UMG 605US
Function
Symbol
Accuracy class
Measurem. range Display range
Neutral cond. current calculated INc
1.5 (IEC61557-12)
0.001 .. 25.5 A
0 A .. 9999 kA
Voltage
U L-N
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage
U L-L
0.5 (IEC61557-12)
18 .. 1000 V
rms
0 V .. 9999 kV
Power factor
PFA, PFV
2 (IEC61557-12)
0.00 .. 1.00
0 .. 1
Short-time flicker, long-time fl.
Pst, Plt
-
-
-
Voltage drops
Udip
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage rises
Uswl
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Transient overvoltages
Utr
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage interruptions
Uint
Du- 1 Zyklus
-
-
Voltage inbalance
1)
Unba
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage inbalance
2)
Unb
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage harmonics
Uh
Cl. 2
(IEC61000-4-7)
bis 2.5 kHz
0 V .. 9999 kV
THD of voltage
3)
THDu
2.0 (IEC61557-12)
bis 2.5 kHz
0 % .. 999 %
Explanations
1) Reference to amplitude.
2) Reference to phase and amplitude.
3) Reference to basic oscillation
4) Reference to effective value.
5) The accuracy class will degrade by
one step when measured with
a ../1A-current transformer.
6) Calculation from fundamental harmonic oscillation.
7) Precision class 0.5S per IEC62053-22
Содержание UMG 605US