35
UMG 96RM-P/-CBM
Battery monitoring function
The device indicates the condition of the battery via
the symbol "EEE" followed by "bAt" and the status
number. Depending on the status number a confirmation
of the information by the operator may be required. It is
recommended that the battery be replaced.
Fault number
Battery fault status
Fault message symbol
Status
Status description
EEE
bAt
321
•
Battery capacity is <85%
•
Operator confirmation required
•
Message appears weekly after confirmation
•
Battery should be replaced
EEE
bAt
322
•
Battery capacity is <75%
•
Battery capacity is too low
•
Can only be detected after resumption of
mains power
•
Battery should be replaced
EEE
bAt
330
•
Battery capacity OK
•
Clock is stopped and must be set
EEE
bAt
331
•
Battery capacity is <85%
•
Clock is stopped and must be set
•
Operator confirmation required
•
Message appears weekly after confirmation
•
Battery should be replaced
EEE
bAt
332
•
Battery capacity is <75%
•
Clock is stopped and must be set
•
Operator confirmation required
•
Message appears daily after confirmation
•
Battery should be replaced