The User Manual of JAC200 Series General Frequency Converter
- 70 -
place
source
0
Without binding
1
The frequency source of digital setting
2
AI
3
Reserved
4
Key
potentiometer
5
Reserved
6
Multi-stage instruction
7
Simple PLC
8
PID
9
Communication reference
Tens place
The selection of terminal command binding frequency
source (0-9, same with ones place)
Hundreds
place
The selection of communication command binding
frequency source (0-9, same with ones place)
Thousands
place
The selection of automatic running binding frequency
source (0-9, same with ones place)
Define the binding combination among 3 kinds of operation commands and 9 frequencies given channel to
implement synchronous switch.
Above the meaning of frequency given channels is same with frequency source X selection F0-03. Please
see Function code description F0-03.
Different operation command can bind same frequency given channel.
When command source has binding frequency source, the frequency source set by F0-03-F0-07 is invalid in
the valid term of command source.
Group F1 The first motor parameter
F1-00
Motor type selection
Default value
0
Set range
0
Common asynchronous motor
1
Frequency conversion asynchronous motor
F1-01
Rated power
Default value
Model dependent
Set range
0.1kW
~
400.0kW
F1-02
Rated voltage
Default value
Model dependent
Set range
1V
~
2000V
F1-03
Rated current
Default value
Model dependent