background image

Jason International, Inc.  •  

 

501.771.4477  

 

 

 

Page 5 of 15

 

 

 

 

Customer Service :  800.255.5766 

5.  Extend piping stubout through the floor as illustrated in 

Figure 7.  

Piping between the remote blower location and 

the bath can be insulated using a minimum of 1/2” thick 

insulation. 

warNING:

  Any  modification  to  the  equipment  is  not 

recommended and will void the manufacturers warranty. 

6.  Attach one end of the hose to the bath connection and 

attach the other end of the hose to the 1-1/2” PVC pipe 

that is plumbed to the blower with the included clamps.  

7.  The keypad cable, remote control cable (if applicable), and 

the light cable must be routed through the floor cutout and 

connected to the control box.  

warNING:

 When routing 

cables, 

do not allow the cable to be pinched under the bath.

  

Use the tie buttons attached to the bath to support the 

cables.  

NOTe:

 A minimum of four (4) feet of hose and cable must 

be free from binding to allow for pulling the cables back 

up through the floor cutout.  When installing on a cement 

slab a conduit may be used if desired to run the cable from 

the bath to the control box.  This will allow the bath to be 

lifted and removed from the skirt if access is required in 

the future.  

During installation if it is preferred to run the blower hose 

on top of the floor, a 2 1/2” diameter hole can be drilled in 

the toe kick area of the skirt.  A means to cover the hole, 

hose, and wires is not provided.  

(See Figure 7.)

  

8.  Before finishing the installation, it is recommended that the 

bath controls be tested without filling the bath with water 

to assure all electric connections are properly working.  

Refer to the 

Operating Instructions 

section on page 11 or 

12 for testing.  

Faucetry connections should also be tested for leaks at 

this time.

9.  Remove the 2” x 4” boards and lower the bath into the 

skirt.  

warNING:

 

When you lower the bath into the skirt, do not 

allow the hose sections to bind.

 Align the drain and overflow 

with the corresponding bath holes and the bath brackets 

with the pre-drilled holes in the skirt. 

(See Figure 8.)

Jason baths are designed to be supported at the base of the 

bath.  If the floor is smooth and level the bath’s Level Form™ 

Base will provide proper drainage and support. 

(See Figure 8.)  

NOTe: 

The bottom of the bath’s Level Form™ Base must be 

level with the bottom of the skirt.)

 Note:

  Do not use a sand 

bed to install or level the bath.

10. Start with one (1) bolt and lift the bath enough to partially 

install the bolts.  Do not tighten the bolts completely at 

this time.  Align the bolts with the slot in the bath bracket.  

Repeat  the  process  until  all  six  (6)  bolts  are  partially 

installed.  

11.Continue to fully tighten all six (6) bolts  with a 3/8” open-

end wrench. 

(See Figure 9.)

 

Figure 7

STANdArd ANd SIgNATurE EdITION

INSTALLATION INSTRUCTIONS (cont.)

L2-W HITE W ITH

RED M ARK

L1-BLACK

G ND-G REEN

FRO M CO NTRO L

L2

240 V

L1

NO CO NNECTIO N

(LO AD NEUTRAL)

BREAKER BO X

Note: The load neutral term inal is not used. There should be no connection to the load neutral

term inal on the G FCI circuit breaker. The green wire (G ND-G REEN) is the equipm ent ground

and should be connected to the neutral bus found in the m ain breaker box.

BREAKER BO X CO NNECTIO NS

SIgNATurE EdITION ONLY

Note: 

The load neutral terminal is not used.  There 

should  be  no  connection  to  the  load  neutral 

terminal  on  the  GFCI  circuit  breaker.    The  green 

wire (GND-GREEN) is the equipment ground and 

should be connected to the neutral bus found in the 

main breaker box.

Содержание Forma AirMasseur AC635P

Страница 1: ...llation will not be covered by warranty and is the responsibility of the installer ALL WARRANTY CLAIMS ON ACRYLIC SURFACE DAMAGE 49 1000 113 Date 11 07 MUST BE MADE PRIOR TO INSTALLATION Inspect plumbing and bath surface for missing or damaged components Alert your dealer of any discrepancies To protect the unit from damage keep the unit in its carton until ready for installation EQUIPMENT ACCESS ...

Страница 2: ...ed according to the instructions herein 5 Aninstallationtemplateisprovidedtolocatethefloordrain location sump area location remote blower tubing floor cutout location water inlet stub out location mounting holes and skirt center lines Tape the template to the sub floor in its desired location 6 Mark on the sub floor the sump area location the water inlet stub out location and the remote blower tub...

Страница 3: ...netheproperfittothebath NOTE Itisrecommended that the Geberit drain and overflow model 150 176 be used If any other drain is used it may not conform to these instructions Drain Not Included This drain can be purchased from Figure 3 any authorized Jason International Inc dealer Position the bath in place and attach the drain and overflow to the floor drain P trap CAUTION Only dry fit the drain and ...

Страница 4: ...OTE MOUNTING of air blower Do not remote mount the blower and control box more than 15 feet away from the air inlet of the bath Choose a location as close as possible to the bath to assure maximum efficiency 1 The installer is to determine the layout of the piping exact remote mount location and service access before beginning any work Use1 5 ABSorPVCplastictubing Locatethecontrolbox with the blow...

Страница 5: ... Instructions section on page 11 or 12 for testing Faucetry connections should also be tested for leaks at this time 9 Remove the 2 x 4 boards and lower the bath into the skirt WARNING When you lower the bath into the skirt do not allow the hose sections to bind Align the drain and overflow with the corresponding bath holes and the bath brackets with the pre drilled holes in the skirt See Figure 8...

Страница 6: ...edwiththeuseofawood edge trowel Paint or tar stains may need to be removed with a cleaner such as paint thinner turpentine or isopropyl alcohol rubbing alcohol Never allow the cleaner to soak against the surface for long periods of time Always rinse the surface immediately following the use of cleaners NOTE Follow the manufacturers instructions for safely using these or similar products If the sur...

Страница 7: ... 6 ABOVE SUB FLOOR A licensed electrician must provide the dedicated electrical service protected by a GFCI The location of the GFCI must be at least five 5 feet away from the inside surface of the bath and accessible for regular testing Use copper conductors only DANGER RISK OF ELECTRIC SHOCK Connect only to a circuit protected by a Ground Fault Circuit Interrupter GFCI In the unlikely occurrence...

Страница 8: ...bath from bacteria viruses etc while leaving the plumbing lines clean and fresh The ozone system works automatically in conjunction with the blower motor TOUCHPAD FEATURES A main control touchpad mounted on the bath deck features an LCD readout which alternately indicates the water temperature 5 F and air bath time remaining The touchpad operates all functions of the blower as well as the LED Mood...

Страница 9: ...th industry The blower control box must be properly connected for the bath to function correctly THE BLOWER CONTROL BOX The blower keypad LED light ozone sanitation unit and temperature sensor must be plugged into the proper receptacles for correct operation of the AirMasseur system See Figure 12 for connections A The junction box for the blower control box must be connected into a 240v 15 amp GFC...

Страница 10: ...and the bath is completely drained the blower will start again for a 2 minute purge cycle that dries the air channel Note that the LCD display will read PURGE and begin to countdown the 10 or 20 minute pause before the purge cycle begins The readout will display PURGE ON during the purge cycle Any time during the pause before the purge cycle begins pressing and holding the Blower Speeds icon will ...

Страница 11: ...by a slow flashing light Pressing the icon again will change the blower to Pulse mode This is indicated by a rapid light flash Pressing the icon a third time moves the blower back to Constant mode Blower Speeds Icon The Blower Speeds icon is used to increase or decrease the blower speed once the blower is on Press and hold the icon to decrease the blower speed until the desired inten sity is reach...

Страница 12: ...his function has a 2 hour timer and remembers the last mode The LCD displays Light On or Light Off while the key is pressed for less than 2 seconds Light Cycle is displayed if pressed for more than 2 seconds OPTION ICON This key is reserved for future options CUSTOMIZED SETTINGS The12characterLCDdisplaycanbecustomizedbypressing the Blower and Blower Speeds icons simultaneously for 5 seconds while ...

Страница 13: ...olution i e glass cleaner and a soft wet cloth or sponge Do not run the air system with foaming cleaners or soaps Rinse the bath thoroughly after cleaning SURFACE MAINTENANCE Areas with minor scratches or dull surfaces can be restored by applying commercially available plastic polish i e Novus Plastic Polish No 2 available at your Jason dealer followed by an application of acrylic paste wax Buff t...

Страница 14: ...fuses and replace if bad b Make sure plug is fully inserted into the outlet c Check and reconnect if necessary Blower shut off by itself or before time elapses a Blower motor overheated and thermal protection device deactivated motor possibly low voltage b GFCI tripped a Check that blower has sufficient ventillation and that the intake into the blower is not blocked Clear and allow the motor to co...

Страница 15: ...ng Never use the therapy bath while under the influence of alcohol anticoagulants stimulants antihis tamines vasoconstrictors vasodilators hypnotics narcotics or tranquilizers F Persons with a medical history of heart disease low or high blood pressure circulatory system problems or diabetes should consult a physician before using a therapy bath G Persons using medication should consult a physicia...

Отзывы: