FIGURE 4.  AQUAIR S PCB REMOVAL

FIGURE 5.  AIR CIRCULATION FAN RE-

MOVAL

www.johnsonandstarley.co.uk

10

15. COMMISSIONING

15.1 

Ensure the heater is correctly fitted with water and all air vented from the flow and return circuits.

15.2 

Switch on electrical supply.

15.3  Setting maximum speed.

15.3.1  Make a short across Thermista-stat connections, if fitted, and adjust the fan speed as 

required, then remove the short.

15.4  Setting minimum fan speed.

15.4.1  Make a short across the pipe sensor and adjust the fan speed as required, then remove 

short.

15.5  WITH THERMISTA-STAT FITTED

15.5.1  Turn up Thermista-stat to call for heat.
15.5.2   Check for 230V on switch live out.
15.5.3  With the water at the required temperature, ensure fan starts.
15.5.4   Allow the system to warm up and check temperature rise across unit is 40 °C.
15.5.5   Set water differential to 20 °C using lock shield valve or equivalent.
15.5.6  Turn off Thermista-stat and check there is NO 230V on switch live out.
15.5.7  Check fan stops when water cools to required temperature.

15.6  WITH NO THERMISTA-STAT FITTED

15.6.1  With the water at the required temperature ensure fan starts.
15.6.2   Allow the system to warm up and check temperature rise across unit is 40 °C.
15.6.3   Set water differential to 20 °C using lock shield valve or equivalent.
15.6.4  Check fan stops when water cools to required temperature.

16.  SERVICING & MAINTENANCE

16.1 

ROUTINE MAINTENANCE

 

IMPORTANT: Before carrying out any work on the unit, ALWAYS ENSURE THE 
MAINS ELECTRICAL SUPPLY IS ISOLATED FROM THE UNIT.

 

Remove the filter and unscrew the two retaining screws holding the front cover on the unit, gen-
tly pull it forward. Servicing and maintenance should be carried out at least once per year. 
16.1.1   Check that the heat exchanger airways is free from 

obstructions. If necessary, clean with a vacuum cleaner 
from the air inspection panel, taking care to not damage 
the airways.

16.1.2   Check the condition of the external strainer, cleaning as 

necessary.

16.1.3   Check that the air filter is being regularly cleaned in ac-

cordance with the User Instructions.

16.2  PCB REMOVAL & REPLACEMENT

16.2.1    Disconnect the wiring at the PCB terminal block.
16.2.2   Release the 4 clips securing the PCB and withdraw the 

panel, disconnecting the fan supply lead at the fan tray 
terminal block.

13.2.3    Reassemble or replace in reverse order.

16.4  FAN REMOVAL

16.4.1    Disconnect the electrical connections.
16.4.2    Remove the screws securing the fan and withdraw on the 

location runners.

16.4.3    Reassemble or replace in reverse order.

LOCATION 

RUNNERS

SCREW

CLIPS

Содержание AQUAIR S Series

Страница 1: ...co uk Aquair S 10 Aquair S 16 Aquair S 20 INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication N...

Страница 2: ...paration 5 9 Installation Instructions 6 Downflow Configuration Upflow Configuration Water Connections Upflow Automatic Air Vent Electrical Harness Ancillaries Available 10 Return Air System 7 11 Elec...

Страница 3: ...5 5 4 4 3 6 10 AQUAIR S 10 FEATURES 1 Mains Supply 2 Air Filter 3 Air Circulation Fan with EC technology 4 PCB Control Board 5 Hot Water Return to Heat Source 6 Hot Water Flow from Heat Source 7 Flow...

Страница 4: ...ackaging and during installation procedure Manoeuvring the boiler may include the use of a sack truck and involve lifting pushing and pulling 5 1 2 It should be noted that this appliance may contain s...

Страница 5: ...ent clearance must be provided for the assembly of ducting and pipework ITEM S 10 S 16 S 20 Nominal Rated Output kW 10 15 20 Air on Temperature C 20 20 20 Air off Temperature C 67 67 67 Water Supply T...

Страница 6: ...o be fitted the top of the unit must be suitably guarded to prevent any blockage 9 4 5 Once the installation is complete stick the Aquair decal in position on the front cover top left hand side 9 5 UP...

Страница 7: ...r duct size flexible duct size and the return air grille size at maximum output 10 2 An adequate and unobstructed return air path is required from areas not served by a directly ducted return and to w...

Страница 8: ...www johnsonandstarley co uk 8 12 CIRCUIT DIAGRAM FIGURE 4 AQUAIR S CIRCUIT DIAGRAM COLOUR CODE bn BROWN bl BLUE bk BLACK g y GREEN YELLOW r RED w WHITE or ORANGE y YELLOW...

Страница 9: ...sta stat connected the fan will run when a water temperature of 33 C is reached and it stops when the water temperature falls to 20 C The fan speed is controlled by the Thermista stat demand 14 2 3 Wi...

Страница 10: ...k temperature rise across unit is 40 C 15 6 3 Set water differential to 20 C using lock shield valve or equivalent 15 6 4 Check fan stops when water cools to required temperature 16 SERVICING MAINTENA...

Страница 11: ...put Check for live supply into clock Replace clock if live is present Is 230 250VAC present Check harness connections to PCB If all OK Replace PCB Remove MAF stat connections and link Low Voltage term...

Страница 12: ...ross high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is the MAF stat connected Is fan now running Link ou...

Страница 13: ...ENSIONS FIGURE 6 AQUAIR S 16 DIMENSIONS FIGURE 5 AQUAIR S 10 DIMENSIONS 485 787 48 362 402 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768...

Страница 14: ...Q16 0182005 S 20 1 AQ20 0182005 2 Air Circulation Fan S 10 1 AQ10 0126005 S 16 1 AQ16 0126005 S 20 1 AQ20 0126005 3 PCB Board 1 1000 0526275 4 Temperature Flow Sensor 1 1000 0526505 5 Front Cover 1 AQ...

Страница 15: ...20 EXPLODED DIAGRAM FIGURE 8 AQUAIR S EXPLODED DIAGRAM GUARD FAN SLIDER SIDE KNOCK OUTS FLYING LEAD HOT WATER FLOW FROM HEAT SOURCE HOT WATER RETURN TO HEAT SOURCE AIR FILTER AIR CIRCULATION FAN PCB T...

Страница 16: ...ales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2012 In the interest of continuous development Johnson Starley...

Отзывы: