When  used  in  locations  vulnerable  to  rodent  attack,  all
plastic pipes and fittings should be adequately protected
within sealed ducts.

Speedfit  products  along  with  other  materials  such  as
electrical cables may be damaged if rodents are present.
If vermin infestation is suspected then a rodent exterminator
should take appropriate action

.

No taste, colour, odour or toxicity is imparted to water by
Speedfit components, nor do they promote
microbiological growth.

In accordance with BS7291: Part 1 Clause 6.7, the opacity
of both pipes and fittings allows insufficient light to pass
for the growth of algae

Tests  within  the  Water  Regulations  Advisory  Scheme, 
have  approved  Speedfit  pipe  and  fittings  to  BS  6920  for 
water quality. 

On  completion  of  the  plumbing  and  heating  system  it  is
essential  that  system  checking  and  a  hydraulic  wet  test
takes  place.  Connections  to  boilers,  radiators  and
sanitary ware should first be capped or plugged.

Testing  should  be  carried  out  at 
2 bar for 10 minutes followed by 10
bar for 10 minutes.

This  testing  combined  with  other
relevant  checks,  should  reveal  most
system  problems.  Any  components
within  the  system  not  designed 
to  take  these  pressures  should 
be disconnected. 

Before carrying out a pressure test
ensure all Speedfit pipe and fittings
are  installed  correctly.  Speedfit
Barrier Pipe is printed with insertion
marks  to  help  ensure  full  insertion
has been achieved.

Remember  pressure  testing  is  NOT  a  substitute  for
making sure fittings are clean and free of any grit, dirt or
swarf  and  the  pipe  is  correctly  inserted  (see  Making  a
Good Connection, on page 06.

With existing systems, flushing prior to the use of Speedfit is
essential to remove any harmful contamination or chemical
residues from elsewhere in the system.

For  the  installation  of  central  heating  systems  flushing
procedures must be in line with BS7593 code of practice
for treatment of water in domestic hot water heating systems.

Flux residues used in the soldering of capillary fittings are
very corrosive. Dirt and grit, which can enter the system
when Speedfit pipe is being pushed through underfloor or
across a roof space, must be removed.

The JG Speedfit Technical Advisory Service is available to
assist  and  advise  on  all  aspects  of  using  the  Speedfit
system. The service is available between 8.00am and 4.30pm,
Monday  to  Friday  on  Telephone  No.  01895  425333  and
Fax No. 01895 425350. Products within this Product Guide
are  designed  for  use  within  UK  plumbing  and  heating
installations or in other countries where similar installation
requirements apply. For information on products suitable
for  use  in  other  countries  please  consult  our  Technical
Advisory Service.

We take pride in the quality of our products and all complaints
are investigated thoroughly. If you have a problem with a
Speedfit Product please return both fitting and pipe to us
for  investigation.  We  will  need  at  least  50mm  of  pipe  to
ensure an accurate analysis. If there is a suspicion that the
pipe is faulty, please provide marking details from the pipe.

PROTECTION AGAINST RODENTS

BIOLOGICAL

SYSTEM TESTING

SYSTEM COMMISSIONING AND FLUSHING

TECHNICAL ADVISORY SERVICE

Ceiling 

24°C

Floor 
18°C

2.70

1.70

Ideal 

Heating
System

Floor 

Heating
System

Radiator

Heating
System

UNDERFLOOR HEATING

The Speedfit Underfloor Heating System has been designed
to be as quick and easy as possible to install with component
parts manufactured to UK and European standards.

Underfloor heating provides the most comfortable even warmth
of any heating system. It is economical to run and virtually
maintenance  free.  The  principle  has  been  with  us  since
Roman  times  but  is  still  the  system  of  choice  in  some
European countries, accounting for 70% of installations.

The  Speedfit  System  has  water  being  pumped  from  a
boiler to a pump pack, where it is mixed to approximately
50ºC  then  distributed  via  a  manifold  to  heating  circuits
made  using  Speedfit  Barrier  Pipe.  The  pipe  is  laid  in
concrete or suspended just below the surface of the floor.

In concrete floors, the pipe is laid on insulation and then
covered with a screed on which can be laid almost any type
of floor covering.

For timber floors, spreader plates are laid between the joists
and  the  floor  decking  or  on  the  underside  of  the  floor.
Speedfit Pipe is pushed into the grooves on the plates.

The  floor  area  is  typically  warmed  to  between  25ºC  and
28ºC, providing an even distribution of heat at only slightly
higher  than  room  temperature.  The  system  is  controlled
by one or more thermostats which signal the Pump Pack
when heat is required.

21

22

RADIATOR SYSTEM AND HEAT GRADIENT

UNDERFLOOR HEATING SYSTEM

An Underfloor Heating System heats mainly by radiation.
Radiant  energy  is  emitted  by  the  floor  giving  an  even
distribution of heat. No cold spots, hot ceilings or cold feet.

The  overall  effectiveness  of  an  UFH  heating  system  can
be seen below.

The  heat  is  concentrated  where  it  is  most  needed  for
comfort and efficiency.

Problem:

Burst or melted pipe.

Pipe will be distorted showing either a ‘Parrot beak’ look 
or a long opening with the edges of the pipe melted in a 
wave shape.

Identification:

A ‘Parrot beak’ will have been formed by

the pipe bursting due to the water freezing. If the Pipe has
a  melted  appearance  it  will  have  been  subject  to  a
temperature  in  excess  of  128  degrees  Celsius.  This  will
have  been  caused  by  direct  contact  with  a  heat  source
such  as  a  blowtorch  or  flue  pipe  or  by  water  or  steam
within the system rising above safety levels.

Problem:

A fitting or part of a fitting dissolved - the fitting

may  have  blown  off  the  pipe  and  may  have  missing
component parts.

Identification:

The  fitting  will  have  failed  because  of  a

chemical  attack.  The  most  common  attack  is  from  acid
based  solder  flux  running  down  into  the  fitting  during
soldering  of  a  nearby  copper  fitting  or  flux  coming  into
contact with the fitting in some other way.

Problem:

Weep from fitting.

Identification :

The pipe has not been fully inserted up to

the  pipe  stop  or  one  or  both  of  the  ‘O’  rings  have  been
damaged by burrs or sharp edges on the end of pipe. See
‘What Not to Do’ on page 06.

Problem:

The  fitting  has  blown  off  the  pipe.  Fitting  is

missing the collet, the pipe insert is still inside the fitting
after the pipe has come out.

Identification: 

If this happens on first fix, the most likely 

reason is that the pipe has not been fully inserted into the
fitting, up to the pipe stop, and the system has not been
pressure tested.

If  the  collet  (gripping  device)  is  missing  everything  will
blow out. If the collet is there and the pipe support is still
inside the connector but the pipe has still blown out, this
means that full insertion had not been accomplished.

COMMON PROBLEMS AND IDENTIFICATION

During  the  commissioning  of  a  heating  system,  all  air
must  be  removed  from  the  system  before  the  boiler  is
allowed  to  fire.  This  will  ensure  pockets  of  air  do  not
cause  localized  overheating  within  the  system  as  this
could  have  a  detrimental  affect  on  the  pipework  and
boiler.

For  further  advice  on  chemical  flushing  agents  and
inhibitor  treatments,  the  following  manufacturers  should
be contacted: Fernox Manufacturing Ltd., 01799 550811
or Sentinel Betz Dearborn Ltd., 0151 420 9595.

Ceiling 

18°C

Floor
24°C

By contrast, radiators transfer heat from a relatively small
area at a much higher temperature than the space being heated.

The  radiator  system  heats  mainly  by  convection.  This
results  in  the  floor  being  the  coolest  place  in  the  room,
with the mass of warm air at ceiling level.

The Speedfit Underfloor Heating System offers many benefits
to the consumer. These include: 

Installation

It is simple to install, requiring the minimum of installation
effort and little maintenance. 

Comfort

The system uses radiant heat, the most comfortable form
of  heating,  to  give  a  good  even  distribution  of  warmth
over the whole room.

Space 

The  system  in  unobtrusive  and  space  saving  which  means
every  square  metre  of  floor  and  wall  space  can  be  fully
utilised giving freedom of interior design.

Noise

Compared to radiator systems the system is virtually silent running.

Health

Dust  is  minimised  reducing  the  problem  of  house  dust
mites. Reduced numbers of hot surfaces and sharp edges
minimise risk of burns or injury.

Economic

Underfloor  Heating  Systems  are  designed  to  operate  at
lower  temperatures  than  radiator  systems,  resulting  in
reduced energy consumption and lower heatloss from the
building structure.

Control

The system is easy to control and the small temperature
difference between the floor and air means the system is
virtually self - regulating.

Environment

Underfloor  heating  is  suitable  for  use  with  the  most  energy
efficient  and  environmentally  friendly  heating  systems
including condensing boilers, solar power and heat pumps.

FEATURES & BENEFITS

The  Speedfit  Underfloor  Heating  System  is  suitable  for
most floor finishes, including ceramic tiles, carpets, vinyl
and laminate. 

The thermal resistance of floor covering will have a marked
effect on the performance of the heating system.

Advice on the use of floor coverings and their effect on 
the performance of a system is laid out in the Speedfit
Underfloor Heating Manual. 

FLOOR FINISHES AND COVERING

Содержание Speedfit

Страница 1: ...rposes only Subject to our Terms and Conditions of Sale available on request Z2105 217 10 07 No s 95 3177 BS7291 KM39767 AVAILABLE FROM THE PUSH FIT SOLUTION FOR PLUMBING HEATING SYSTEMS UK PRODUCT RA...

Страница 2: ...ducts A reputation built on producing consistently high quality products with an ongoing commitment to value engineering and product development 01 02 Technical Support Our national team of Technical...

Страница 3: ...s application Speedfit fittings suitable for central heating systems can withstand temperatures up to 114 C intermittently for short periods Speedfit fittings shown as not suitable for central heating...

Страница 4: ...ead The O ring on the Superseal Pipe Insert provides a secondary seal against the bore of the fitting A good connection has been made Gap between Cap and Flange Pipe mark indicates full insertion Twis...

Страница 5: ...e connectors are useful when replacing existing brassware or in other confined spaces Coupling up to a supply is easy The pipe is simply pushed home into the Speedfit connection and is instantly secur...

Страница 6: ...28 x 22 PEMSTC1514 15mm x 1 2 BSP PEMSTC1516 15mm x 3 4 BSP PEMSTC2216 22mm x 3 4 BSP PEMBTC1514 15mm x 1 2 BSP PART NO SIZE MM PSE4610W 10 PSE4615W 15 PSE4622W 22 Suitable for central heating systems...

Страница 7: ...50mm long 1000mm long PART NO SIZE MM X MALE FLX48 12 x M10 FLX28 15 x M10 FLX29 15 x M12 FOR MONOBLOC MIXERS PART NO SIZE MM X BSP PART NO SIZE MM X BSP FLX36P 15 x 1 2 ELBOW PATTERN 300mm long 300mm...

Страница 8: ...15BPEX 120C 15mm x 120m 15BPEX 150C 15mm x 150m 22BPEX 25C 22mm x 25m 22BPEX 50C 22mm x 50m Suitable for central heating systems Coils The pipe has an inner barrier to stop the ingress of atmosphere...

Страница 9: ...Copper pipe PE copper coupler MDPE pipe with Pipe Insert Collet clip Speedfit Pipe Speedfit pipe should never be connected directly to a boiler Although most modern boilers have a high limit thermost...

Страница 10: ...M M M M M M P P Plastic M Metal NB All Waste Pipes are plastic 1 Supplementary bonding is carried out to the earth terminal of protective conductors of class I and class II equipment within the bathro...

Страница 11: ...rs does not affect the fire resistant properties of the structure Speedfit pipework can be easily cabled through studwork and within wall systems as well as behind dot and dab plasterboard installatio...

Страница 12: ...ntrolled by one or more thermostats which signal the Pump Pack when heat is required 21 22 RADIATOR SYSTEM AND HEAT GRADIENT UNDERFLOOR HEATING SYSTEM An Underfloor Heating System heats mainly by radi...

Страница 13: ...ntralised control of the set back functions for the whole manifold via a digital programmer The timer acts as a timed switch to alternate between daytime and Set Back time PART DESCRIPTION PACK NO QTY...

Страница 14: ...on of the outside walls and windows will determine the pattern of the pipe layout The counterflow pattern is recommended although other options are shown below Single Serpentine Double Serpentine Trip...

Страница 15: ...nst the face of fitting With the collet held in this position the pipe can be withdrawn We recommend the replacement of the O ring and collet before making a new connection Remove collet cover pull ou...

Страница 16: ...ulose based paints paint thinners or strippers solder flux or acid based descalents or aggressive household cleaning products Exposure to sunlight Speedfit products when used indoors are not affected...

Отзывы: