JANSTAR Mk 2

WARM AIR HEATER

INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

G.C. No 42 *** **

Publication No. ZZ 1019/1E

September 1999

Fig. 1

JANSTAR Mk2 Principal Components

1.1

The Johnson & Starley JANSTAR Mk 2 is a wall mounted, room sealed, fan assisted, down flow warm air heater. It is
designed for use with a concentric air inlet/flue, which enables combustion air to be admitted to the burner, whilst
combustion  products are discharged to the outside, via a concentric terminal.

1.2

The air heater output is 8.0 kW (27,300Btu/h) for horizontal flued installations, and 8.5 kW (96000Btu/h) for vertical
flued installations.

1.3

The appliance is supplied assembled for left hand return air entry. For conversion to right hand return entry, refer to
Section 4. If return air is via the top of the fan chamber, a side blanking plate (Pt No ****-*******) is required. The
appliance may be base duct mounted. JANSTAR Mk 2 is also provided with the facility for connection to a remote time
control (not supplied), with volt-free contacts (i.e. The switching supply is provided by JANSTAR Mk 2), to enable
selection of operating times.

1.4

A mesh filter, for air return duct mounting, is supplied as standard. However, a Cleanflow electronic filter is offered as an
alternative option.

THIS APPLIANCE CONFORMS TO BS EN 55014

Key

Description

Key

Description

  1

Air circulating fan

  7

Air filter (L H shown)

  2

Burner assembly

  8

Flue  outlet/combustion  air  inlet

  3

Ignition/detection  electrode

  9

Fan to flue connection

  4

Gas connection

 10

Flue gas test point

  5

Multifunctional  control

 11

Combustion air fan

  6

Fan delay/ Overheat limit control

 12

Pressure switch

1

This appliance has been tested and certified for use with natural gas.

1.

GENERAL DESCRIPTION

2

3

5

7

1

8

4

9

10

11

6

12

ZZ 1019/1E

11.

SHORT LIST OF SPARES

G.C.

MAKER’S

DESCRIPTION

QTY

No

No

E00 124

W800-0701000

Burner assembly

1

E00 125

W800-0774000

Burner metal fibre assembly

1

245 549

1000-1500840

Gasket - burner top plate

1

*** ***

1000-0705480

Injector Bray Cat 15.3400

1

245 530

W800-0300000

Heat exchanger assembly

1

*** ***

1000-0708060

Multifunctional control valve

1

245 534

1000-0704490

Ignition/detection electrode

1

*** ***

1000-0520105

Fan delay/limit control

1

*** ***

1000-0519440

Electronics module

1

*** ***

****-*******

Transformer

1

245 525

1000-0515730

Transformer (Cleanflow filter)

1

*** ***

****-*******

Ignition module

1

*** ***

****-*******

Combustion air fan assembly

1

*** ***

1000-0500130

Air circulation fan

1

245 509

1000-0513820

Fuse T3.15A

1

*** ***

****-*******

Thermostat

1

*** ***

1000-0520110

Ignition Control Module

1

*** ***

1000-0519430

Air Proving Switch

1

16

Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.

JOHNSON & STARLEY LTD.

Telephone:

(01604) 762881

Rhosili Road,

B r a c k m i l l s ,

 Telefax:

(01604)  767408

    Northampton NN4 7LZ

Содержание JANSTAR Mk 2

Страница 1: ...Key Description Key Description 1 Air circulating fan 7 Air filter L H shown 2 Burner assembly 8 Flue outlet combustion air inlet 3 Ignition detection electrode 9 Fan to flue connection 4 Gas connecti...

Страница 2: ...ely separated by either a non combustible partition or a perforated metal partition with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the...

Страница 3: ...es For applications where the flue exits directly through a wall the telescopic flue supplied with the heater may be used as shown in Fig 2 6 2 3 The horizontal flue shall be installed with horizontal...

Страница 4: ...e application Fig 4 Flue jointing Fig 6 Electrical panel ZZ 1019 1E 13 Ignition Control Unit Control Module Fuse Fan speed selector Air Heating Summer Airflow switch Burner ON indicator Fig 7 JANSTAR...

Страница 5: ...SSIONING 7 1 Ensure the following 7 1 1 Gas and Electrical supplies are OFF 7 1 2 Filter fan and fan compartments are free from obstructions 7 1 3 All registers or grilles are open and conform to desi...

Страница 6: ...essary Note It is possible to obtain a spark even when the electrode lead is damaged but the lead may not be able to conduct the very small detection current to the ignition detection control If there...

Страница 7: ...inal marked C3 d BROWN lead from the terminal marked C4 e YELLOW lead from the terminal marked C5 f YELLOW lead from the terminal marked C6 g RED lead from the terminal marked C7 h BLACK lead from the...

Страница 8: ...swing down and support the electrical panel ensuring that no strain is place upon or any damage is caused to any electrical wiring or connections 9 5 5 Remove the air circulation fan securing screw a...

Страница 9: ...swing down and support the electrical panel ensuring that no strain is place upon or any damage is caused to any electrical wiring or connections 9 5 5 Remove the air circulation fan securing screw a...

Страница 10: ...inal marked C3 d BROWN lead from the terminal marked C4 e YELLOW lead from the terminal marked C5 f YELLOW lead from the terminal marked C6 g RED lead from the terminal marked C7 h BLACK lead from the...

Страница 11: ...essary Note It is possible to obtain a spark even when the electrode lead is damaged but the lead may not be able to conduct the very small detection current to the ignition detection control If there...

Страница 12: ...SSIONING 7 1 Ensure the following 7 1 1 Gas and Electrical supplies are OFF 7 1 2 Filter fan and fan compartments are free from obstructions 7 1 3 All registers or grilles are open and conform to desi...

Страница 13: ...e application Fig 4 Flue jointing Fig 6 Electrical panel ZZ 1019 1E 13 Ignition Control Unit Control Module Fuse Fan speed selector Air Heating Summer Airflow switch Burner ON indicator Fig 7 JANSTAR...

Страница 14: ...es For applications where the flue exits directly through a wall the telescopic flue supplied with the heater may be used as shown in Fig 2 6 2 3 The horizontal flue shall be installed with horizontal...

Страница 15: ...ely separated by either a non combustible partition or a perforated metal partition with the perforations not exceeding 13mm 0 5in 2 3 In under stair installations the compartment must comply with the...

Страница 16: ...Key Description Key Description 1 Air circulating fan 7 Air filter L H shown 2 Burner assembly 8 Flue outlet combustion air inlet 3 Ignition detection electrode 9 Fan to flue connection 4 Gas connecti...

Отзывы: