background image

Rev. C 

- 7

 

-

Figure2: PV module installed on different ground covers

 

2.3 Mechanical Installation 

I

ntroduction

Solar PV modules usually can be mounted by using the following methods: bolts and clamps. 

Note:

(1)

All installation methods herein are only for reference, and Jinko Solar will not provide

 

related mounting components

.  T

he system installer or trained professional personnel

 

must

 

be responsible for the PV system’s design, installation, and mechanical load

 

calculation

 

and security of the system.

(2)

Before installation, the following items should be addressed:

1)

Visually check the module for any damage. Clean the module if any dirt or residue

 

remains from shipping.

2)

Check if module serial number stickers match.

3)

The minimum distance between modules should be more than 10mm for all installation

 

methods.

(3)

The 

mounting

 with bolts and/or clamps 

on  the 

long side of 

the 

frames 

could 

meet a 

maximum positive 

testing 

(downward) pressure of 

54

00Pa

 

and negative 

testing 

(upward)

 

pressure of 

24

00Pa. The 

mounting w

ith clamps 

on the

 short side of

 the

 

frames 

could meet  

a

 

positive 

testing 

(downward) pressure

 

and negative 

testing 

(upward) pressure of 1600Pa

.

  The mounting 

of 

clamps 

on

 the long &

 

short sides of 

frames 

could meet 

a positive 

testing 

(downward) pressure and

 

negative 

testing 

(upward) pressure of 2400Pa.

 with a 1.5 times safety factor.

 

Содержание JKM M-60 Series

Страница 1: ...JinkoSolar Photovoltaic Module User Manual UL1703 ...

Страница 2: ...allation Condition 2 2 1 Climate Condition 2 2 2 Site Selection 2 2 3 Tilt Angle Selection 2 3 Mechanical Installation Introduction 2 3 1 Mounting with Bolts 2 3 2 Mounting with Clamps 2 3 2 1 Clamp Mounting on Long Sides of the Frames 2 3 2 2 Clamp Mounting on Short Sides of the Frames 2 3 2 3 Clamp Mounting on Long Short Sides Edition 1 2019 L 33 Contact us 7 11 12 18 Appendix 1 Applicable Produ...

Страница 3: ...y through UL 1703 within this application class are considered to meet the requirements of Safety Class II The Fire rating is Class C in Canada but the Module Fire performance is type 1 in America with the specified construction in below table when used with a listed mounting system that has been rated as a Class A System when installed with type 1 modules is suitable to maintain the System Class ...

Страница 4: ...pection certifying that the installed module complies with the requirements of UL1703 The installation work of the PV array can only be done under the protection of sun sheltering covers or sunshades and only qualified person can install or perform maintenance work on this module Follow the battery manufacture s recommendations if batteries are used with modules Do not use this module to replace o...

Страница 5: ...e to the module and cause injury for you Only PV modules with the same cell size should be connected in series During transporting modules please attempt to minimize shock or vibration to the module as this may damage the module or lead to cell micro cracks During all transportation situations never drop the module from a vehicle house or hands This will damage the module Do not clean the glass wi...

Страница 6: ...e mated with each other connectors Connector model name Allowable mating connector model name TL Cable01F TL Cable01M PV JK00MO PV JK00MO UTXCFA4A UTXCMA4A Helios H4 Assembled Helios H4 Assembled PV JK03M 1 PV JK03M 1 PV KST4 6II UR PV KBT4 6II UR PV JK03M 2 PV JK03M 2 PV JK03M F xy PV JK03M M xy PV KBT4 EVO2 6II UR PV KST4 EVO2 6II UR PV JK03M F 2B PV JK03M M 2B Table 1 Allowable mating connector...

Страница 7: ... to the system design 2 2 2 Site Selection In most applications Jinko Solar PV modules should be installed in a location where they will receive maximum sunlight throughout the year In the Northern Hemisphere the module should typically face south and in the Southern Hemisphere the modules should typically face north Modules facing 30 degrees away from true South or North will lose approximately 1...

Страница 8: ...ns where the PV modules are attached to a permanent structure PV modules should be tilted so that the energy production from the PV modules will be maximized on an annual basis Only for UL listed products The System Fire Class Rating of the module or panel in a mounting system in combination with a roof covering should complete the requirements to achieve the specified System Fire Class Rating for...

Страница 9: ...ually check the module for any damage Clean the module if any dirt or residue remains from shipping 2 Check if module serial number stickers match 3 The minimum distance between modules should be more than 10mm for all installation methods 3 The mounting with bolts and or clamps on the long side of the frames could meet a maximum positive testing downward pressure of 5400Pa and negative testing up...

