JETSTOR SAS 760J/JD Hardware Installation Guide
Page 57 of 71
Chapter 10
Appendix D: Replacing Enclosure Components
This section covers the replacement of components in the JETSTOR SAS 760J/JD
storage enclosure.
10.1 INTRODUCTION / GENERAL CAUTIONS
There are 3 major components of the JETSTOR SAS 760J/JD enclosure that are
customer replaceable. All three of the components are hot-swappable, meaning that they
can be pulled and replaced while the unit is in operation.
•
Disk Drives
•
Power & Cooling Modules (PCM)
•
I/O Controller Modules
Caution:
Before touching any of the enclosure components, ground
yourself and take antistatic precautions. Use an antistatic wrist strap
and a grounding wire as a minimum precaution.
Caution:
The JETSTOR SAS 760J/JD is intended to run with two
PCMs and at least one I/O controller (maximum two I/O controllers)
installed. If only one I/O controller is being used, an I/O ‘blank’ must
be installed in the other slot to maintain proper temperatures within
the box.
Caution:
When replacing any component in the JETSTOR SAS
760J/JD, it is recommended that the replacement be installed within
five minutes
to maintain proper cooling. The JETSTOR SAS 760J/JD
will sound an alarm if an overtemp condition is reached. If this is not
addressed, the potential exists for the unit to perform an auto-
shutdown to protect the internal components from thermal damage.