7
TN and TT systems
Measurement is designed for 3-phase sys-
tems with neutral conductors (TN and TT
systems).
Fig. Block diagram, UMG507 in the TN sys-
tem.
Fig. Block diagram, UMG507 in the IT system
with N.
Fig. Block diagram, UMG507 in the IT system
without N.
IT systems
The UMG507 is only conditionally suitable for
use in IT systems, as the measurement volt-
age is measured at the housing potential and
the input impedence of the device causes a
leakage current to the earthing. The leakage
current can cause the insulation monitoring
in IT systems to respond. It must also be en-
sured that the maximum permissible voltage
at the inputs of the UMG507 are not exceeded
to earth (e.g. in case of a phase-to-earth fault).
The connection options shown in Fig. 4.1b
(with PEN conductor) or Fig. 4.6a (without a
PEN conductor) are suitable for IT systems
without restriction. Here the IT system is insu-
lated through the use of voltage transformers.
It is absolutely necessary to connect
the
PEN conductor N.
Product Description
UMG507
System
earthing
DC
AC/DC
230/400V 50/60Hz
L2
L3
L1
auxiliary power
voltage measurement
4M
4M
4M
4M
PE
Impedance
L1
L3
L2
N
UMG507
System
earthing
DC
AC/DC
500V 50/60Hz
L2
L3
L1
auxiliary power
voltage measurement
4M
4M
4M
4M
PE
Impedance
PE - L max.
500V
L1
L3
L2
N
UMG507
System
earthing
DC
AC/DC
PE
230/400V 50/60Hz
L2
L3
N
L1
auxiliary power
voltage measurement
4M
4M
4M
4M
PE
PE - L max.
500V
L1
L3
L2
N