Step 4:
Programming of the logic.
In the logic is checked, which switching clock channel is active, and if it is summer or winter.
The combinations would be as follows:
Time switch channel 1
AND
Comparator 1
= Flag 82
//Summer Tariff 1
Time switch channel 2
AND
Comparator 2
= Flag 83
//Summer Tariff 2
permanent active
NOT AND
Comparator 1
= Flag 84 //Inverting comparator
Time switch channel 3
AND
Flag 84
= Flag 85 //Winter Tariff 1
Time switch channel 4
AND
Flag 84
= Flag 86 //Winter Tariff 2
Flag 82
OR
Flag 85
= Flag 87 // Result Tariff 1 Active
Flag 83
OR
Flag 86
= Flag 88 // Result Tariff 2 Active
Programming of the function combinations in
panel „Logic operations for maker flags“
Step 5:
Programming of the output configuration
The flags are assigned to the energy meters in the I/O assignment.