Johnson & Starley JANSTAR Mk 2 Скачать руководство пользователя страница 12

ZZ 1019/1E

5

6.3

CONDENSATE

6.3.1

When firing , the unit may produce condensate which must be drained away. A JDT1 kit, which externally drains
the condensate away from the flue terminal is available for horizontal flued applications. Vertical flued
applications require the fitment of an in-line condensate trap within 0.5 m of the unit, in the first vertical flue run,
and before any bends in the flue run. Such a trap, with a 32 mm male drainage connection, is available for this
purpose.

6.3.2

Condensate from vertical flued applications must be drained away using 32 mm or 20 mm internal diameter, rigid
plastic pipe, connected to the condensate drain using KUTERLITE 700 or similar straight coupling. The pipe
should be installed in such a manner, that it forms a continuous downward slope away from the unit at a minimum
3

o

 angle (6 mm per 100 mm, or, 0.75 in per foot run), and that the risk of mechanical damage and interior

interference is minimised. The pipe is to be protected against frost damage.

6.4

ELECTRICAL

6.4.1

Mains:

     The heater is supplied with mains cable (PVC sheathed, high temperature resistant, 3 core [Brown-

Blue-Green/Yellow], 6A, 0.75mm

2

), connected to a terminal block and exiting from the heater at the bottom right

hand rear. The cable is suitable for a 230V 50Hz single phase supply and must be protected by a 5A fuse, and an
earth wire must be connected. This cable must only be replaced by either the maunfacturer or a recognised and
qalified service engineer.A double pole switch or fused spur box should also be used. All wiring conform to I.E.E.
regulations, (current edition).

6.4.2

Thermostat:     

A Thermostat is provided with the appliance. The Thermostat wiring is to be connected to

terminals 6 and 7 on the air heater  control panel, (marked ‘THERMOSTAT’), polarity being unimportant. It should
be located where there is free air circulation, and approximately 1.5m (5ft) from the floor. The following
locations should be avoided.

a.

In a room where temperature is greatly affected by the sun or any other heat source (e.g. radiant fire, wall
light fitting or TV set).

b.

Near an outside door or windows, or on an outside wall.

c.

Where it can be affected by warm air ducts, diffusers, waste pipes or the heater itself.

d.

Where it can be subject to vibration.

6.4.3

Time Control:

     If an external time control (not supplied) is to be fitted, connect the live supply to terminal 3,

the neutral to terminal 4, and the time-switch output to terminal 5. If no time control is fitted, link terminal 3
and 5.

6.5

GAS (see BS 5864 and BS 6891)

6.5.1

An independent gas supply pipe from the gas meter is to be preferred wherever possible. However, when this is
not possible, the pipe must be capable of taking the complete input of the heater and all other gas appliances being
served by this same pipe. This supply should be suitably sized to conform to British Standards requirements of no
more than 1.0 mbar (0.4 in. wg.) pressure drop (see table of discharge in BS 6891).

6.5.2

The 

1

/

2

 in union gas cock (supplied) must be fitted externally in the gas inlet of the heater for easy isolation during

servicing. The gas pipe should be fitted and installed as to be durable, substantial and gas tight. Gas entry to the air
heater may be through the left hand side, right hand side front, or rear, to an Rc

1

/

2

 (

1

/

2

in B.S.P. internal (taper)

thread).

7.

COMMISSIONING

7.1

Ensure the following:

7.1.1

Gas and Electrical supplies are 

OFF.

7.1.2

Filter, fan and fan compartments are free from obstructions.

7.1.3

All registers or grilles are open and conform to design specifications.

7.1.4

Return, relief and ventilation air installations are adequate.

7.1.5

Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots.

7.2

Turn ON the gas supply to the heater.

7.3

Test for gas soundness at supply, Multifunctional control and the Main burner using proprietary detection fluid, sealing
any leaks found, and purge the whole gas pipe as described in BS 6891.

7.4

Set the Thermostat to its maximum setting.

7.5

Ensure that the time control (if fitted) is in an 

ON 

position.

7.6

Switch on the electrical supply to the heater. The combustion air fan will start up immediately; after a minimum of 30
seconds, the burner will automatically ignite and the green ‘

BURNER ON

’ indicator will illuminate.

12

ZZ 1019/1E

BURNER NOT OPERATING

Check that the time control is on and Thermostat is calling for heat.
Check mains electrical supply.
Link terminals 3 & 5 (shorts out clock).
Disconnect Thermostat at terminals 6 & 7.

No response

Burner lights

Link terminals 15 & 16.

Reinstate connections at 6 & 7.
Check wiring to, or replace
Thermostat.

No response

Burner lights

Check terminal 14 for 230 volts.

Replace fan delay/limit
control.

No 230 volts

230 volts detected

Check ICU terminal 5 for 230 volts.

Check wiring to, or replace
multifunctional control.

No 230 volts

230 volts detected

Check ICU terminal 8 for 230 volts.

Check wiring.

No 230 volts

230 volts detected

Check terminal C4 for 230 volts.

Replace Ignition Control
Unit.

No 230 volts

230 volts detected

Check terminal C3 for 230 volts.

Check wiring.

No 230 volts

230 volts detected

Check terminal 5 for 230 volts

Replace Control Module.

No 230 volts

230 volts detected

Check 3.15 A fuse, if OK check 230 volt

Check wiring and Air Heating

input at terminal 1

Switch.

Air Heating Switch and
Wiring OK

Replace Ignition Control unit
or Pressure switch

BURNER ON, BUT AIR CIRCULATION FAN NOT RUNNING

Check for 230 volts at fan terminals 11 & 12

No 230 volts detected

 230 volts detected

Switch to ‘Summer Airflow’.

Switch to ‘Summer Airflow’.

230 volts detected

Replace air circulation fan.

Air circulation fan runs

Air circulation fan does

Replace fan delay/limit control.

not run

Replace Fan Speed Transformer

BURNER ON CONTINUOUSLY

(ROOM TEMPERATURE TOO HIGH)

Set the Air Heating Switch to ‘Summer Airflow’

Burner remains alight

Burner goes out

Disconnect solenoid plug at

Replace Thermostat.

multifunctional control.

Burner remains alight

Replace multifunctional control.

AIR CIRCULATION FAN CONTINUES TO RUN OR CYCLES

WHEN BURNER IS NOT ON

Check that Air Heating switch is not set to ‘Summer Airflow’.

Disconnect Thermostat and link terminals 6 & 7.
Disconnect the fan delay/limit control.

Air circulation fan stops

Air circulation fan continues to run

Replace fan delay/limit

Replace Control module

control

AIR CIRCULATION FAN ON, BUT BURNER CYCLES BEFORE

REQUIRED COMFORT LEVEL IS REACHED

Disconnect Thermostat at terminals 6 & 7.

Burner continues to cycle

Burner remains on

Check air filter, return air path

Thermostat defective.

and outlets for restrictions.

Burner continues to cycle

Link terminals 15 & 16 to bypass limit control.

Burner continues to cycle

Burner runs and room

Replace Thermostat.

temperature rises

Check temperature rise.

Less than 60 degrees C

More than 60 degrees C

Replace fan delay/overheat (limit)

Replace Thermostat

control.

PRESSURE SWITCH DEFECTIVE

Содержание JANSTAR Mk 2

Страница 1: ...Key Description Key Description 1 Air circulating fan 7 Air filter L H shown 2 Burner assembly 8 Flue outlet combustion air inlet 3 Ignition detection electrode 9 Fan to flue connection 4 Gas connecti...

Страница 2: ...ely separated by either a non combustible partition or a perforated metal partition with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the...

Страница 3: ...es For applications where the flue exits directly through a wall the telescopic flue supplied with the heater may be used as shown in Fig 2 6 2 3 The horizontal flue shall be installed with horizontal...

Страница 4: ...e application Fig 4 Flue jointing Fig 6 Electrical panel ZZ 1019 1E 13 Ignition Control Unit Control Module Fuse Fan speed selector Air Heating Summer Airflow switch Burner ON indicator Fig 7 JANSTAR...

Страница 5: ...SSIONING 7 1 Ensure the following 7 1 1 Gas and Electrical supplies are OFF 7 1 2 Filter fan and fan compartments are free from obstructions 7 1 3 All registers or grilles are open and conform to desi...

Страница 6: ...essary Note It is possible to obtain a spark even when the electrode lead is damaged but the lead may not be able to conduct the very small detection current to the ignition detection control If there...

Страница 7: ...inal marked C3 d BROWN lead from the terminal marked C4 e YELLOW lead from the terminal marked C5 f YELLOW lead from the terminal marked C6 g RED lead from the terminal marked C7 h BLACK lead from the...

Страница 8: ...swing down and support the electrical panel ensuring that no strain is place upon or any damage is caused to any electrical wiring or connections 9 5 5 Remove the air circulation fan securing screw a...

Страница 9: ...swing down and support the electrical panel ensuring that no strain is place upon or any damage is caused to any electrical wiring or connections 9 5 5 Remove the air circulation fan securing screw a...

Страница 10: ...inal marked C3 d BROWN lead from the terminal marked C4 e YELLOW lead from the terminal marked C5 f YELLOW lead from the terminal marked C6 g RED lead from the terminal marked C7 h BLACK lead from the...

Страница 11: ...essary Note It is possible to obtain a spark even when the electrode lead is damaged but the lead may not be able to conduct the very small detection current to the ignition detection control If there...

Страница 12: ...SSIONING 7 1 Ensure the following 7 1 1 Gas and Electrical supplies are OFF 7 1 2 Filter fan and fan compartments are free from obstructions 7 1 3 All registers or grilles are open and conform to desi...

Страница 13: ...e application Fig 4 Flue jointing Fig 6 Electrical panel ZZ 1019 1E 13 Ignition Control Unit Control Module Fuse Fan speed selector Air Heating Summer Airflow switch Burner ON indicator Fig 7 JANSTAR...

Страница 14: ...es For applications where the flue exits directly through a wall the telescopic flue supplied with the heater may be used as shown in Fig 2 6 2 3 The horizontal flue shall be installed with horizontal...

Страница 15: ...ely separated by either a non combustible partition or a perforated metal partition with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the...

Страница 16: ...Key Description Key Description 1 Air circulating fan 7 Air filter L H shown 2 Burner assembly 8 Flue outlet combustion air inlet 3 Ignition detection electrode 9 Fan to flue connection 4 Gas connecti...

Отзывы: