Sales/Spares & Replacement Help Line 01604 762881

9.6 

WATER & ELECTRICAL CONNECTIONS    
9.6.1  WATER CONNECTIONS

 

 

 

The water connections to the unit should be compression type fittings that are suitable for 
the duty of the appliance. Isolation valves must 

be fitted to facilitate the removal 

of the heat exchanger assembly.

9.6.2   UPFLOW AUTOMATIC AIR VENT 

 

For upflow units an ALTECNIC 502 ROBOCAL Air vent (Part No. 1000-0302300) MUST 
be fitted to the top of the unit. This come as part of the AQUP Kit. 

 

Any queries contact Johnson & Starley Ltd for details, Telephone 01604 762881.

9.6.3  To fit the vent, swivel the disc cap by breaking the paint seal, tap the disc and swivel. 

Remove the cap in the end of the flow pipe and screw in the air vent. 

NOTE:

  Care must be taken with the heat exchanger matrix, as it is fragile and is easily damaged.

9.6.4  ELECTRICAL HARNESS

 

Re-route the harness cable through the side knockout. Use the grommet attached to 
seal the hole. 

9.7 

ANCILLARIES AVAILABLE

NOTE:

 

When using a side return air kit (with either the downflow or upflow configuration) you need a 
blanking plate to cover the existing opening.

10.  RETURN AIR SYSTEM

10.1 

The return air system should be constructed of fire-resistant material. It is important that the cor-
rect size of return air grilles and ducting is used. Refer to the table below for return air duct size, 
flexible duct size and the return air grille size at maximum output. 

10.2 

An adequate and unobstructed return air path is required from areas not served by a directly 

ducted return and to which warm air is delivered. All such rooms should be fitted with relief grilles 

which have a free area of 0.0088 m²/kW (1 in²/250Btu/h) of heat supplied to the room. The only 

exceptions are kitchens, bathrooms and WCs.

11. ELECTRICAL

11.1 

The appliance is supplied with PVC sheathed, 3 core 0.75 mm

2

 CSA rated at 6 A, connected to 

a terminal block and exiting through the casing at the top left hand front. The cable is suitable for 
a 230 V, 50 Hz single phase supply.

11.2 

The means of isolating the appliance MUST be via a double pole switch with a contact separation 
of at least 3 mm in both poles, and fused at 3 A. If switched live is fitted, a triple pole switch should 
be used.

11.3 

SUMMER AIR CIRCULATION

 

To run the fan at full commissioned speed in warm weather and in order to circulate the air, a 
single pole, volt free switch (not supplied) must be connected across terminals 3-4 (see circuit 
diagram Figure 4).

  

AQUAIR

DUCT EQUIVALENT SIZE

FLEXIBLE DUCT SIZE

RETURN AIR GRILLE

S-10

250 x 200mm (10” x 8”)

300mm (12”) dia

860cm² (137in²)

S-16

300 x 250mm (12” x 10”)

350mm (14”) dia

1266cm² (196in²)

S-20

400 x 300mm (16” x 12”)

406mm (16”) dia

2118cm² (328in²)

MODEL

UPFLOW KIT

CLEANFLOW

PASSIVE SIDE 

RETURN AIR KIT

SIDE AIR

RETURN KIT

TOP SLOT FIT KIT

S-10

AQUP-10

CFA-10

SRAQ-10P

SRAQ-10

TSQ-10

S-16

AQUP-16

CFA-16

SRAQ-16P

SRAQ-16

-

S-20

AQUP-20

CFA-20

SRAQ-20P

SRAQ-20

-

Содержание AQUAIR S Series

Страница 1: ...co uk Aquair S 10 Aquair S 16 Aquair S 20 INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication N...

Страница 2: ...paration 5 9 Installation Instructions 6 Downflow Configuration Upflow Configuration Water Connections Upflow Automatic Air Vent Electrical Harness Ancillaries Available 10 Return Air System 7 11 Elec...

Страница 3: ...5 5 4 4 3 6 10 AQUAIR S 10 FEATURES 1 Mains Supply 2 Air Filter 3 Air Circulation Fan with EC technology 4 PCB Control Board 5 Hot Water Return to Heat Source 6 Hot Water Flow from Heat Source 7 Flow...

Страница 4: ...ackaging and during installation procedure Manoeuvring the boiler may include the use of a sack truck and involve lifting pushing and pulling 5 1 2 It should be noted that this appliance may contain s...

Страница 5: ...ent clearance must be provided for the assembly of ducting and pipework ITEM S 10 S 16 S 20 Nominal Rated Output kW 10 15 20 Air on Temperature C 20 20 20 Air off Temperature C 67 67 67 Water Supply T...

Страница 6: ...o be fitted the top of the unit must be suitably guarded to prevent any blockage 9 4 5 Once the installation is complete stick the Aquair decal in position on the front cover top left hand side 9 5 UP...

Страница 7: ...r duct size flexible duct size and the return air grille size at maximum output 10 2 An adequate and unobstructed return air path is required from areas not served by a directly ducted return and to w...

Страница 8: ...www johnsonandstarley co uk 8 12 CIRCUIT DIAGRAM FIGURE 4 AQUAIR S CIRCUIT DIAGRAM COLOUR CODE bn BROWN bl BLUE bk BLACK g y GREEN YELLOW r RED w WHITE or ORANGE y YELLOW...

Страница 9: ...sta stat connected the fan will run when a water temperature of 33 C is reached and it stops when the water temperature falls to 20 C The fan speed is controlled by the Thermista stat demand 14 2 3 Wi...

Страница 10: ...k temperature rise across unit is 40 C 15 6 3 Set water differential to 20 C using lock shield valve or equivalent 15 6 4 Check fan stops when water cools to required temperature 16 SERVICING MAINTENA...

Страница 11: ...put Check for live supply into clock Replace clock if live is present Is 230 250VAC present Check harness connections to PCB If all OK Replace PCB Remove MAF stat connections and link Low Voltage term...

Страница 12: ...ross high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is the MAF stat connected Is fan now running Link ou...

Страница 13: ...ENSIONS FIGURE 6 AQUAIR S 16 DIMENSIONS FIGURE 5 AQUAIR S 10 DIMENSIONS 485 787 48 362 402 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768...

Страница 14: ...Q16 0182005 S 20 1 AQ20 0182005 2 Air Circulation Fan S 10 1 AQ10 0126005 S 16 1 AQ16 0126005 S 20 1 AQ20 0126005 3 PCB Board 1 1000 0526275 4 Temperature Flow Sensor 1 1000 0526505 5 Front Cover 1 AQ...

Страница 15: ...20 EXPLODED DIAGRAM FIGURE 8 AQUAIR S EXPLODED DIAGRAM GUARD FAN SLIDER SIDE KNOCK OUTS FLYING LEAD HOT WATER FLOW FROM HEAT SOURCE HOT WATER RETURN TO HEAT SOURCE AIR FILTER AIR CIRCULATION FAN PCB T...

Страница 16: ...ales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2012 In the interest of continuous development Johnson Starley...

Отзывы: