UMG 804
www.janitza.com
22
BLACK
WIRE
WHITE
WIRE
Push to release
conductor
Insert CT Conductor
Circuit Designations
Conductor Size: 16-20 AWG (0.5-1.5mm)
Stripping length: 8mm
Fig. 9: Current Transformer installation
CT installation orientation should have the label
side of the CT face the load side of the breaker as
shown in figure 9. This is not critical as the monitor
will automatically correct for breakers that have
been installed in the wrong orientation.
CT-
LOAD SIDE
CT LABEL
MUST FACE
LOAD SIDE
LINE SIDE
CT+
10.4 Cable Ports and Circuit Designation
It is critical the correct Smart Port receptacle
is connected to the correct CT Interface Board.
The circuit number expressed by the monitor will
be determined by the port the Interface Board
is plugged into. Native circuit numbers may be
Fig. 10: Circuit designation by Smart Port
changed using the Dynamic Circuit (True Circuit)
display configuration tool. The chart below shows
a relationship between the Smart Port and CT
Interface Card based on the Schneider Emulation
point map.