8. Core Module Installation
DANGER
Disconnect power to the panel or equipment
on which the monitor is being installed before
starting the installation.
DANGER
Débranchez l’alimentation du panneau ou de
l’équipement sur lequel le moniteur est en cours
d’installation avant de commencer l’installation.
The Core Module can be housed in existing
enclosures where permitted by code or inside
standard electrical enclosures. Note that when
using the cellular modem option the antennas
must be mounted on the exterior of any metallic
enclosure. Be sure that the mounting area allows
for adequate wire bending radiuses per local and
national electrical codes.
The Core Module is installed by mounting on
standard 35mm DIN rail. The enclosure can be
mounted in any orientation. Secure the DIN rail
using a mechanical fastener such as sheet metal
screw or bolt to a secure surface.
158.7 mm
6.25”
59.2 mm
2.33”
108.54 mm
4.27”
158.7 mm
6.25”
59.2 mm
2.33”
108.54 mm
4.27”
Fig. 4: Core Module dimensions
Mount the enclosure on the DIN rail by lifting up
circlips and placing enclosure over the rail as
shown. Once rail is in place push the circlips down
to secure the enclosure in place.
125mm (5”)
7.5 mm
min.
35 mm
min. width
35 mm
DIN Rail
DIN Circlips
Unlock
Lock
125mm (5”)
7.5 mm
min.
35 mm
min. width
35 mm
DIN Rail
DIN Circlips
Unlock
Lock
Fig. 5: Core Module Installation
125mm (5”)
7.5 mm
min.
35 mm
min. width
35 mm
DIN Rail
DIN Circlips
Unlock
Lock