INSTALLATION INSTRUCTIONS

9.1 

The Aquair S unit is supplied as a downflow configured appliance 

as standard. It has been designed with the provision to be 

converted to an upflow unit. 

9.2  

The Aquair S-16 & S-20 appliances exceed the recommended 

weight for a one-man lift as detailed in the Manual Handling 

Operations,1992 Regulations.

9.3 

Once the unit has been unpacked, unscrew the transit plate from 

the base of the unit and discard. 

NOTE:

 This unit could contain sharp edges and care MUST be taken 

when handling.

9.4 

DOWNFLOW CONFIGURATION 

See Figure 2

9.4.1    Remove the filter to expose the two screws holding the 

door in place. Remove the screws and gently pull and lift 

the door off the unit.

9.4.2    Lift the appliance onto the plenum or base support and 

position correctly. Seal the join with the appropriate 

sealing material.

9.4.3   The water connections to the unit should be by 

compression. Fittings that are suitable for the duty and 

isolation valves must be fitted to facilitate the removal of 

the heat exchanger assembly.

9.4.4   If a return air duct is not to be fitted, the top of the unit 

must be suitably guarded to prevent any blockage.

9.4.5    Once the installation is complete, stick the Aquair decal in 

position on the front cover, top left hand side.

9.5 

UPFLOW CONFIGURATION

 

See Figure 3 

9.5.1   To fit the upflow configuration you need the additional 

Aquair Upflow Kit (AQUP).

9.5.2    Remove the filter to expose the two screws holding the 

door in place. Remove the screws and gently pull and lift 

the door off the unit.

9.5.3   Remove the 10 screws holding return air frame and 

remove.

9.5.4 

Invert the unit so the air filter is at the bottom of the unit.

9.5.5 

In the AQUP Kit use the new spigot frame and screw to 

the top of the unit to form the duct connection spigot. 

9.5.6    Lift the appliance onto the plenum or base support and 

position correctly. Seal the joint with the appropriate 

sealing material.

9.5.7   If a return air duct is not to be fitted, the top of the unit 

must be suitably guarded to prevent any blockage.

9.5.8    Once the installation is complete, stick the Aquair decal in 

position on the front cover top left hand side.

FIGURE 2. DOWNFLOW CONFIGURATION

FIGURE 3. UPFLOW CONFIGURATION

SCREWS

AIR FILTER

AIR FILTER

PLENUM

PLENUM

HARNESS 

KNOCKOUT

SCREWS

RETURN AIR

RETURN

AIR

FIGURE 4. FITTING AUTOMATIC AIR 

VENT

AIR VENT

SWIVEL

CAP

INSIDE UNIT

Содержание AQUAIR S Series

Страница 1: ...co uk Aquair S 10 Aquair S 16 Aquair S 20 INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication N...

Страница 2: ...paration 5 9 Installation Instructions 6 Downflow Configuration Upflow Configuration Water Connections Upflow Automatic Air Vent Electrical Harness Ancillaries Available 10 Return Air System 7 11 Elec...

Страница 3: ...5 5 4 4 3 6 10 AQUAIR S 10 FEATURES 1 Mains Supply 2 Air Filter 3 Air Circulation Fan with EC technology 4 PCB Control Board 5 Hot Water Return to Heat Source 6 Hot Water Flow from Heat Source 7 Flow...

Страница 4: ...ackaging and during installation procedure Manoeuvring the boiler may include the use of a sack truck and involve lifting pushing and pulling 5 1 2 It should be noted that this appliance may contain s...

Страница 5: ...ent clearance must be provided for the assembly of ducting and pipework ITEM S 10 S 16 S 20 Nominal Rated Output kW 10 15 20 Air on Temperature C 20 20 20 Air off Temperature C 67 67 67 Water Supply T...

Страница 6: ...o be fitted the top of the unit must be suitably guarded to prevent any blockage 9 4 5 Once the installation is complete stick the Aquair decal in position on the front cover top left hand side 9 5 UP...

Страница 7: ...r duct size flexible duct size and the return air grille size at maximum output 10 2 An adequate and unobstructed return air path is required from areas not served by a directly ducted return and to w...

Страница 8: ...www johnsonandstarley co uk 8 12 CIRCUIT DIAGRAM FIGURE 4 AQUAIR S CIRCUIT DIAGRAM COLOUR CODE bn BROWN bl BLUE bk BLACK g y GREEN YELLOW r RED w WHITE or ORANGE y YELLOW...

Страница 9: ...sta stat connected the fan will run when a water temperature of 33 C is reached and it stops when the water temperature falls to 20 C The fan speed is controlled by the Thermista stat demand 14 2 3 Wi...

Страница 10: ...k temperature rise across unit is 40 C 15 6 3 Set water differential to 20 C using lock shield valve or equivalent 15 6 4 Check fan stops when water cools to required temperature 16 SERVICING MAINTENA...

Страница 11: ...put Check for live supply into clock Replace clock if live is present Is 230 250VAC present Check harness connections to PCB If all OK Replace PCB Remove MAF stat connections and link Low Voltage term...

Страница 12: ...ross high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is the MAF stat connected Is fan now running Link ou...

Страница 13: ...ENSIONS FIGURE 6 AQUAIR S 16 DIMENSIONS FIGURE 5 AQUAIR S 10 DIMENSIONS 485 787 48 362 402 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768...

Страница 14: ...Q16 0182005 S 20 1 AQ20 0182005 2 Air Circulation Fan S 10 1 AQ10 0126005 S 16 1 AQ16 0126005 S 20 1 AQ20 0126005 3 PCB Board 1 1000 0526275 4 Temperature Flow Sensor 1 1000 0526505 5 Front Cover 1 AQ...

Страница 15: ...20 EXPLODED DIAGRAM FIGURE 8 AQUAIR S EXPLODED DIAGRAM GUARD FAN SLIDER SIDE KNOCK OUTS FLYING LEAD HOT WATER FLOW FROM HEAT SOURCE HOT WATER RETURN TO HEAT SOURCE AIR FILTER AIR CIRCULATION FAN PCB T...

Страница 16: ...ales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2012 In the interest of continuous development Johnson Starley...

Отзывы: