Figure 2. MTII4200-H-A-D-x-x-H-xxx/xxx Bent Bottom Left Hand Angled Assembly 
 

(3.500)

DETERMIND BY SE

POSITION AT ASSEMBLY

MAX. ACTIVE SENSING LENGTH

 

 

2. PRODUCT DESCRIPTION 

The MTII4200 liquid level sensor is a multifunctional transmitter with 4-20 mA loop and HART.  It provides an analog 
output of level and the HART digital protocol. Outputs can be monitored using 4-20 mA signal output, a HART device 
(hand-held or PC-compatible software), the integral display, or all of the above.  The MTII4200 transmitters are available 
in a single cavity explosion-proof enclosure. 
 

2.1 MTII4200 Transmitter Specifications 
 

PARAMETER  SPECIFICATIONS 

 

 

LEVEL OUTPUT

 

Measured Variable:

Liquid level, interface level 

Output: 

4-20 mA, HART 

Full Range:

12 to 228 in. (46 to 579 cm) for mounting style S 
12 to 144 in. (46 to 365 cm) for mounting style H 

Non-linearity: 

0.020% F.S. (Independent BSL) or 1/32 in. (0.794 mm)* 

Repeatability: 

0.005% F.S. or 0.005 in. (0.127 mm)* 

Sensor Operating Temperature:

-40 to 300°F (-40 to 149°C) Ambient 

 

 

GAUGE LOOP

 

Input Voltage Range:

10.5 to 36 VDC 

Reverse Polarity Protection:

 

Series diodes

 

Transient Protection: 

Stage 1: line-to-ground surge suppressors; 2500 Amps 
peak (8/20 µsec.) 
Stage 2: line-to-line and line-to-ground transient 
suppressors; 1500 Watts peak (10/1000 µsec.) 

 

 

CALIBRATION

 

Zero Adjust Range: 

Anywhere within the active length 

Span Adjust Range:

 

Full Scale 

0.5 ft. (152 mm) from zero 

 
 
 

 
 
 

Содержание MTII4200 Series

Страница 1: ...D B TOP RIGHT HAND C BOTTOM RIGHT HAND D BOTTOM LEFT HAND ALARM SETTING L 3 85 mA DEFAULT H 22 5 mA MAX SENSING LENGTH IN INCHES ON 6 INCH INCREMENTS LCD DISPLAY M mA OUTPUT DEFAULT I INCHES P PERCENT...

Страница 2: ...II4200 transmitters are available in a single cavity explosion proof enclosure 2 1 MTII4200 Transmitter Specifications PARAMETER SPECIFICATIONS LEVEL OUTPUT Measured Variable Liquid level interface le...

Страница 3: ...f Operation The MTII4200 transmitters precisely sense the position of an external float by applying an interrogation pulse to a waveguide medium This current pulse causes a magnetic field to instantly...

Страница 4: ...Transmitter Always follow applicable local and national electrical codes and observe polarity when making electrical connections Never make electrical connections to the MTII4200 transmitter with powe...

Страница 5: ...how the HART protocol is applied to the MTII4200 level transmitter only Using the HART interface allows for calibration without having to remove the transmitter from the process and position the float...

Страница 6: ...to exit the program mode replace the calibration jumper to the ON position and return your controllers to automatic To set high value You should now be in the Range Values screen To set the 20 mA Upp...

Страница 7: ...n until it is Press the enter button to set the low level of the range At this time position the float magnet at the desired low level point and keep it there while pressing the Enter button and holdi...

Отзывы: