8.3 Shielding
For connections via the interfaces, provide
a twisted and shielded cable and observe the
follow points for the shielding:
·Ground the shields of all cables that lead into
the cabinet at the cabinet entrance.
·Connect the shield over a large area and with
good conductivity to a noiseless ground.
·Do
NOT
connect the shield to terminal C (GND)
·Mechanically trap the cable above the
grounding clamp in order to prevent damage
caused by cable movement.
·Use appropriate cable entries for guiding the
cable into the switch cabinet, for example, PG
glands.
WARNING
Transmission errors and risk of injury due to
electrical disturbance!
Due to atmospheric discharge, errors in the
transmission and dangerous voltages on the
device can arise.
Therefore, please observe the following:
·
Place the shielding at least once on
functional ground (PE).
·
If there is a greater source of interference
or the frequency converters are in the
switch cabinet, connect the shielding as
close as possible on the device to the
functional ground (PE).
·
Adhere to the maximum cable length of
12000 m at a baud rate of 38.4 k.
·
Use shielded cable.
·
Lay interface lines separated or additionally
insulated from the system parts carrying
mains voltage.
8.4 Termination resistors
The cable is terminated with resistors (bus
terminator, 120 Ω, 1/4 W) at the start and end of
a segment.
The device does not contain an integrated
termination resistor.
Correct
Incorrect
Terminal strip in the switch cabinet.
Device with RS485 interface
(without termination resistor)
Device with RS485 interface
(With termination resistor on the device)