manualshive.com logo in svg
background image

5

MAIN WARNING

RECOMENDED GUIDELINES

RELATIVE PROFILE

It is possible to run all profiles with the Control TC plugged or unplugged.

When the Control TC is plugged, all the working modes follow the target temperatures of the selected 
profile.

Once a profile has been run for the first time, it is already available in the “relative profile” mode. This 
means you can run this profile without plugging the Control TC. If you place the board on the PreHeater 
as the same way than you run the profile for the first time with the TC, the board will be heated identically. 
To make it easier, the PH321 support has a numbered ruler and fitting parts.

Each time a profile runs completely with the plugged TC, the Relative Profile is updated.

It is possible to test a Relative profile by using the Test Relative profile within the Profile Settings menu.

MAXIMUM RAMP-UP EXCEED

The maximum ramp-up rate is set in the Station Setting Menu. The unit shows this warning if anytime 
you exceed this gradient. 

NO RELATIVE PROFILE. CONNECT TC

The profile should be run completely at least one time in order to be saved in the relative profile. 

SECURITY TERMOCOUPLE EXCEEDED

The unit is equipped with an auxiliary TC. It is possible to set a temperature target for this TC in the Station 
Settings Menu. The unit stops when the auxiliary TC reaches the target set.

INVALID PROGRAM. Error > 10ºC

This is displayed when the actual temperature differs from the setpoint by more than 10ºC for 20s.
The unit incorporates 3 default profiles which can be appropriate for most common jobs about FR4 bila-
yer substrates, multilayer and thick multilayer respectively. 

1.

 Place the Control TC as near as possible of the component to work with.

2.

 If there is any sensitive component, use the Auxiliary Thermocouple as protection.

3.

  For  repetitive  jobs,  you  can  work  without  TC.  Once  you  set  the  appropriate  profile  by  using  the 

Thermocouple, you can use the Relative Profile for the following PCBs to repair. The heating will be 
always the same as long as you work with the same board on the same place and position. 

4. 

Do not exceed the allowable heat cycles for a board or component.

5.

 Do not recommend to exceed ramp-up rates of more than 3-4 °C /sec

Отзывы: