OPERATION AND MAINTENANCE MANUAL PN 28.04.1014 GPU JET-POWER FILTER II 2500 PN 28.09.1013
PAGE 23/43
From 150 to 220m
Cable 95mm
2
35mm
2
From 220 to 300m
Cable 120mm
2
50mm
2
THE USE OF THE NEUTRAL CABLE IS INDISPENSABLE.
THE NEUTRAL CABLE IS BLUE.
IMPORTANT NOTES:
The gauges can seem exaggerated from the “JET-POWER” consump-
tion of current, but it is very important that the drop of tension be as
minimal as possible, not to compromise its functioning.
A great drop of tension in the exit, below of the bearable limits during
the peak of starting the turbine, can cause serious consequences for the
turbine (maximum drop of 10%).
DO NOT use cables with gauges below the specified, so that the instal-
lation does not come to be problematic and insufficient to the departure
of the turbines.
A good installation can be the guarantee of years of services without
departure problems.
If it will not be used for departures it can be considered using 40% of
the real distance.
Follow correctly the specifications and avoid problems of insufficient
current.