Страница 10: ...nstallation manual 7 The clearance between the module and the roof deck should be a minimum of 6 inches 15mm 2 3 1 Mounting with Bolts The frame of each module has 8 or 12 mounting holes used to secure the module to the support structure The module frame must be attached to a mounting rail using M8 corrosion proof bolts together with spring washers and flat washers in eight symmetrical locations o...

Страница 11: ... type of mounting method please be sure to use at least four clamps on each module two clamps should be attached on each long side of the module The applied torque value should be big enough to mount the modules steadily Please consult with the clamp or racking supplier for the specific torque value Please find detailed mounting information in the below illustration The mounting zone is greater th...

Страница 12: ... installed at the side with Clamp fitting method Clamp type Dimension mm Composition material End Clamp 40mm thickness 39x50x42 39x60x42 For 1 5mm thickness frame Aluminum alloy End Clamp 35mm thickness 41 5x50x40 Middle Clamp 42x50x28 42x60x28 For 1 5mm thickness frame Q O R P 13 5 0 5 2 15 2 5 Table 3 Mechanical dimensions specification and material when modules installed with mid clamps ...

Страница 13: ...f modules installed with clamps on long side of frame 2 3 2 2 Clamp Mounting on Short Sides of the Frames Module type Dimension mm Max Test Pressure 1600Pa positive 1600Pa negative mechanical load A B J K Group 2 1665 992 1684 1002 50 240 Group 8 1665 992 1684 1002 50 240 Group 11 1987 992 2000 992 2008 1002 50 240 Group 5 1987 992 2000 992 2008 1002 50 240 Group 1 Group 3 1650 992 1665 1002 50 24...

Страница 14: ...uld have similar current and modules must not be connected together to create a voltage higher than the permitted system voltage The maximum number of modules in series depends on system design the type of inverter and environmental conditions Module type Dimension mm Max Test Pressure 2400Pa positive 2400Pa negative mechanical load A B J K M N Group 1 Group 3 1650 992 1665 1002 50 240 400 420 Gro...

Страница 15: ...or a single component it is recommended the cross sectional area of cables be 4mm2 and the rated current of connectors be more than 10A otherwise cables and connectors will become overheated from high current Please note the temperature limit of the cables is 85 e Jinko modules can be grounded using bolts Attach the equipment grounding conductor to the module frame using the hole and hardware prov...

Страница 16: ...ll comply with the NEC article 250 j CNL models shall be in accordance with CSA C22 1 Safety Standard for Electrical Installations Canadian Electrical Code Part 1 k It is recommended that the M8 bolt be tightened to a torque of about 16 20 N m l The cable of the junction box is defined as L1 as showed below For Jinko standard module L1 is 900 1200mm and for customized module L1 can be based on you...

Страница 17: ...ristics of PV products at STC and the tolerance of Isc Voc Vmp and Imp is 10 6 Disclaimer of Liability Because the use of the manual and the conditions or methods of installation operation use and maintenance of photovoltaic PV product are beyond Jinko s control Jinko does not accept responsibility and expressly disclaims liability for loss damage or expense arising out of or in any way connected ...

Страница 18: ...SxxxPP 60B W xxx 200 275 in increment of 5 Group 4 JKMxxxP 72 JKMxxxP 72B JKMxxxP 72 J4 JKMxxxP 72B J4 JKMxxxPP 72 JKMxxxPP 72B JKMxxxPP 72 Plus JKMxxxPP 72 J4 JKMxxxPP 72B J4 JKMxxxPP 72 W JKMxxxPP 72B W JKMxxxPP 72B V JKMxxxP 72 V JKMxxxPP 72 V JKMxxxPP 72 V Plus JKMxxxPP 72 WV xxx 250 360 in increment of 5 Group 5 JKMxxxPP 72H JKMxxxPP 72H J4 JKMxxxPP 72HB JKMxxxPP 72H V JKMxxxPP 72H J4 V JKMxx...

Страница 19: ... JKMxxxM 72BL V xxx 370 400 in increment of 5 Group 11 JKMxxxM 72H JKMxxxM 72HB JKMxxxM 72H V JKMxxxM 72HB V xxx 250 410 in increment of 5 JKMxxxM 72HL JKMxxxM 72HL V JKMxxxM 72HBL JKMxxxM 72HBL V xxx 370 410 in increment of 5 Group 12 JKMSxxxM 72 JKMSxxxM 72 J4 JKMSxxxM 72 W xxx 250 355 in increment of 5 Group 13 JKMxxxM 72HL TV xxx 375 420 in increment of 5 JKMBxxxM 72HL TV xxx 410 455 in increm...

Страница 20: ...m Power Voltage Vmp V 30 8 31 1 31 4 31 7 32 0 32 3 32 5 32 8 33 1 33 4 33 6 33 9 Maximum Power Current Imp A 8 28 8 37 8 44 8 52 8 61 8 69 8 77 8 86 8 95 9 03 9 11 9 19 Open circuit Voltage Voc V 38 0 38 1 38 6 38 8 39 1 39 4 39 6 39 8 40 1 40 3 40 6 40 8 Module Type Group 1 and Group 2 xxx 200 205 210 215 220 225 230 235 240 245 250 Maximum Power at STC Pmax Wp 200 205 210 215 220 225 230 235 24...

Страница 21: ...2x35mm 66 30 39 45 x1 38 inch Maximum series overcurrent protective device rating 20A Module Type Group 3 xxx 200 205 210 215 220 225 230 235 Maximum Power at STC Pmax Wp 200 205 210 215 220 225 230 235 Maximum Power Voltage Vmp V 26 8 27 0 27 2 27 4 27 6 27 2 27 9 28 1 Maximum Power Current Imp A 7 46 7 60 7 73 7 86 7 98 8 12 8 23 8 36 Open circuit Voltage Voc V 33 5 33 7 34 0 34 3 34 5 34 8 35 0...

Страница 22: ...8 Maximum Power Current Imp A 7 31 7 39 7 49 7 59 7 71 7 81 7 93 8 03 8 11 8 15 8 20 8 30 Open circuit Voltage Voc V 43 5 43 7 43 9 44 1 44 2 44 4 44 5 44 7 44 9 45 1 45 3 45 6 Short circuit Current Isc A 8 05 8 18 8 26 8 33 8 43 8 49 8 58 8 61 8 69 8 76 8 84 8 91 Module Type Group 4 and Group 5 Group 5 xxx 310 315 320 325 330 335 340 345 350 355 360 365 370 Maximum Power at STC Pmax Wp 310 315 32...

Страница 23: ... 33 3 33 4 33 5 33 7 Maximum Power Current Imp A 7 69 7 78 7 88 7 99 8 12 8 22 8 35 8 45 Open circuit Voltage Voc V 41 3 41 5 41 7 41 9 42 0 42 2 42 3 42 5 Short circuit Current Isc A 8 52 8 61 8 70 8 77 8 87 8 94 9 03 9 06 Module Type Group 6 xxx 290 295 300 305 310 315 320 325 330 Maximum Power at STC Pmax Wp 290 295 300 305 310 315 320 325 330 Maximum Power Voltage Vmp V 34 0 34 4 34 8 34 9 35 ...

Страница 24: ... 8 76 Module Type Group 9 xxx 250 255 260 265 270 275 280 285 290 295 Maximum Power at STC Pmax Wp 250 255 260 265 270 275 280 285 290 295 Maximum Power Voltage Vmp V 30 5 30 8 30 9 31 2 31 4 31 6 31 8 32 0 32 2 32 4 Maximum Power Current Imp A 8 20 8 28 8 42 8 50 8 60 8 70 8 81 8 90 9 02 9 10 Open circuit Voltage Voc V 37 7 37 9 38 0 38 2 38 4 38 5 38 6 38 7 39 5 39 7 Short circuit Current Isc A ...

Страница 25: ...0 255 260 265 270 275 280 285 290 295 Maximum Power Voltage Vmp V 30 5 30 8 30 9 31 2 31 4 31 6 31 8 32 0 32 2 32 4 Maximum Power Current Imp A 8 20 8 28 8 42 8 50 8 60 8 70 8 81 8 90 9 02 9 10 Open circuit Voltage Voc V 37 7 38 0 37 9 38 2 38 4 38 5 38 6 38 7 39 5 39 7 Short circuit Current Isc A 8 85 8 96 9 10 9 19 9 28 9 40 9 49 9 51 9 55 9 61 Module Type Group 7 and Group 8 Group 8 xxx 300 305...

