Johnson & Starley JANSTAR Скачать руководство пользователя страница 2

Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS7671 Institute of Electrical Engineers (IEE.) Wiring Regulations
BS6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS5440 Pt.1 (Flues for Gas Appliances)
BS5440 Pt.2 (Air Supply for Gas Appliances)
BS5864 Installation of Gas Fired Ducted Air Heaters
British System Design Manual “Gas Fired Warm Air Heating”
Model and Local Authority Bye-laws

IMPORTANT: STATUTE LAW DEFINES THAT ALL GAS APPLIANCES MUST BE INSTALLED BY COMPETENT
PERSONS, (i.e. CORGI REGISTERED INSTALLERS) IN ACCORDANCE WITH THE GAS SAFETY (INSTALLATION
AND USE) REGULATIONS (CURRENT EDITION). FAILURE TO COMPLY WITH THESE REGULATIONS MAY
LEAD TO PROSECUTION.

2.

HEATER COMPARTMENT AND CLEARANCES

 (See BS5864)

2.1

A minimum clearance of 15mm (

5

/

8

 in) at either side of the heater, and 150mm (6in) above the heater, should be allowed.

For service access, a minimum of 450mm (18in) is required at the front of the heater, and 75mm at the left hand side.
Space must also be allowed, in a compartment installation, to permit the removal of the heater. If a Cleanflow electronic
air filter is to be fitted in the compartment, allowance must be made for this in the width of the compartment. The
compartment must be of a fixed rigid structure and the internal construction must be of half-hour fire resistance to
internal fire; the inside lining or finishing of the enclosure must be noncombustible or a class 1 finish (see also BS 476).

2.2

In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of
BS 5864 and must be completely separated by either a noncombustible partition or a perforated metal partition with the

perforations not exceeding 13mm (0.5in).

2.3

In under-stair installations, the compartment must comply with the relevant section of BS5864, provided that, in addition,

all internal surfaces, including the base, are of, or lined with noncombustible material.

3.

VENTILATION AND COMBUSTION AIR

3.1

A room sealed appliance does not require a combustion air vent in the room or internal space in which it is installed. If
the appliance is installed in a compartment, the minimum total free area of the high and low level ventilation air vents
must be as specified in Table 1 below, (in reference to BS5440 Pt 2, Table 1).

2

ZZ757/9

Position of

Air from room

Air direct

air vents

or internal space

from outside

High level

89cm

2

 (14 in

2

)

45cm

2

 (7 in

2

)

Low level

89cm

2

 (14 in

2

)

45cm

2

 (7 in

2

)

TABLE 1

MINIMUM EFFECTIVE AREAS

4.

ADAPTING TO RIGHT HAND AIR ENTRY

4.1

Remove the return air spigot and the short side cover from the left hand side of the appliance, and lay to one side.

4.2

Remove the long side cover from the right hand side of the appliance, and reassemble it on the left hand side, ensuring
that the 

slots are towards the front

 of the appliance.

4.3

Reassemble the short side cover and the return air spigot ton the right side of the appliance, ensuring that the 

slots in the

side cover are towards the front

 of the appliance.

5.

DUCT SYSTEM

(See British Design Manual - Gas Fired Warm Air Heating).

IMPORTANT:  All duct work MUST be mechanically secured, and sealed with ducting tape.

5.1

RETURN AIR

5.1.1

Room sealed appliances may be installed without return air ducting, provided that the path between the return air
grille and the appliance return air inlet is protected in such a manner that the required airflow will be maintained at
all times. Where no ducting is fitted, a finger guard (Ref. FGJ, available from Johnson and Starley Ltd.), MUST be
fitted.

13

ZZ757/9

Fig. 7 JANSTAR functional flow circuit diagram

268

44

40

122

600

830

Return air

plenum

Warm air

plenum

Fixing holes
in rear face

440

75

285

190

Flue
Spigot

Rear face

Fig. 8 Principal dimensions (mm)

Содержание JANSTAR

Страница 1: ...o an upflow model The appliance may be base duct mounted The JANSTAR is also provided with the facility for connection to a remote time control not supplied with volt free contacts i e The switching s...

Страница 2: ...n with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the relevant section of BS5864 provided that in addition all internal surfaces includ...

Страница 3: ...ction meeting the outer side of the wall or roofing at the point where it begins to flare out refer to Fig 2 One 90o horizontal bend is equivalent to 1m of straight flue a 45o horizontal bend is equiv...

Страница 4: ...the connections to the fan are sound and then if necessary change the control module followed by the combustion air fan 10 4 3 If lockout occurs and it is known that gas is being supplied to the appl...

Страница 5: ...e 7 1 5 Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots 7 2 Turn ON the gas supply to the heater 7 3 Test for gas soundness at supply Multifunctio...

Страница 6: ...utomatically determined by the appliance and the demand for heat HORIZONTALFLUE VERTICAL FLUE APPLICATIONS APPLICATIONS kW MJ h Btu h kW MJ h Btu h INPUT 9 80 35 3 33 500 10 5 37 8 35 800 OUTPUT 8 0 2...

Страница 7: ...OF INJECTOR 9 6 1 Referring to 9 3 remove the burner assembly 9 6 2 Using 14mm A F ring spanner undo the nut and washer and remove injector from burner manifold 9 6 3 Refitting or replacement is in re...

Страница 8: ...OF INJECTOR 9 6 1 Referring to 9 3 remove the burner assembly 9 6 2 Using 14mm A F ring spanner undo the nut and washer and remove injector from burner manifold 9 6 3 Refitting or replacement is in re...

Страница 9: ...utomatically determined by the appliance and the demand for heat HORIZONTALFLUE VERTICAL FLUE APPLICATIONS APPLICATIONS kW MJ h Btu h kW MJ h Btu h INPUT 9 80 35 3 33 500 10 5 37 8 35 800 OUTPUT 8 0 2...

Страница 10: ...e 7 1 5 Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots 7 2 Turn ON the gas supply to the heater 7 3 Test for gas soundness at supply Multifunctio...

Страница 11: ...the connections to the fan are sound and then if necessary change the control module followed by the combustion air fan 10 4 3 If lockout occurs and it is known that gas is being supplied to the appl...

Страница 12: ...ction meeting the outer side of the wall or roofing at the point where it begins to flare out refer to Fig 2 One 90o horizontal bend is equivalent to 1m of straight flue a 45o horizontal bend is equiv...

Страница 13: ...n with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the relevant section of BS5864 provided that in addition all internal surfaces includ...

Страница 14: ...amix 828 245 534 1000 0704490 Ignition detection electrode 1 245 535 1000 0516440 Fan delay overheat limit control 1 245 536 1000 0516400 Electronics module 1 245 537 1000 0516250 Transformer 1 245 52...

Страница 15: ...o an upflow model The appliance may be base duct mounted The JANSTAR is also provided with the facility for connection to a remote time control not supplied with volt free contacts i e The switching s...

Отзывы: