.00
1.02
0.92
T*(8,L)X*B12
FC/MC/PC43B
1.00
1.02
0.92
(T*(8,L)C/T*8V)*A12
FC/MC/PC32A
1.00
1.02
0.96
(T*(8,L)C/T*8V)*B12
FC/MC/PC35B
1.00
1.01
0.92
(T*9C/T*9V)*B12
FC/MC/PC35B
1.00
1.02
0.92
(T*(8,L)C/T*8V)*A12
FC/MC/PC36A
1.00
1.01
0.92
(T*(8,L)C/T*8V)*B12
FC/MC/PC36B
1.00
1.02
0.92
(T*9C/T*9V)*B12
FC/MC/PC36B
1.00
1.01
0.92
(T*(8,L)C/T*8V)*A12
FC/MC/PC37A
1.00
1.02
0.92
(T*(8,L)C/T*8V)*B12
FC/MC/PC43B
1.00
1.01
0.92
(T*9C/T*9V)*B12
FC/MC/PC43B
1.00
1.02
0.92
(T*(8,L)C/T*8V)*A12
UC36A
0.98
0.99
0.94
(T*(8,L)C/T*8V)*B12
UC36B
0.98
1.00
0.94
(T*9C/T*9V)*B12
UC36B
0.98
1.00
0.94