Страница 26: ... 34 8 35 0 35 3 35 6 35 9 36 1 36 3 36 5 36 7 36 8 37 0 37 2 37 4 Maximum Power Current Imp A 7 18 7 29 7 37 7 44 7 52 7 62 7 71 7 81 7 90 8 02 8 11 8 20 8 29 Open circuit Voltage Voc V 43 4 43 6 43 9 44 1 44 4 44 6 44 8 45 0 45 2 45 3 45 5 45 7 45 9 Short circuit Current Isc A 7 84 7 92 7 99 8 07 8 15 8 23 8 32 8 40 8 47 8 55 8 64 8 72 8 80 Module Type Group 10 and Group 11 xxx 315 320 325 330 33...

Страница 27: ...mm 77 91 39 45 x1 57 inch Half cut PV module 1987x992x40mm 78 23 39 05 x1 57 inch Large cell Half cut PV module 2008x1002x40mm 79 06 39 45 x1 57 inch Half cut PV module 2000x992x40mm 78 74 39 05 x1 57 inch Maximum series overcurrent protective device rating 20A Module Type Group 12 xxx 250 255 260 265 270 275 280 285 290 295 300 305 Maximum Power at STC Pmax Wp 250 255 260 265 270 275 280 285 290 ...

Страница 28: ...410 415 420 Maximum Power at BSTC Pmax Wp 410 415 420 425 430 435 440 445 450 455 Module Type Group 12 xxx 310 315 320 325 330 335 340 345 350 355 Maximum Power at STC Pmax Wp 310 315 320 325 330 335 340 345 350 355 Maximum Power Voltage Vmp V 37 4 37 6 37 8 38 0 38 2 38 4 38 7 38 9 39 1 39 3 Maximum Power Current Imp A 8 29 8 38 8 47 8 55 8 64 8 72 8 79 8 87 8 94 9 04 Open circuit Voltage Voc V 4...

Страница 29: ... 315 320 325 330 335 340 345 350 Maximum Power at STC Pmax Wp 315 320 325 330 335 340 345 350 Maximum Power Voltage Vmp V 32 7 32 9 33 1 33 24 33 40 33 62 33 76 33 94 Maximum Power Current Imp A 9 63 9 73 9 82 9 93 10 03 10 11 10 22 10 31 Open circui Voltage Voc V 39 9 40 1 40 3 40 39 40 46 40 60 40 75 40 87 Short circuitCurrent Isc A 9 99 10 07 10 15 10 25 10 34 10 43 10 53 10 62 Module Type Grou...

Страница 30: ...c A 10 07 10 17 10 26 10 36 10 45 10 54 Module Type Group 15 xxx 375 380 385 390 395 400 Maximum Power at BSTC Pmax Wp 420 425 430 435 440 445 Maximum Power Voltage Vmp V 39 32 39 43 39 53 39 64 39 74 39 85 Maximum Power Current Imp A 10 67 10 79 10 90 11 01 11 12 11 23 Open circuit Voltage Voc V 48 10 48 20 48 31 48 40 48 50 48 63 Short circuit Current Isc A 11 27 11 38 11 48 11 59 11 69 11 79 Ma...

Страница 31: ...Pmax Wp 350 355 360 365 Maximum Power Voltage Vmp V 33 00 33 17 33 38 33 51 Maximum Power Current Imp A 10 68 10 80 10 90 11 02 Open circuit Voltage Voc V 40 19 40 32 40 43 40 56 Short circuit Current Isc A 11 32 11 45 1155 11 67 Maximum system Voltage 1500VDC Dimensions 1704 1008 35 67 09 39 69 1 38 inch Maximum series overcurrent protective device rating 25A Bifaciality Coefficient φIsc Isc back...

Страница 32: ..._______________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ ...

Страница 33: ...4100 Tel 86 793 8588188 Fax 86 793 8461152 Jinko solar Import and Export co LTD Xuri District Shangrao Economic Development Zone Jiangxi Province China Postcode 334100 Tel 86 793 8618987 Fax 86 793 8461152 Customer Service cs jinkosolar com JinkoSolar U S Inc 595 Market Street Suite 2200 San Francisco CA 94105 Tel 415 402 0502 Fax 415 402 0703 us jinkosolar com Jinko Solar Canada Co Ltd Suite 703 ...

Страница 34: ...ent Zone Jiangxi Province China 334100 Tel 86 793 858 8188 Fax 86 793 846 1152 Jiangxi Manufacture Base No 58 Yuanxi Road Haining Yuanhua Industrial Park Zhejiang Province China 314416 Tel 86 573 8798 5678 Fax 86 573 8787 1070 Zhejiang Manufacture Base Jinko Building 99 Shouyang Road Jingan District Shanghai China 200027 Tel 86 21 5183 8777 Fax 86 21 5180 8600 ...

Отзывы: