40
UMG 605US
1,5k
+
-
4k
19
Digital
Input 1
3,9V
3,9V 4k
20
21
Digital
Input 2
24V
=
+
-
1,5k
24V
DC
S0 pulse input
At each UMG605US with inputs for 24 V
you can also connect S0 pulse generators
according to DIN EN 62053-31.
You require only one external auxiliary voltage
of 20..28 V DC and one external 1.5 kohm
resistor each.
Fig. 40.2 UMG605US with inputs for 24
V. Example for connection of an S0 pulse
generator at digital input 2.
S0 pulse
generator
UMG605US
Digital inputs 1-2
S0 pulse generator
Fig. 41.1 UMG605US with inputs for 24 V.
Example with S0 pulse generator.