www.janitza.com
UMG 804
39
It is also possible to trigger manual waveform
captures using the Waveform Capture function on
the Waveform Capture page. The resulting data
are waveforms for each channel will be stored on
a usb stick as a CSV file. These can be viewed
graphically using the waveform graphing template.
CONFIGURATION TAB:
The Configuration tab has six sub tabs [General
Settings], [CT Size], [Breaker Size], [Voltage Pha-
se], [True Circuit] and [Update Core Module] which
define the configuration.
Breaker Size:
You should use the real breaker size on this form and in registers 296 - 391. The alarm threshold is then a
percentage of the actual breaker size which is set in registers 1014 and 1015.
If you have a 32 amp breaker and want an alarm at 80% of that value you would write a value of 32 on the
webpage or register 296. Then in register 1014 you would write a value of 80.