38
7.4.1.2 Set motor parameters by manual
If the first commission failed caused by motor parameters’ mismatching, and reset by
manual is required. Please refer to the following steps:
1. Stop Inverter;
2. Refer to “
8.3.5.3 Key Parameters of the System Set
” to change “MP-Sel” to
“manual”;
3. Refer to “
8.3.5.3 Key Parameters of the System Set
” to revise the parameters
of ”R-Stat”, ”R-Rotr”, ”L-Mutu”, ”L-Leak” to the specified value. (Contact Supplier for
the specified vale)
4. Return to the first screen (press “DOWN” and “ENTER” at the same time), and start
inverter.
7.4.2 Commission
7.4.2.1 Self-detect motor parameter
After finishing motor parameters’ detection, LCD screen will indicate” Test finish start up?
YES/NO”, select “YES”, and inverter will start; select “NO”, inverter will stay in motor
detection model, and re-detect when start it again.
Содержание JNP110KH-V3