9.1 Maintenance and service plan
Check or clean
Spare/replacements parts
System
Item
Periodic maintenance interval
Weekly
(first 4
weeks)
Every 6
months
Every 12
months
Every 36
months
Whole
Visual inspection of the
exterior
Tightening all major bolts
and nuts
Change desiccant bag in
the storage period.
Cleaning interior and ex-
terior with compressed air
Electrical
system
Measurement of Ohm
values according to test
record (max deviation
10%)
Checking the wiring con-
nections
Measurement of voltage
on condense heater
Measurement of insula-
tion resistance
<3 m Ohm at
1000 VDC
Note:
These procedures are considered normal maintenance and are performed at the
owner’s expense.