Johnson & Starley JANSTAR Скачать руководство пользователя страница 6

ZZ757/9

6

7.6.1

If the burner fails to light (amber ‘

LOCKOUT

’ illuminated): Reinstate the ignition sequence by allowing 10

seconds to elapse, and then press and release the ‘RESET’ button.

7.6.2

If the burner ignites but then extinguishes: An automatic purging sequence will take place, which lasts for
approximately 30 seconds. Following this, a second ignition will take place.

7.7

Set the time control (if fitted) to the required ‘Heating On’ periods and adjust the Thermista-stat to the desired comfort
setting. The burner will then initially operate at maximum output until it reaches the set comfort level, whereby the heater
modulates to maintain the required comfort level.

7.8

BURNER PRESSURE CHECK:

Note: The Burner pressure is factory set and MUST NOT BE ADJUSTED.

7.8.1

Turn the gas and electrical supplies to OFF.

7.8.2

Link Terminal block connection ‘

3

’ to ‘

TEST

’ terminal.

7.8.3

Referring to Fig. 5, remove and retain the Burner Pressure Test Point blanking screw, and fit pressure a test gauge
to the test point.

7.8.4

Turn

 

ON the gas and electrical supplies.

7.8.5

Reinstate the ignition sequence as detailed in sub-para 7.6.1

7.8.6

Ensure that the burner ignites, and allow 15 minutes of operation to elapse to ensure stability.

7.8.7

Referring to Table 3, ensure that the burner pressure is within the limits specified for the installed flue length.

7.8.8

If the differential burner pressure is not within the limits stated, run the appliance for a further 10 minutes and
then re-check the burner pressure. If the pressure is still not within the stated limits, contact Johnson and Starley
Ltd. Service Department, since rectification requires the use of special equipment.

7.8.9

Turn the gas and electrical supplies to OFF.

7.8.10 Remove the link from Terminal block connection ‘

3

’ to ‘

TEST

’ terminal.

7.8.11 Remove the pressure test gauge, and refit pressure test point blanking screw.

7.8.12 Turn

 

ON the gas and electrical supplies.

7.9

WARM AIR SYSTEM BALANCING:

7.9.1

Set the Thermista-stat to the 

‘SUMMER AIRFLOW’

 position (fully clockwise switched position), and check

that the air circulation fan is running  full speed, without the burner operating.

7.9.2

Balance the system to provide the required volume proportions at the warm air outlets.

Note: 

If the system includes ceiling diffusers, it is important that the velocities of air through these (except in

very small rooms such as bathrooms) are at least 1.5m/s (300ft/min). In order to achieve this, it may be necessary
to blank off part of the outlet face.

7.9.3

Reset the Thermista-stat to the require comfort level setting.

7.10

AUTOMATIC CONTROLS CHECK:  

Lighting the heater and allowing it to operate for a short time will effectively

check these controls.

7.11

SAFETY CHECK:

7.11.1 Turn OFF the gas supply at service cock and ensure that Multifunctional control fail-safe operates (indicated by

loud click from Multifunctional control).

7.11.2 Turn the gas supply ON at service cock, and ensure that the burner ignites.

7.12

FAN PERFORMANCE: 

No provision is made for fan speed adjustment, since the fan speed is automatically determined

by  the appliance, and the demand for heat.

HORIZONTAL FLUE

   VERTICAL FLUE

     APPLICATIONS

     APPLICATIONS

kW

MJ/h

Btu/h

kW

MJ/h

Btu/h

INPUT

9.80

35.3

33,500

10.5

37.8

35,800

OUTPUT

 

8.0

29.0

27,300

8.57

30.86

29,200

Gas rate cv

0.92m

3

/h (32.3 ft

3

/h)

1037 Btu/h

Burner  setting

      

8.9mbar (3.6 in wg)

  10.2mbar (4.1 in wg)

pressure (hot)

Main Injector

BRAY 15/850

Table 3

Main Burner Pressure Settings

ZZ757/9

9

9.8

TRANSFORMER REMOVAL:

9.8.1

Ensure that the electrical supply is switched off.

9.8.2

Remove the heater front cover.

9.8.3

Remove the 2 x screws securing the heater front door, and open front door.

9.8.4

Disconnect the leads from the transformer.

9.8.5

Release 2 x securing screws, nuts and lock washers, and withdraw transformer from the electrical panel.

9.8.6

Refitting or replacement is in reverse order, ensuring the leads are correctly reconnected to the transformer.

9.9

IGNITION/DETECTION ELECTRODE REMOVAL:

9.9.1

Referring to 9.3, remove the burner assembly.

9.9.2

Remove the securing nut and washer, and carefully remove the electrode from the burner.

9.9.3

Refitting or replacement is in reverse order, taking care to avoid bending the electrode since its profile is critical.

9.10

IGNITION MODULE REMOVAL:

9.10.1 Ensure that the electrical supply is switched off.

9.10.2 Remove the heater front cover.

9.10.3 Remove the 2 x screws securing the heater front door, and open front door.

9.10.4 Disconnect the ignition lead from the ignition module.

9.10.5 Disconnect the ignition module edge connector plug.

9.10.6 Remove the 2 x securing screws and withdraw the ignition module.

9.10.7 Refitting or replacement is in reverse order.

9.11

CONTROL MODULE REPLACEMENT:

9.11.1 Ensure that the electrical supply is switched off.

9.11.2 Remove the heater front cover.

9.11.3 Remove the 2 x screws securing the heater front door, and open front door.

9.11.4 Disconnect the ribbon cable from the combustion air fan, by gripping the plug.

 Do not pull on the ribbon cable.

9.11.5 Disconnect the 2 x grey, and 1 x violet conductors from the transformer.

9.11.6 Disconnect the following conductors from the listed terminal strip connections:

a.

Pink from ‘

3

’,

b.

Pink from ‘

4

’,

c.

White from ‘

5

’,

d.

Yellow from ‘

10

’,

e.

Orange from ‘

12

’,

f.

Orange from ‘

13

’,

g.

Red from ‘

14

’,

h.

Blue from ‘

15

’.

9.11.7 Remove the 2 x securing screws and nuts, and remove the control module.

9.11.8 Refitting or replacement is in reverse order.

9.12

COMBUSTION AIR FAN REMOVAL:

9.12.1 Ensure that the electrical supply is switched off.

9.12.2 Remove the heater front cover.

9.12.3 Remove the 2 x screws securing the heater front door, and open front door.

9.12.4 Disconnect the ribbon cable from the combustion air fan, by gripping the plug.

 Do not pull on the ribbon cable.

9.12.5 Remove 2 x screws securing the 6mm pipe to the combustion air fan,  release the tubing nut at the multifunctional

control, and withdraw the 6mm pipe complete with clamping plate and gasket.

9.12.6 Remove the upper and lower screws securing combustion air fan, and withdraw the fan complete with gasket.

9.12.7 Refitting or replacement is in reverse order.

Important: 

Ensure that both gaskets are undamaged, and that the flue connection is sound. Only use the securing

screws supplied, as longer screws will cause damage to the heat exchanger.

Содержание JANSTAR

Страница 1: ...o an upflow model The appliance may be base duct mounted The JANSTAR is also provided with the facility for connection to a remote time control not supplied with volt free contacts i e The switching s...

Страница 2: ...n with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the relevant section of BS5864 provided that in addition all internal surfaces includ...

Страница 3: ...ction meeting the outer side of the wall or roofing at the point where it begins to flare out refer to Fig 2 One 90o horizontal bend is equivalent to 1m of straight flue a 45o horizontal bend is equiv...

Страница 4: ...the connections to the fan are sound and then if necessary change the control module followed by the combustion air fan 10 4 3 If lockout occurs and it is known that gas is being supplied to the appl...

Страница 5: ...e 7 1 5 Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots 7 2 Turn ON the gas supply to the heater 7 3 Test for gas soundness at supply Multifunctio...

Страница 6: ...utomatically determined by the appliance and the demand for heat HORIZONTALFLUE VERTICAL FLUE APPLICATIONS APPLICATIONS kW MJ h Btu h kW MJ h Btu h INPUT 9 80 35 3 33 500 10 5 37 8 35 800 OUTPUT 8 0 2...

Страница 7: ...OF INJECTOR 9 6 1 Referring to 9 3 remove the burner assembly 9 6 2 Using 14mm A F ring spanner undo the nut and washer and remove injector from burner manifold 9 6 3 Refitting or replacement is in re...

Страница 8: ...OF INJECTOR 9 6 1 Referring to 9 3 remove the burner assembly 9 6 2 Using 14mm A F ring spanner undo the nut and washer and remove injector from burner manifold 9 6 3 Refitting or replacement is in re...

Страница 9: ...utomatically determined by the appliance and the demand for heat HORIZONTALFLUE VERTICAL FLUE APPLICATIONS APPLICATIONS kW MJ h Btu h kW MJ h Btu h INPUT 9 80 35 3 33 500 10 5 37 8 35 800 OUTPUT 8 0 2...

Страница 10: ...e 7 1 5 Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots 7 2 Turn ON the gas supply to the heater 7 3 Test for gas soundness at supply Multifunctio...

Страница 11: ...the connections to the fan are sound and then if necessary change the control module followed by the combustion air fan 10 4 3 If lockout occurs and it is known that gas is being supplied to the appl...

Страница 12: ...ction meeting the outer side of the wall or roofing at the point where it begins to flare out refer to Fig 2 One 90o horizontal bend is equivalent to 1m of straight flue a 45o horizontal bend is equiv...

Страница 13: ...n with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the relevant section of BS5864 provided that in addition all internal surfaces includ...

Страница 14: ...amix 828 245 534 1000 0704490 Ignition detection electrode 1 245 535 1000 0516440 Fan delay overheat limit control 1 245 536 1000 0516400 Electronics module 1 245 537 1000 0516250 Transformer 1 245 52...

Страница 15: ...o an upflow model The appliance may be base duct mounted The JANSTAR is also provided with the facility for connection to a remote time control not supplied with volt free contacts i e The switching s...

Отзывы: