background image

7

Sales/Replacement Telephone 01604 762881

7. 

PREPARATION & POSITIONING

7.1  

DUCTING INFORMATION

7.1.1 

It is an advantage to have all the compatible ductwork already installed and ready to connect to the 
appliance spigots.

7.1.2 

Ducting passing through unheated roof voids must be insulated. Ducting runs should be as straight as 
possible and the horizontal exhaust ducting should always slope downwards from the Q-Vent Compact-L 
unit.

7.1.3 

The recommended types of ducting are:- rigid plastic and spiral wound duct.

7.1.4 

For any exhaust duct passing through a roof use a suitable Vertical Terminal or Ridge Terminal. For exhaust/
supply terminals in high rise applications a purpose designed, high rise terminal MUST be used. For details 
on Johnson & Starley ‘high rise’ terminal colours and sizes see Table 3.

                       * Ensure gravity flaps are removed

7.2  

POSITIONING THE UNIT

7.2.1 

Ensure there is adequate access for installation and maintenance. Ensure the selected electrical mains 
wiring has as an isolator near by for servicing.

NOTE: 

The appliance is for suspended applications only.

7.2.2 

This unit is typically installed in a ceiling void, but if this is not practicable it can be positioned in the loft 
or any other suitable location. Also make sure when choosing the location to take into consideration the 
accessibility of the control, the exhaust exit position, the electrical services, and the required RH path for 
the condense drain.

7.2.3 

It is the responsibility of the installer to ensure that all aspects of the system design are taken into 
consideration. The system is designed as a ducted unit and should only be used in ducted situations. 
Ensure ductwork is supported throughout it’s length.

7.2.4 

The unit has 4 connection spigots and each one is labelled. Ensure that the correct duct is connected to the 
appropriate spigot.

7.2.5 

Consideration must be given to access and servicing. The servicing of the fans and the cleaning of the heat 
exchanger should be carried out annually. Filters are to be cleaned as required.

 

PLEASE NOTE:

 A clear space of at least 500mm x 500mm is required to allow the cover to be removed and 

provide sufficient access for maintenance.

7.3  

SPIGOTS

7.3.1 

The unit is supplied with 100mm/125mm spigots. For satisfactory operation of the unit, ensure ducting used 
is as detailed on the design drawing. Any deviation from the design drawing could lead to noise increase 
on boost.

NOTE: 

In situations where it is either not possible or not desirable to use 125mm ducting, 100mm ducting can be 
used but it MUST be noted, in ‘BOOST’ mode, might increase noise levels.

7.4  

CONDENSATE 

 IMPORTANT:

 At times the unit will produce condensate which MUST be drained away. The unit is provided 

with a drain connection.

7.4.1 

When using the condense adapter, you 

MUST

 use Rigid PVC-U ¾”/19mm push fit pipe. 

 IMPORTANT:

 DO NO USE A SOLVENT WELD on this joint. This joint 

has

 to be disconnected when removing 

the heat exchanger for periodic servicing and maintenance.

7.4.2 

When using 10mm flexible condense pipe, cut the condense adapter off and use the straight hose connector 
supplied. Do not leave any kinks in the condense pipe.

7.4.3 

The unit has a condense anti flood device built in.

 NOTE:

 Fan will stop and a red LED will flash once every 3 seconds if the condense drain path is blocked 

and unit goes into anti flood mode.

TABLE 3.  ‘HIGH RISE’ TERMINAL PART NUMBERS

FINISH

100mm

(4”)

123mm

(5”)

130mm*

(6”)

WHITE

1000-0004790

1000-00005350

1000-0005530

BEIGE

1000-0004810

1000-0005370

1000-0005550

BROWN

1000-0004800

1000-0005360

1000-0005540

TERRACOTTA

1000-0004820

1000-0005380

1000-0005560

Содержание Q-VENT COMPACT-L

Страница 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Q VENT COMPACT L High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the user Publication No ZZ...

Страница 2: ...cal Room Layout 8 Duct Duct Connections 9 9 Installation Instructions 10 10 Electrical 10 11 Fan Performance Graph 10 12 Circuit Diagrams 11 13 Commissioning 12 Pre Commissioning Check Fan Adjustment...

Страница 3: ...single duct and grille 2 2 The case is constructed in aluminium zinc coated steel Internal faces of the casing are acoustically lined with flame retardant acoustic foam 2 3 The unit is fitted with a...

Страница 4: ...L H Fixing Bracket Screws 2 3 6mm x 19mm 21 3mm Condense Adapter 1 4 10mm Straight Hose Connector 1 5 Installation Servicing Maintenance Instructions 1 PCB RTC PCB FEATURES 18 RV1 Speed Adjuster 19 R...

Страница 5: ...be in accordance with the appropriate standards The equipment must be provided with a local triple pole isolator switch 3 3 Ensure safety regulations and practices are adhered to when installing and...

Страница 6: ...79 Sound Power Level LWA 42 Reference Flow Rate m h 72 Reference Pressure Difference Pa 50 SPI W m h 0 500 CONTROL FACTOR TYPOLOGY Control Factor and Control Typology 0 65 Local Demand Control INTERN...

Страница 7: ...h 7 2 4 The unit has 4 connection spigots and each one is labelled Ensure that the correct duct is connected to the appropriate spigot 7 2 5 Consideration must be given to access and servicing The ser...

Страница 8: ...elative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment and necessary adjustment made before proceeding any further NOTE The Q Vent Comp...

Страница 9: ...he rigid ducting to grilles and the unit should be made with a flexible connection 8 4 The duct layout must be designed to suit the requirements for the ventilation recovery system and building layout...

Страница 10: ...ARTHED ALL WIRING MUST CONFORM TO INSTITUTE OF ELECTRICAL ENGINEERS I E E REGULATIONS BS 7671 10 1 The unit is suitable for a 230V 50Hz single phase supply fused at 3A 10 2 The unit needs a mains flex...

Страница 11: ...lacement Telephone 01604 762881 12 CIRCUIT DIAGRAMS FIGURE 10 Q VENT COMPACT L WIRING DIAGRAMS COLOUR CODE BN BROWN BU BLUE BK BLACK GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW FIGURE 11 JS9 SWITCH WI...

Страница 12: ...le see paragraph 13 4 4 13 3 4 To set boost see paragraph 13 5 4 13 3 5 Once both setting are correct press installer mode switch 13 3 6 When out of installer mode the Red LED will stop flashing NOTE...

Страница 13: ...rate decreases lowering the thermal heat recovery through the heat exchanger lowering the supply air temperature NOTE If fans do not boost with mains present at the switched live terminal block then p...

Страница 14: ...SWITCH FUNCTIONS Information Only SWITCH SWITCH POSITION DEFAULT SETTINGS SWITCH POSITION 1 ON Both fans externally controlled at the same time OFF Single fan externally controlled supply fan with CT...

Страница 15: ...r cleaning 14 3 The supply and extract fans and heat exchanger need cleaning annually See Paragraph 14 5 14 7 14 4 GAINING ACCESS TO THE UNIT 14 4 1 To gain access to the unit remove the 2 magnetic fi...

Страница 16: ...WATER OR ANY OTHER FLUIDS NOTE Under no circumstance must any sharp implements which are likely to distort or puncture the heat exchanger air passage walls be used 14 5 5 Wipe clean the condensate tr...

Страница 17: ...shaped tool push the battery out of the casing and replace with new 14 8 5 If there is no power from the mains and battery and the unit is dead Replace the battery before using the RTC Kit to set the...

Страница 18: ...www johnsonandstarley co uk 18 FIGURE 21 Q VENT COMPACT L DIMENSIONS 16 DIMENSIONS...

Страница 19: ...18 SPARES LIST 2 1 3 6 4 3 ITEM PART No DESCRIPTION QTY 1 HR36 0119005 Air Circulation Fan Assembly Complete 1 2 HR36 0116005 Heat Exchanger Condense Tray Assembly Complete 1 3 HR34 0120055 Front Cove...

Страница 20: ...7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales joh...

Отзывы: