Cabinet Dimensions

*For non-vented (recirculating) installations

**The controls are located on the right side of the range hood. A 

minimum clearance of 1½" (3.8 cm) must be maintained 
between the range hood canopy and the right side cabinet to 
allow access to controls.

IMPORTANT:

Minimum distance "X": 18" (45.7 cm) from electric cooking 
surface.
Minimum distance "X": 22" (55.9 cm) from gas cooking 
surfaces.
Suggested maximum distance "X": 24" (61.0 cm)

For vented installations, the chimneys can be adjusted for 
ceilings between 7’ 11" (2.4 m) and 9' 3" (2.8 m).
For non-vented (recirculating) installations, the chimneys can 
be adjusted for ceilings between 7’ 11" (2.4 m) and 9' 7" (2.9 m).
*NOTE: The range hood chimneys are adjustable and designed 

to meet varying ceiling or soffit heights depending on the 
distance “X” between the bottom of the range hood and the 
cooking surface. For higher ceilings, a Chimney Extension Kit 
Part Number W10272075 (stainless) or W10272074 (white) is 
available from your dealer or an authorized parts distributor. The 
chimney extension replaces the upper chimney shipped with the 
range hood.

Venting Requirements

Vent system must terminate to the outside, except for non-
vented (recirculating) installations.

Do not terminate the vent system in an attic or other enclosed 
area.

Do not use 4" (10.2 cm) laundry-type wall caps.

Use metal vent only. Rigid metal vent is recommended. Do 
not use plastic or metal foil vent.

The length of vent system and number of elbows should be 
kept to a minimum to provide efficient performance.

For the most efficient and quiet operation:

Use no more than three 90° elbows.

Make sure there is a minimum of 24" (61 cm) of straight vent 
between the elbows if more than 1 elbow is used.

Do not install 2 elbows together.

Use clamps to seal all joints in the vent system.

The vent system must have a damper. If the roof or wall cap 
has a damper, do not use the damper supplied with the range 
hood.

Use caulking to seal exterior wall or roof opening around the 
cap.

The size of the vent should be uniform.

Cold weather installations

An additional back draft damper should be installed to minimize 
backward cold air flow. A thermal break should be installed to 
minimize conduction of outside temperatures as part of the vent 
system. The damper should be on the cold air side of the thermal 
break.
The break should be as close as possible to where the vent 
system enters the heated portion of the house.

Makeup air

Local building codes may require the use of makeup air systems 
when using ventilation systems greater than specified CFM of air 
movement. The specified CFM varies from locale to locale. 
Consult your HVAC professional for specific requirements in your 
area.

Venting Methods

This range hood is factory set for 8" (20.3 cm) round venting 
through the roof or wall. An 8" (20.3 cm) round vent system is 
needed for installation (not included). To vent through the wall, a 
90° elbow is needed. 
This range hood can also be set for 3¼" x 10" (8.3 x 25.4 cm) 
rectangular venting out the back using the 3¼" x 10" (8.3 x 
25.4 cm) rectangular damper (supplied). See the “Connect Vent 
System” section for details for installing the damper and vent 
system. 
NOTE: Flexible vent is not recommended. Flexible vent creates 
back pressure and air turbulence that greatly reduce 
performance.
NOTE: This hood can be installed without the chimney covers 
when venting directly out the back or when using the recirculation 
kit with the top grille cap. See “For non-vented (recirculating) 
installation without vent cover only:” in the “Connect Vent” 
section.

10" (25.4 cm) min.
13" (33.0 cm) max.

9¹⁄₂

" (24.1 cm)

2" (5.1 cm) min.
9" (22.9 cm) min.*

Centerline

Side

cabinet

Side

cabinet

Vent and power

supply cable

entry location

33½" (85.1 cm)

minimum

36" (91.4 cm)

recommended

"X"

bottom of 

canopy 

to cooking 

surface

10" (25.4 cm) min.
13" (33.0 cm) max.

Cooking surface

1½" (3.8 cm) minimum**

17" (43.2 cm)*

Содержание 32inch (81.3 CM) WALL-MOUNTPERIMETRIC RANGE HOOD

Страница 1: ...site at www jennair com In Canada call 1 800 JENNAIR 1 800 536 6247 or visit our website at www jennair ca Instructions d installation et Guide d utilisation et d entretien Au Canada pour assistance i...

Страница 2: ...l installation 27 UTILISATION DE LA HOTTE 28 Commandes de la hotte 28 ENTRETIEN DE LA HOTTE 29 Nettoyage 29 SCH MA DE C BLAGE 30 ASSISTANCE OU SERVICE 31 Au Canada 31 Accessoires 31 GARANTIE 31 RANGE...

Страница 3: ...ardous or explosive materials and vapors CAUTION To reduce risk of fire and to properly exhaust air be sure to duct air outside do not vent exhaust air into spaces within walls or ceilings attics or i...

Страница 4: ...bserve all governing codes and ordinances Have a qualified technician install the range hood It is the installer s responsibility to comply with installation clearances specified on the model serial r...

Страница 5: ...per If the roof or wall cap has a damper do not use the damper supplied with the range hood Use caulking to seal exterior wall or roof opening around the cap The size of the vent should be uniform Col...

Страница 6: ...d OH 44131 5575 A 120 Volt 60 Hz AC only 15 amp fused electrical circuit is required If the house has aluminum wiring follow the procedure below 1 Connect a section of solid copper wire to the pigtail...

Страница 7: ...cm rectangular vent IMPORTANT All screws must be installed into wood If there is no wood to screw into additional wall framing supports may be required Remove the template 9 Drill 4 8 mm pilot holes a...

Страница 8: ...g 5 Remove the 4 mounting screws holding the 8 20 3 cm diameter transition damper to the canopy top Set the damper and mounting screws aside 6 Remove the 4 screws holding the blower motor to the canop...

Страница 9: ...opy using 3 of the the screws removed from the 8 20 3 cm diameter transition damper Tighten screws Install Range Hood NOTE For rear venting installations the 3 x 10 8 3 x 25 4 cm damper must be assemb...

Страница 10: ...bottom of the hood exhaust outlet 3 Cut the duct to the measured size X 4 Remove the air deflector 5 Slide the duct onto the bottom of the air deflector 6 Place the assembled air deflector and duct o...

Страница 11: ...lief screw 9 Install terminal box cover 10 Check that all light bulbs are secure in their sockets 11 Reinstall top cover using 5 screws removed previously Tighten screws 12 Reconnect power A Cover scr...

Страница 12: ...ood Care section 3 Check the operation of the range hood blower and light See the Range Hood Use section NOTE To get the most efficient use from your new range hood read the Range Hood Use section RAN...

Страница 13: ...Reinstall the filter by making sure the spring release handles are toward the front Insert aluminum filter into upper track 5 Push in spring release handle 6 Push up on metal filter and release handl...

Страница 14: ...rd Y BR W R BK BU GY Y G Y Y Y Y Y Y Y Y TRANSFORMER Capacitor High Speed Switch Operation FUNCTION Off Lamps Low Speed POSITION Brown Yellow L LA Med Speed Brown White L 1 Brown Red L 2 Brown Black L...

Страница 15: ...mber W10272074 White Parametric Trim Kit Order Part Number W10272066 Oil Bronze Order Part Number W10272067 Black In Canada Call the dealer from whom your appliance was purchased or call Jenn Air at 1...

Страница 16: ...R OF IMPLIED WARRANTIES IMPLIED WARRANTIES INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLO...

Страница 17: ...re appareil m nager Assurez vous de toujours lire tous les messages de s curit et de vous y conformer AVERTISSEMENT DANGER Voici le symbole d alerte de s curit Ce symbole d alerte de s curit vous sign...

Страница 18: ...que d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plaf...

Страница 19: ...10 8 3 x 25 4 cm 2 chevilles d ancrage mural de 8 x 40 mm 4 chevilles d ancrage mural de 10 x 50 mm Exigences d emplacement IMPORTANT Observer les dispositions de tous les codes et r glements en vigu...

Страница 20: ...m talliques Des conduits m talliques rigides sont recommand s Ne pas utiliser de conduit en plastique ou en feuille m tallique La longueur du circuit d vacuation et le nombre de coudes doit tre r dui...

Страница 21: ...n Pour les installations sans d charge l ext rieur recyclage sans cache conduit uniquement Installations sans d charge l ext rieur recyclage S il n est pas possible d vacuer les fum es et vapeurs de c...

Страница 22: ...ion et de tous les codes et r glements en vigueur INSTRUCTIONS D INSTALLATION Pr paration de l emplacement Il est recommand d installer le circuit d vacuation avant de proc der l installation de la ho...

Страница 23: ...depuis le tableau de distribution avec fusibles ou disjoncteurs pour r aliser facilement le raccordement dans le bo tier de connexion de la hotte REMARQUE Ne pas mettre le syst me sous tension avant...

Страница 24: ...r vers le bas pour l immobiliser et aligner les trous destin s aux vis de montage Installer les vis de montage et les serrer 10 Rebrancher la fiche du ventilateur 11 Remonter la vitre centrale sur l a...

Страница 25: ...l ext rieur uniquement 1 Installer le circuit d vacuation sur le raccord de transition 2 Serrer le raccord avec des brides de serrage 3 V rifier que les clapets anti retour fonctionnent correctement P...

Страница 26: ...homologation UL ou CSA 4 Acheminer le cordon d alimentation du domicile travers le serre c ble dans le bo tier de connexion A Vis de montage du clapet A A Vis du couvercle B Couvercle sup rieur AVERTI...

Страница 27: ...des sections sup rieure et inf rieure du cache conduit pousser la section inf rieure vers le bas sur la hotte et soulever la section sup rieure vers le plafond pour installer l aide des deux vis de 4...

Страница 28: ...tilateur Les boutons FAN SPEED vitesse du ventilateur permettent d allumer le ventilateur et d en contr ler la vitesse ainsi que le niveau sonore ce qui permet de le faire fonctionner sans bruit On pe...

Страница 29: ...enfoncer la partie centrale inf rieure pour l embo ter Filtres d installation sans d charge l ext rieur recyclage Le filtre charbon n est pas lavable Celui ci devrait durer pendant six mois dans des c...

Страница 30: ...JA VE JA JA JA JS JA JA JA JA TRANSFORMER Capacitor Vitesse lev e Fonctionnementducommutateur FONCTION Off arr t Lampes Vitesse basse POSITION Marron Jaune L LA Vitesse moyenne Marron Blanc L 1 Marro...

Страница 31: ...ompter de la date d achat lorsque ce gros appareil m nager est install utilis et entretenu conform ment aux instructions jointes au produit ou fournies avec la marque Jenn Air de Whirlpool Corporation...

Страница 32: ...plus tendue ou plus compl te que la garantie limit e fournie avec ce gros appareil m nager adressez vous Jenn Air ou votre d taillant pour obtenir les modalit s d achat d une garantie tendue LIMITATI...

Отзывы: